GAMMA
instabus
Technical Product Information
February 2010
Blind actuator UP 520/31
5WG1 520-2AB31
Siemens AG
UP 520/31, 4 pages
Technical Manual
Industry Sector, Building Technologies
Low Voltage Distribution
© Siemens AG 2010 Update:
http://www.siemens.com/gamma
PO Box 10 09 53, D-93009 Regensburg
Subject to change without further notice
2.10.1.18/1
Product and Function Description
Photo
The blind actuator receives telegrams from sensors via the
Instabus and controls a shutter or blind motor with its
output. Both travel directions are mechanically
interlocked. With sun protection or positioning telegrams,
the actuator offers moreover the possibility of moving
shutters, blinds and slats into any desired position. On
reception of a storm warning, the actuator is capable of
moving shutters or blinds into a predefined safety position
and to lock them up in this position.
In addition, the device has two extension inputs that
depending on parameter settings, can act directly on the
output (local operation, see “state of delivery”) or
alternatively also as binary inputs on the Instabus. The
connected potential-free switch or push button contacts
are read in via a common reference potential on the
actuator. As binary input, telegrams can be transmitted for
switching or dimming, for Venetian blind control, value
setting or scene recall / save.
State of delivery:
•
When delivered, the switching state of the outputs is
undefined.
•
On application of the bus voltage, the relays will switch
off.
•
With the bus voltage applied, the extension inputs
control the relays of the actuator as follows:
input Operation
behavior
short
stop / slat up
A
long move
up
short
stop / slat down
B
long move
down
Simultaneous actuation of A and B is not possible
Application program
12 A1S2 Shutter, 2x Input 207301
•
2 binary inputs
o
ON / OFF / TOGGLE switching
o
Value setting
o
Dimming
o
Blind / Shutter – control
o
Scene control
o
Inputs blocking function
o
Behavior on bus power restoration
•
1 channel with additional functions
o
Sun protection function
o
Safety function
o
Adjustable response after bus voltage
failure
o
Adjustable response to bus voltage return
o
Adjustable priority of sun protection
function and manual operation