Technical data  

Metrological accuracy class  

3 as per EN 1434 
ratio q

s

  / q

 = 2 : 1 

ratio q

p

  / q

 = 25 : 1 vertical 

ratio q

p

  / q

 = 50 : 1 horizontal  

Environmental class  

A as per EN 1434 

Energy unit  

Standard 
On request 

 
kWh 
GJ 

Flow values  

Minimum flow q

i

  

   Horizontal  
   Vertical 
Nominal flow q

p

  

Maximum flow q

 

Starting value – horizontal  

0.6 m

3

/h 1.5 

m

3

/h 2.5 

m

3

/h 

 
12 l/h 

30 l/h 

50 l/h 

24 l/h 

60 l/h 

100 l/h 

600 l/h 

1500 l/h 

2500 l/h 

1200 l/h 

3000 l/h 

5000 l/h 

4 l/h 

10 l/h 

16 l/h 

Upper limit of thermal power P

S

 0.6 

m

3

/h 1.5 

m

3

/h 2.5 

m

3

/h 

125 

kW 313 

kW 523 

kW 

Quality of heating water 

VDI guide line 2035 
(VDI – union of german engineers) 

Max. permissible operating pressure  

10 bar 

Range of use – flow meter  

15… 90 °C 

Temperature measurement 

temperature range of sensor  
temperature difference   

 
15…105 °C 
3…90 K 

Behaviour of  flow 

Flow 

 2,1 ×* q

p

 

Flow > 2,1 × q

p

 

 
Linear 
Constant 

Permissible ambient temperature  

Transport and storage 
Operation 

 
–20 °C .. +70 °C 
+5 °C .. +55 °C  

Battery life time 

10 years + ½ years  

Connection sizes and mass  

threaded end connections  
Installation length  
Mass 

0.6 m

3

/h 1.5 

m

3

/h 1.5 

m

3

/h 2.5 

m

3

/h 

G¾B G¾B G¾B G1B 
110 mm 

80 mm 

110 mm  130 mm

0,620 kg

 

0,565

 

kg 0,604 

kg  0,686 

kg 

Temperature sensor  

Temperature sensing element 
Temperature probe type 
Response time 

τ

0,5 

 

Diameter of

 

protective sheath

 

Connecting lead 

 
Pt 1000 as per EN 60751 
Short DS 

3.5 s 

5 mm 
1.5 m 

Standards, CE 

EN 61000-4-3:2002+A1:2002     

 

DIN EN 61000-4-Parts 2, 4, 8 

 

DIN EN 55022 

 

DIN EN 1434, (1997, 2002) 

 

Содержание WFM407 series

Страница 1: ...inal flow of 0 6 m3 h 1 5 m3 h and 2 5 m3 h The electronic SiemecaTM heat meter can be read out and parameterized via an IrDa interface Application The heat meter is used for measuring heat energy The major areas of application are heating systems with central heating facilities in which the heating energy is supplied to several consumers as required This is useful in Apartment buildings Offices a...

Страница 2: ...t Integrated Return WFM407 D119 2 5 m3 h 130 mm 1 5 m Indirect Integrated Return WFM407 E139 Place of installation Inlet Nominal Flow qp Installation Length Cable Length Immersed Flow Sensor Place of Installation Type Ref 0 6 m3 h 110 mm 1 5 m Direct Integrated Flow WFP407 B113 1 5 m3 h 110 mm 1 5 m Direct Integrated Flow WFP407 D113 2 5 m3 h 130 mm 1 5 m Direct Integrated Flow WFP407 E133 1 5 m h...

Страница 3: ...r 130 mm installation length return sensor indirectly immersed flow sensor in immersion sleeve WFZ E130 IT For 130 mm installation length return sensor directly immersed flow sensor in ball valve WFZ E130G1 I For 130 mm installation length return sensor indirectly immersed flow sensor in immersion sleeve WFZ E130G1 IT Scope of delivery installation sets WFZ Accessories E80 E80G3 E110 I E110 IT E11...

Страница 4: ...t meter with 110 mm installation length and 30 April as due date WFM407 B113 Due date April Technology The meter operates according to the single jet measuring principle The water flows against an impeller its speed is scanned electronically and without a magnetic field The temperatures in the flow and return are measured with immersion sensors Pt1000 platinum measuring elements The heat meter is ...

Страница 5: ...connected to the pipe it is made of brass and contains the metering chamber with the single jet impeller sensor The inlet connection has a filter to trap large dirt particles The heat meter is a compact version The calculator contains the electronics and the 8 digit display LCD The operating voltage of DC 3 V is supplied by a lithium battery The IrDA interface for automatically reading out the rea...

Страница 6: ...ed at the inlet in front of the device 150 mm for installation lengths of 80 mm and 110 mm 200 mm for an installation length of 130 mm If the device is only to be used when starting up the spacer can be mounted first Before installing the meter rinse the pipe well mount the spacer for this purpose When installing observe the flow sign an arrow on the flow meter If tees of a different brand are use...

Страница 7: ...line 2035 VDI union of german engineers Max permissible operating pressure 10 bar Range of use flow meter 15 90 C Temperature measurement temperature range of sensor temperature difference 15 105 C 3 90 K Behaviour of flow Flow 2 1 qp Flow 2 1 qp Linear Constant Permissible ambient temperature Transport and storage Operation 20 C 70 C 5 C 55 C Battery life time 10 years years Connection sizes and ...

Страница 8: ...h 130 mm This Data Sheet only contains general descriptions and technical features which in the case of specific applica tions may not necessarily apply or which may change due to further development of the product Technical details and features are binding only if explicitly agreed upon at the time of contract closure 2005 Siemens Building Technologies Subject to alterations ...

Отзывы: