Interpretation of Markings.  
 

Markings on the outside of this gland carry the following meanings:  

Cable Gland Type & Size E-a-b-IE-c-FR-ddd-eee-IP67-nn   
 
a

  

= Seal Type  

1

 = Neoprene (black - temp range 

–20º to +85ºC)  

2

 = Neoprene with Continuity washer for lead sheathed cable  

3

 = Silicone (white or red - temp range 

–60º to +180ºC) ;  

b

  

=

 

Armour clamping  

W

 = single wire armour  

XZ

 = woven steel wire/tape   

L

  

= Kit for W and XZ  

IE

  

= Integral Earth stud option  

c

  

= Main component material  

none

 = brass  

S

 = stainless steel ;  

R  

= Optional reduced bore outer seal (red silicone)  

ddd

   = Gland size ;  

eee

   = Entry thread type and size ;  

IP67

   = Ingress Protection code  

nn

  

= year of manufacture  

 

Protection Concept and Gas Groups EEx d IIC / EEx e II 

(CENELEC & ATEX) ; 

Ex d IIC / Ex e II  

(IEC) ; Ex d = Flameproof ; IIC = suitable for Gas Group IIC (e.g. 

hydrogen) ignitable gas/air mixtures, and also Groups IIB and IIA ; II = combined 
Gas Group  

Certificate Numbers

(ATEX) 

KEMA 06ATEX0105 

The ‘X’ suffix denotes Special Conditions for Safe Use’ (see 

below)    

 

ATEX (EU Directive 94/9/EC) Markings 

 

II 2 GD

 - Equipment Group II (Non-Mining) for Category 2 (Zone 1) with 

potentially explosive gas mixtures or combustible dusts  

 

ATEX Special Conditions for Safe Use 

 

1.  These glands must not be used with EEx d IIC enclosures with a volume greater 

than 2 litres.  

2.  These glands must not be used with enclosures where the temperature at the 

point of mounting exceeds -20°C to +85°C using neoprene seals, or 

–60° to 

+180°C using silicone seals.  

IEC Ex Conditions of Certification 

 

Содержание 640S-EEX

Страница 1: ...Appendix for ATEX Certified EX Units Instruction Manual Sierra Instruments Model 640S EEX and 780S EEX Flow Transmitters Part Number IM ATEX Rev C 1 October 2013...

Страница 2: ...nsible for cleaning the mass flow meter to the degree required for your oxygen flow application COPYRIGHT SIERRA INSTRUMENTS 2013 No part of this publication may be copied or distributed transmitted t...

Страница 3: ...he ATEX Approved Equipment 6 4 2 Mounting Commissioning and Operation 6 4 3 Explosive Hazardous Area 6 4 4 Special Conditions for a Safe Use 7 4 5 Particular Recommendations Closing the Cover 7 5 Remo...

Страница 4: ...pril 1994 KEMA ATEX official label from Sierra Instruments Inc The following information is provided as part of the labeling of the transmitter Name and address of the manufacturer Sierra Instruments...

Страница 5: ...ea in which an explosive gas atmosphere is likely to occur in normal operation occasionally Zone 2 Area in which an explosive gas atmosphere is not likely to occur in normal operation and if it does o...

Страница 6: ...ed changes may arise For this reason the instrument must be installed connected operated and maintained according to the instructions in this and the specific product operating manual Persons handling...

Страница 7: ...SME B1 20 1 NOTE Please insure that when you mount these cable glands they are made up wrench tight At least 31 2 turns of the thread must be engaged inside of the electronics enclosure 4 4 Special Co...

Страница 8: ...ew in the edge of the dome Unscrew the set screw and screw the dome from the housing Record the color of the wires to terminals 16 thru 20 Disconnect the sensor wires See diagram below Fig 2 Wiring di...

Страница 9: ...e external earthing connection is located on the boss on the outside of the housing and consist of an 316SS screw 10 24 UNC 2B tread seal spring washer and cable shoe crimp lug suited for maximum 3 mm...

Страница 10: ...r Service at www sierrainstruments com or 831 373 0200 in the USA or 31 0 72 5071400 in Europe Return shipments to USA Headquarters Sierra Instruments Inc Attn Customer Service Department 5 Harris Cou...

Страница 11: ...nds are for indoor use and offer IP54 environmental protection A termination suitable for EMC protection can be made using armoured cables with these glands Clamp options allow woven steel wire and st...

Страница 12: ...on For lead sheathed cable the lead sheath must pass through the Continuity Washer when installation is complete B Expose armour approx 20mm long 5 Slide Cone onto inner sheath and under armour Slide...

Страница 13: ...or taper threads use thread sealant Also see page 1 diagram and Hole Data above 5 The surface of the enclosure should be sufficiently flat and rigid to make both the IP joint and earth contact where n...

Страница 14: ...tection code nn year of manufacture Protection Concept and Gas Groups EEx d IIC EEx e II CENELEC ATEX Ex d IIC Ex e II IEC Ex d Flameproof IIC suitable for Gas Group IIC e g hydrogen ignitable gas air...

Страница 15: ...1 These glands are certified with one specific size of flameproof sealing ring per gland size as supplied 2 These glands must not be used with enclosures where the temperature at the point of mounting...

Отзывы: