Siemens VN2001-A1 Скачать руководство пользователя страница 3

A6V10370415_en--_a                                              3 

 

 

 

MOUNTING 

Mounting the VN2001-A1 Ethernet Module, 10/100 BaseTx, in a Voice Network of FV2025/2050 Fire 
Voice Control Panels 

CAUTION:  Power down the Voice Panel before mounting the VN2001-A1. 

1.  Open the middle door of the FV2025/2050 Fire Voice Control Panel. 

2.  Unscrew the latch on the front of the Card Cage and remove the Card Cage cover. 

3.  If a VCC2001-A1 Voice CPU is installed in card slot X202, remove it. If no VCC2001-A1 is 

installed, proceed to the next step. 

4.  Referring to Figure 4, if the two knockouts for Ethernet modules are still present in the Card 

Cage top panel, remove them. To avoid damage to sensitive electronic components, remove 
any burrs that may be present in the knockout opening. 

5.  Install the VCC2001-A1 Voice CPU card into card slot X202 according to instructions provided in 

Siemens Industry, Inc., Building Technologies Division, document number A6V10397772 

Installation Instructions for the Model VCC2001-A1 Voice CPU Card.

 

Figure 4 
Removing knockouts for Ethernet Modules  

6.  Refer to the site specific shop drawings to determine which position on the Voice CPU Card the 

module is to be installed in. 

7.  Insert the VN2001-A1 through the specified knockout opening on top of the VCA2002-A1 Card 

Cage and carefully press it into the multi-pin connector mounted on the VCC2001-A1 Voice 
CPU card. The multi-pin connector is located approximately 2

1

/

2

” below the knockout opening, 

as illustrated in Figure 5.  Install the second module for the other link in the same manner 
through the remaining knockout opening. 

8.  Tighten the fastening pin on the top of each module (see Figure 5) by turning it clockwise until 

KNOCKOUTS FOR 
ETHERNET MODULES 

COVER LATCH 

CARD CAGE COVER 

COVER GUIDE 

CARD CAGE TOP PANEL 

COVER GUIDE 

Содержание VN2001-A1

Страница 1: ... over Ethernet PoE 24V 500mA user selectable Can be used in the UL and ULC markets PRE INSTALLATION 1 Determine from the site specific shop drawings whether the VN2001 A1 should be set for ground fault supervision alone Power over Ethernet PoE plus ground fault supervision or neither function 2 For ground fault supervision alone set the jumpers as illustrated in Figure 2a For Power over Ethernet p...

Страница 2: ...uctions for the Model VN2002 A1 Ethernet Module MM and the Model VN2003 A1 Ethernet Module SM The backbone is a dual self healing redundant ring network that is able to detect failures and then automatically isolate and recover from them using an alternate routing VOICE CARD CAGE VOICE CARD CAGE VOICE CARD CAGE COPPER FIBER ETHERNET BACKBONE NETWORK FV2025 2050 PANEL FV2025 2050 PANEL FV2025 2050 ...

Страница 3: ...ot X202 according to instructions provided in Siemens Industry Inc Building Technologies Division document number A6V10397772 Installation Instructions for the Model VCC2001 A1 Voice CPU Card Figure 4 Removing knockouts for Ethernet Modules 6 Refer to the site specific shop drawings to determine which position on the Voice CPU Card the module is to be installed in 7 Insert the VN2001 A1 through th...

Страница 4: ... sliding it downward until it reaches bottom 10 Screw the cover latch back into the Card Cage cover Mounting the VN2001 A1 Ethernet Module 10 100 BaseTx in an FN2012 A1 Ethernet Switch Modular 1 Remove the screws fastening the cover to the body of the FN2012 A1 Ethernet Switch modular and lift the cover off the assembly 2 Please refer to Figure 6 If necessary remove one of the knockouts in the FN2...

Страница 5: ...ns for installing the VN2001 A1 onto the VCC2001 A1 Voice CPU card or into an FN2012 A1 Ethernet Switch modular When using the VN2001 A1 Ethernet Module 10 100 BaseTx to connect FV2025 2050 Panels consult the site specific shop drawings for instructions on cabling FV2025 2050 Panels together to establish Ethernet rings A single multi conductor cable is used to connect from one module to the next i...

Страница 6: ...V10370415_en _a 6 ELECTRICAL RATINGS VN2001 A1 Ethernet Module 10 100 BaseTx Power Requirements Ethernet option no PoE Aux 20 30VDC 35mA max MoNET 36mA With PoE active Aux 20 30VDC 35mA max MoNET 36mA max ...

Страница 7: ...A6V10370415_en _a 7 This page has been left intentionally blank ...

Страница 8: ...ft intentionally blank Siemens Industry Inc Siemens Canada Limited Document ID A6V10370415_en _a Building Technologies Division Building Technologies Division P N A5Q00054390 Florham Park NJ 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada ...

Отзывы: