Sierra InnovaSonic 207i BACnet Скачать руководство пользователя страница 30

 

 

Page  30   

 

 

Enumerator 

Custom BACnet Unit Name 

Enumerator 

Custom BACnet Unit Name 

355 

  liters_per_day 

468 

  btu_per_hour 

362 

  cubic_meters_per_day 

469 

  btu_per_day 

364 

  cubic_feet_per_day 

470 

  million_btu 

420 

  million_gallons 

471 

  million_btu_per_second 

420 

  pounds_per_cubic_foot 

472 

  million_btu_per_minute 

421 

  usa_barrels 

473 

  million_btu_per_hour 

427 

  pounds_per_square_inch_absolute 

474 

  million_btu_per_day 

428 

  bar_absolute 

475 

  metric_tonnes 

438 

  imperial_barrels 

476 

  metric_tonnes_per_second 

439 

  imperial_barrels_per_second 

477 

  metric_tonnes_per_minute 

440 

  imperial_barrels_per_minute 

478 

  metric_tonnes_per_hour 

441 

  imperial_barrels_per_hour 

479 

  metric_tonnes_per_day 

442 

  imperial_barrels_per_day 

480 

  tons_refrigeration_per_second 

443 

  oil_barrels 

481 

  tons_refrigeration_per_minute 

444 

  oil_barrels_per_second 

482 

  tons_refrigeration_per_hour 

445 

  oil_barrels_per_minute 

483 

  tons_refrigeration_per_day 

446 

  oil_barrels_per_hour 

484 

  megapascals_absolute 

447 

  oil_barrels_per_day 

485 

  nanoseconds 

448 

  gigajoules 

486 

  kilograms_per_liter 

449 

  gigajoules_per_second 

487 

  killowatt_hours_per_second 

450 

  gigajoules_per_minute 

488 

  killowatt_hours_per_minute 

451 

  gigajoules_per_hour 

489 

  killowatt_hours_per_hour 

452 

  gigajoules_per_day 

490 

  killowatt_hours_per_day 

453 

  megajoules_per_second 

491 

megapascals_gauge 

454 

  megajoules_per_minute 

1000 

error 

Содержание InnovaSonic 207i BACnet

Страница 1: ...1 InnovaSonic 207i BACnet Instruction Manual BACnet Device Specification for 207i Ultrasonic Liquid Flow Meter Version IM 207i BACnet V2 3 19...

Страница 2: ...own Pu Dong New District Shanghai P R China Postal Code 201316 Phone 8621 5879 8521 Fax 8621 5879 8586 COPYRIGHT SIERRA INSTRUMENTS 2019 No part of this publication may be copied or distributed transm...

Страница 3: ...1 Configure Baud Rate and MAC Address with Smart Interface Portal SIP 11 3 2 Configure Baud Rate and MAC Address Using Local Display and Keypad 13 4 Supported BACnet Services Objects PICS 16 4 1 Acron...

Страница 4: ...ements or precautions may result in flow meter damage or malfunction Symbol Descripition To avoid potential electric shock follow National Electric Code safety practices or your local code when wiring...

Страница 5: ...echnical Support make sure to include this information The flow range serial number and Sierra order number all marked on the meter nameplate The software version visible at start up The problem you a...

Страница 6: ...one 1 year for calibration and non calibration defects from date of delivery To assure warranty service customers must register their products online on Sierra s website Online registration of all of...

Страница 7: ...C networks that is governed by the American Society of Heating Refrigerating and Air Conditioning Engineers ASHRAE SSPC 135 ANSI and ISO 16484 5 standard protocol The BACnet Master Slave Token Passing...

Страница 8: ...o prevent reflections RS 485 repeaters may be used to exceed 30 devices or to clean up the signal In some cases a pull up and pull down resistor may be used to stiffen the bus bias although most devic...

Страница 9: ...network wires to the RS 485 connections which are A B C isolated RS 485 ground Follow all RS 485 wiring practices See Figure 1 and Figure 2 The BACnet board has one dual LED that helps during trouble...

Страница 10: ...before installing any module Plug the BACnet Module into an open slot slot 12 normally and secure it with the four plastic screws provided You will need to temporarily remove the LCD to access the ba...

Страница 11: ...the SIP software on the Sierra website at sierrainstruments com 207isoftware 2 Connect the 207i to your computer via the USB cable provided in your shipment For more details on SIP installation refer...

Страница 12: ...twork and require a re boot to restore full network functions 1 Select On in the Off On Text field 2 Type in the BACnet MAC address in the Address field Acceptable number range 1 to 127 3 Choose your...

