EN
22
N32P-09
User's manual
13
While navigating the meter main menu with the groups of the parameters, the upper line of
the display shows the name of the group and the lower line continuously displays the word
MENU. After entering the group of the parameters (after pressing the confirm button), the
upper line displays the value of a given setting and the lower line shows the name of the
parameter which value is displayed in the upper line. Sample view of the selection of the
measured input signal type is shown in Fig. 9.
The buttons
allow to navigate the menu of the meter. After selecting the
group of the parameters which configuration is to be changed, press the confirm button to
move to the parameters of the group. The parameter which value is to be modified is
selected the same way as the selection of the group. To cancel the parameter change,
press the cancel button
to exit the parameter changing mode or the parameter
group. The meter will automatically exit the programming mode and return to displaying
the measuring value if no button is pressed for 30 seconds during programming. The
programming matrix is shown below.
Voltage measuring
range selection.
Current
measurement range
selection
Selection of the
synchronization
source
Rated voltage of the
voltage transformer
primary
Rated voltage of the
voltage transformer
secondary
Rated voltage of the
current transformer
primary
Rated voltage of the
current transformer
secondary
Single measurement
time as a multiple of
100 milliseconds.
Selection of
measuring quantities
values averaging
method (standard or
moving window
method).
Measuring quantities
values averaging
period in minutes.
Averaging
synchronization with
the time clock.
Value entered into
the import energy
counter when
resetting the counter.
Value entered into
the export energy
counter when
resetting the counter.
Pulse weight on a
binary output
Selection of the
counter controlling
the binary output
Fig. 8: View of meter menu.
Fig. 9: View of menu when setting a parameter.
Parameter
which can be configured
Current value
of a setting
N32P-09
User's manual
14
Reset (enter initial
value) energy
counter.
Selection of main
displayed value.
Minimum value on
the display. For
values lower than
this value, a lower
overrun message is
displayed.
Maximum value on
the display. For
values higher than
this value, an upper
overrun message is
displayed.
Resolution - position
of the decimal point.
Function of a lower
line of the display -
selection of a
quantity displayed in
the lower line.
Selection of quantity
controlling the alarm
state.
Selection of alarm
type.
Alarm state change
lower threshold.
Alarm state change
upper threshold.
Alarm activation
delay.
Alarm deactivation
delay.
Active alarm
memory.
Meter network
address.
Transmission frame
type - data format.
Baud rate.
Selection of the type
of analog output
used.
Selection of value
controlling the
analog output.
Value of the
controlling quantity
for which the output
will have a minimum
value, in accordance
with the selected
output type.
Value of the
controlling quantity
for which the output
will have a rated
value, in accordance
with the selected
output type.
Value on the analog
output in case of
manual control or an
error on the
measuring input.
Current time
according to the
internal clock.
Current date
according to the
internal clock.
Automatic change of
DST and inversely
Password to protect
against settings
modification.
Restore default
settings
5.3.1
How to change quantity of a selected parameter
To increase the value of the selected parameter, press the button
. Pressing the
button will increases the currently set digit by 1 and after reaching the value 9, pressing
the button will set the value 0. After setting the required value of a digit, move to the next
digit by pressing the button
. After setting the required parameter value, press the
confirm button
to accept the entered value or the cancel button
to cancel
the parameter change and return to the previous value of the parameter. It is possible to
change a sign of the entered value during setting the last digit (most significant).
There are three steps to change the floating point values. The first step is to set the digits
and a sign in accordance with the algorithm described above. The second step is set the
position of the decimal point after pressing the confirm button. The buttons
are used to set the position of the decimal point. After setting the decimal point position as
required, press the confirm button to move to the third step - setting the multiplier of kilo,
mega or no multiplier. Symbol of the multiplier value is shown on the left side of the