Page 12
4.
Click on “BACnet MS/TP Setup” button.
Figure 5. 207i SIP BACnet MS/TP Setup
5.
In the “BACnet MS/TP Setup” screen, complete the configuration of your 207i for BACnet by doing the following:
WARNING |
Due to the way BACnet token passing works, duplicate addresses may lock
up the entire network and require a re-boot to restore full network functions.
1)
Select “On” in the “Off/On/Text” field.
2)
Type in the BACnet MAC address in the “Address” field. Acceptable number range 1 to 127.
3)
Choose your “Baud Rate”: 9600, 19200, or 38400.
4)
Once done, click the “Update Meter” button.
CAUTION |
When configuring BACnet, it is very
important that all of the devices on an
MS/TP bus communicate at the same baud rate: 9600, 19200 and 38400. Configure the
MAC (MS/TP) address between 1 to 127.
BACnet
MS/TP Setup