Страница 13: ...ing the local display and keypad on the meter follow the steps below 1 Press the key Pressing the key will bring you the top of the MAIN MENU 2 From the MAIN MENU scroll down to the Input Output menu...

Страница 14: ...creen in the BACnet setup area is the Off On Test menu Scroll down and select On to turn on the BACnet Module Press to go to Address screen 5 Once in the BACnet MAC Address menu type in your MAC addre...

Страница 15: ...y in the BACnet setup menu 7 Leave Parity on None and press the key twice to return to the MAIN MENU NOTE The Parity is always None regardless of the menu s selection CAUTION When configuring BACnet i...

Страница 16: ...ages show the implemented properties for each InnovaSonic 207i flow meter 4 1 Acronyms and Definitions Acronyms and Definitions Item Description APDU Application Protocol Data Unit BACnet Building Aut...

Страница 17: ...e DM DCC B Who Is Execute DS RPM B I Am Initiate DS WPM B Who Has Execute DS RP B I Have Initiate DS WP B Device Communication Control Execute 4 3 BACnet Supported Device Object and Property Table BAC...

Страница 18: ...APDU Length Accepted 480 Segmentation Supported No APDU Timeout 6000 Number Of APDU Retries 3 Max Master 127 Max Info Frames 1 Device Address Binding Database Revision 0 Flow AI 1 Object Identifier AI...

Страница 19: ...OS Totalizer AI 3 Object Identifier AI 3 Object Name POS Totalizer Object Type Analog Input Present Value 0 Description POS Flow Total Status Flags F F F F Event State NORMAL Out Of Service 0 Units as...

Страница 20: ...ut Of Service 0 Units as selected in 207i menu Energy Flow Rate AI 6 Object Identifier AI 6 Object Name Energy Flow Rate Object Type Analog Input Present Value 0 Description Energy Flow Rate of Fluid...

Страница 21: ...rgy Negative Total Status Flags F F F F Event State NORMAL Out Of Service 0 Units as selected in 207i menu Energy NET Total AI 9 Object Identifier AI 9 Object Name Net Energy Tot Object Type Analog In...

Страница 22: ...ject Type Analog Input Present Value 0 Description Signal Amplitude Status Flags F F F F Event State NORMAL Out Of Service 0 Units decibels Quality AI 12 Object Identifier AI 12 Object Name Quality Ob...

Страница 23: ...AI 14 Object Name Gain Object Type Analog Input Present Value 0 Description Gain at Amplifier Status Flags F F F F Event State NORMAL Out Of Service 0 Units percent Fluid Temp AI 15 Object Identifier...

Страница 24: ...per measurement menu Outlet Temp AI 17 Object Identifier AI 17 Object Name Outlet Temp Object Type Analog Input Present Value 0 Description Outlet Temperature Status Flags F F F F Event State NORMAL...

Страница 25: ...F F F F Event State NORMAL Out Of Service 0 Units as selected in 207i menu Inlet Enthalpy AI 20 Object Identifier AI 20 Object Name Inlet Enthalpy Object Type Analog Input Present Value 0 Description...

Страница 26: ...nput Present Value 0 Description Error Flag 1 Status Flags F F F F Event State NORMAL Out Of Service 0 Units no units Error Status2 AI 23 Object Identifier AI 23 Object Name Error Flag 2 Object Type A...

Страница 27: ...s Flag 1 Decoded by Bit Bit Function Description 0 1 ext_fram_err External FRAM memory error 1 2 ext_flash_err External Flash memory error 2 4 temp_err Internal control unit thermometer error or 20 C...

Страница 28: ...he totalizers remotely Just write one of the following decimal values 1 2 or 3 and then write a 0 If you do not do this the totalizers will keep resetting 0 Do nothing default state 1 Reset flow total...

Страница 29: ...By BACnet BACnet does not support absolute and gauge pressure so we have decided to assume gauge pressure For example psig will be displayed as pounds force per square inch and psia will use the cust...

Страница 30: ...ls_per_minute 478 metric_tonnes_per_hour 441 imperial_barrels_per_hour 479 metric_tonnes_per_day 442 imperial_barrels_per_day 480 tons_refrigeration_per_second 443 oil_barrels 481 tons_refrigeration_p...

Страница 31: ...unicating Sierra verifies the 207i is correct per the EIA RS 485 spec CAUTION We have found cases where other devices with A and B reversed and sometimes marked as A and B If in doubt swap A and B 2 E...

Отзывы: