Type list – Accessories  

Accessories 

Description, scope of delivery 

Type Ref. 

Spacer 

For installation length of 80 mm, external thread ¾” 

WFZ.R80 

Spacer 

For installation length of 110 mm, external thread ¾” 

WFZ.R110 

Spacer 

For installation length of 130 mm, external thread 1”  

WFZ.R130 

Ball valve  

Internal thread ½”, with sensor seat  

WFZ.K15 

Ball valve 

Internal thread ¾”, with sensor seat  

WFZ.K18 

Ball valve 

Internal thread 1”, with sensor seat  

WFZ.K22 

Tee 

Internal thread ½”, with immersion sleeve M10×1 

WFZ.T16 

Tee 

Internal thread ¾”, with immersion sleeve M10×1 

WFZ.T19 

Tee 

Internal thread 1”, with immersion sleeve M10×1 

WFZ.T22 

Threaded joints 

Profipress G-Adapter with SC-Contur, gunmetal, female thread, 15× ½”  

WFZ.P2 

Threaded joints 

Profipress G-Adapter with SC-Contur, gunmetal, female thread, 18× ¾”  

WFZ.P2-1 

Parameterisation and 
diagnosis tool  

PC-software tool (additional tool required: with USB-Tool set 
WHZ3.USB or IrDA interface F12150-2018 on Com (RS232) port) 

ACT20 

Order 

When ordering, specify the type reference according to the type overview. The stan-
dard electronic Siemeca

TM

 heat meter has an IrDA interface. 

If a due date other than the 31 December is desired, the desired month should also be 
entered in addition to the type reference (the last day of a month is always the due 
date).  
Order model for a heat meter with 

110

 mm installation length and 30 April as due date: 

WFM407.B113, Due date: April

 

Technology 

The meter operates according to the single-jet measuring principle. The water flows 
against an impeller; its speed is scanned electronically and without a magnetic field. 
The temperatures in the flow and return are measured with immersion sensors Pt1000 
(platinum measuring elements).  

The heat meter is equipped either for installing in the return or in the flow. Please select 
the corresponding meter from the type list for the place of installation. 
The flow is continuously measured in the calculator and at least once every minute the 
flow and return temperature. A microprocessor in the calculator determines the differ-
ence in temperature and calculates the consumed quantity of heat based on the aver-
age flow and the heat coefficient. 

The heat consumption values are totalled continuously. The current state is saved on 
the next due date at 24.00 h.  
The due date can be factory-programmed; the standard due date is entered as 
31 December (compare «Order») 
When the annual consumption is saved, the heat meter simultaneously calculates a 
control number.  After special parameterisation with ACT20 service software the check-
sum is readable. Self-readers must inform the utility company/property management of 
this control number and the due date value that has been read out so that they can 
check that the display has been read correctly.  
The due date value remains saved for one year. 

 

Measuring principle  

Determination of heat 
consumption 

Saving of consump-
tion values  

Содержание WFM407 series

Страница 1: ...inal flow of 0 6 m3 h 1 5 m3 h and 2 5 m3 h The electronic SiemecaTM heat meter can be read out and parameterized via an IrDa interface Application The heat meter is used for measuring heat energy The major areas of application are heating systems with central heating facilities in which the heating energy is supplied to several consumers as required This is useful in Apartment buildings Offices a...

Страница 2: ...t Integrated Return WFM407 D119 2 5 m3 h 130 mm 1 5 m Indirect Integrated Return WFM407 E139 Place of installation Inlet Nominal Flow qp Installation Length Cable Length Immersed Flow Sensor Place of Installation Type Ref 0 6 m3 h 110 mm 1 5 m Direct Integrated Flow WFP407 B113 1 5 m3 h 110 mm 1 5 m Direct Integrated Flow WFP407 D113 2 5 m3 h 130 mm 1 5 m Direct Integrated Flow WFP407 E133 1 5 m h...

Страница 3: ...r 130 mm installation length return sensor indirectly immersed flow sensor in immersion sleeve WFZ E130 IT For 130 mm installation length return sensor directly immersed flow sensor in ball valve WFZ E130G1 I For 130 mm installation length return sensor indirectly immersed flow sensor in immersion sleeve WFZ E130G1 IT Scope of delivery installation sets WFZ Accessories E80 E80G3 E110 I E110 IT E11...

Страница 4: ...t meter with 110 mm installation length and 30 April as due date WFM407 B113 Due date April Technology The meter operates according to the single jet measuring principle The water flows against an impeller its speed is scanned electronically and without a magnetic field The temperatures in the flow and return are measured with immersion sensors Pt1000 platinum measuring elements The heat meter is ...

Страница 5: ...connected to the pipe it is made of brass and contains the metering chamber with the single jet impeller sensor The inlet connection has a filter to trap large dirt particles The heat meter is a compact version The calculator contains the electronics and the 8 digit display LCD The operating voltage of DC 3 V is supplied by a lithium battery The IrDA interface for automatically reading out the rea...

Страница 6: ...ed at the inlet in front of the device 150 mm for installation lengths of 80 mm and 110 mm 200 mm for an installation length of 130 mm If the device is only to be used when starting up the spacer can be mounted first Before installing the meter rinse the pipe well mount the spacer for this purpose When installing observe the flow sign an arrow on the flow meter If tees of a different brand are use...

Страница 7: ...line 2035 VDI union of german engineers Max permissible operating pressure 10 bar Range of use flow meter 15 90 C Temperature measurement temperature range of sensor temperature difference 15 105 C 3 90 K Behaviour of flow Flow 2 1 qp Flow 2 1 qp Linear Constant Permissible ambient temperature Transport and storage Operation 20 C 70 C 5 C 55 C Battery life time 10 years years Connection sizes and ...

Страница 8: ...h 130 mm This Data Sheet only contains general descriptions and technical features which in the case of specific applica tions may not necessarily apply or which may change due to further development of the product Technical details and features are binding only if explicitly agreed upon at the time of contract closure 2005 Siemens Building Technologies Subject to alterations ...