1. 

OPERATION 

The VN2001-A1 Ethernet Module (10/100 BaseTx) can be used both in Voice networks of FV2025/2050 
Fire Voice Control Panels and in generic Ethernet systems. 

Operation in a Voice Network

 

of FV2025/2050 Fire Voice Control Panels

 

The VN2001-A1 Ethernet Module (10/100 BaseTx) is an optional card that plugs into the VCC Card Cage to 
provide an electrical interface for an Ethernet backbone network of FV2025/2050 Fire Voice Control Panels 
(see Figure 3). Each link in a Backbone is independently of any other link.  It can be implemented as either 
copper wire or fiber-optic cable without any regard to what is used for the other links in the network.  

NOTE: 

For installation instructions applicable to fiber-based links,

 

see Siemens Industry, Inc., Building 

Technologies Division, document number A6V10370419 

Installation Instructions for the Model 

VN2002-A1 Ethernet Module (MM) and the Model VN2003-A1 Ethernet Module (SM)

The backbone is a dual self-healing, redundant, ring network that is able to detect failures and then 
automatically isolate and recover from them using an alternate routing. 

VOICE CARD 
CAGE

VOICE CARD 
CAGE

VOICE CARD 
CAGE

COPPER / FIBER ETHERNET BACKBONE 

NETWORK

FV2025/2050 

PANEL

FV2025/2050 

PANEL

FV2025/2050 

PANEL

VN2001-A1 (10/100 BASE Tx) 

OR

 VN2002-A1 (MM)

OR

VN2003-A1 (SM) ETHERNET 

MODULES

 

Figure 3 
Ethernet Network Topology in a Voice Network of FV2025/2050 Panels 

Operation in a Generic Ethernet Network

  

In addition to its use in an Ethernet backbone network of FV2025/2050 Fire Voice Control Panels (as 
illustrated in Figure 3), the VN2001-A1 Ethernet Module (10/100 BaseTx) can also be used to support copper 
wire connections among standalone FN2012-A1 Ethernet Switches (modular).  

Controls and Indicators 

The two LEDs on the VN2001-A1 which are located at the copper cable connector indicate the following: 

Green   = Link established 
Yellow   = Signal activity 

Содержание VN2001-A1

Страница 1: ... over Ethernet PoE 24V 500mA user selectable Can be used in the UL and ULC markets PRE INSTALLATION 1 Determine from the site specific shop drawings whether the VN2001 A1 should be set for ground fault supervision alone Power over Ethernet PoE plus ground fault supervision or neither function 2 For ground fault supervision alone set the jumpers as illustrated in Figure 2a For Power over Ethernet p...

Страница 2: ...uctions for the Model VN2002 A1 Ethernet Module MM and the Model VN2003 A1 Ethernet Module SM The backbone is a dual self healing redundant ring network that is able to detect failures and then automatically isolate and recover from them using an alternate routing VOICE CARD CAGE VOICE CARD CAGE VOICE CARD CAGE COPPER FIBER ETHERNET BACKBONE NETWORK FV2025 2050 PANEL FV2025 2050 PANEL FV2025 2050 ...

Страница 3: ...ot X202 according to instructions provided in Siemens Industry Inc Building Technologies Division document number A6V10397772 Installation Instructions for the Model VCC2001 A1 Voice CPU Card Figure 4 Removing knockouts for Ethernet Modules 6 Refer to the site specific shop drawings to determine which position on the Voice CPU Card the module is to be installed in 7 Insert the VN2001 A1 through th...

Страница 4: ... sliding it downward until it reaches bottom 10 Screw the cover latch back into the Card Cage cover Mounting the VN2001 A1 Ethernet Module 10 100 BaseTx in an FN2012 A1 Ethernet Switch Modular 1 Remove the screws fastening the cover to the body of the FN2012 A1 Ethernet Switch modular and lift the cover off the assembly 2 Please refer to Figure 6 If necessary remove one of the knockouts in the FN2...

Страница 5: ...ns for installing the VN2001 A1 onto the VCC2001 A1 Voice CPU card or into an FN2012 A1 Ethernet Switch modular When using the VN2001 A1 Ethernet Module 10 100 BaseTx to connect FV2025 2050 Panels consult the site specific shop drawings for instructions on cabling FV2025 2050 Panels together to establish Ethernet rings A single multi conductor cable is used to connect from one module to the next i...

Страница 6: ...V10370415_en _a 6 ELECTRICAL RATINGS VN2001 A1 Ethernet Module 10 100 BaseTx Power Requirements Ethernet option no PoE Aux 20 30VDC 35mA max MoNET 36mA With PoE active Aux 20 30VDC 35mA max MoNET 36mA max ...

Страница 7: ...A6V10370415_en _a 7 This page has been left intentionally blank ...

Страница 8: ...ft intentionally blank Siemens Industry Inc Siemens Canada Limited Document ID A6V10370415_en _a Building Technologies Division Building Technologies Division P N A5Q00054390 Florham Park NJ 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada ...

Отзывы: