Log functions 

Logbook 

In  the  internal  logbook,  metrologically  relevant 
events  (errors,  states,  actions)  are  stored  in 
chronological  order  with  their  time  of  occurrence. 
The events acquired are predefined. The data of the 
logbook cannot be deleted. 
Each  event  is  stored  in  a  separate  4-level  shift 
register;  the  overflows  are  transferred  to  a  25-level 
circulating buffer. Therefore, at least the last 4 times 
can be traced for each event. 
In  a  monthly  register,  the error states are stored for 
the  current  month  and  for  the  past  18  months 
(without time stamp). 

Ser
No. 

Type 

Description 

F0 = Air in measuring tube 

F1 = Interruption flow sensor 

F2 = Interruption return sensor 

F3 = Error temperature electronics 

F5 = Short-circuit flow sensor 

F6 = Short-circuit return sensor 

F8 = Sensor error > 8 hours 

Er

ro

o

c

c

u

rs

 o

b

a

c

k

-t

o

 n

o

rm

a

F9 = ASIC error 

Above max. temperature in the volume 

measuring unit  

10 

Below min. temperature in the volume 

measuring  

11 

Max. flowrate qs was exceeded 

12 

Soiling prewarning 

13 

Line voltage off 

14 

St

a

te

 o

c

c

u

rs

 o

e

n

d

s

 

CRC error occurred 

15 

Adjustment values parameterized 

16 

F7-(EEPROM) pre-warning 

17 

Reset made 

18 

Date / time parameterized 

19 

Yearly set day parameterized 

20 

Monthly set day parameterized 

21 

Master reset performed 

22 

All times deleted 

23 

Missing time deleted 

24 

Ev

e

n

o

c

c

u

rs

 

Maxima deleted 

Read-out  is  performed  via  the  optical  interface  with 
the service software. 

 

 

Data logger

 (optional) 

The data logger permits the archiving of data that the 
user can select from a predefined set of values. The 
data logger contains four archives whose 8 channels 
can be assigned. 
The data can be assigned to any of the channels. 

Archive 

Timebase 

Storage 

depth 

Averaging 

time for 

maximum 

Hourly 

archive 

1 hour 

45 days 

1 hour *) 

Daily 

archive 

1 day 

65 days 

1 hours 

Monthly 

archive 

1 month 

15 months 

1 hours 

Yearly 

archive 

1 year 

15 years 

1 hours / 
24 hours 

*)  For  a  shorter  measuring  period  than  1  hour,  the 
largest  value  from  the  maximum  values  calculated 
within one hour applies. 
The  data  are  recorded  with  the  value  and  time 
stamp. 
Parameterizing  and  read-out  is  performed  via  the 
optical interface with the service software . 
Note: Data transmission is in a manufacturer-specific 
format. 

Value set for data to be recorded 

Meter readings 
at the end of the period 
for... 

Quantity of energy 
Tariff register 1, 2, 3 
Volume 
Operating duration *) 
Fault duration *) 
Pulse input 1 
Pulse input 2 
*) depending on parameter 
setting: hours or days 

Instantaneous values 
at the end of the period 
for... 

Power 
Flowrate 
Flow temperature 
Return temperature 
Temperature difference 
Error display 

Maximum for... 

Power 
Flowrate 
Flow temperature 
Return temperature 
Temperature difference 

 
 

Содержание UH50 FLOW SENSOR

Страница 1: ...prior notice UH 106 101k Page 1 15 Static Heat and Cold Meter UH50 issue January 2010 Configuration Instructions UH 106 101k Static meter for Heating and Cooling systems UH50 ULTRAHEAT UH50 ULTRACOLD UH50 FLOW SENSOR Version of firmware 5 15 and higher ...

Страница 2: ...l voids the warranty The 110 V 230 V versions must only be connected by an electrician The lithium batteries must be properly returned Lightning protection cannot be ensured this must be provided by the building wiring Only one compartment for the power supply must be equipped do not remove the red locking hatch General information The UH50 meter is used for energy consumption metering in short an...

Страница 3: ... 6 10 G 2 20 100 40 300 1 5 190 3 5 260 7 35 14 60 14 4 5 1 5 190 2 5 G 1 5 25 10 200 5 6 1 8 0 5 190 1 5 3 15 6 1 2 G 1 160 3 8 0 6 1 2 6 2 4 150 1 5 14 4 5 G 1 260 12 60 24 180 Tolerance pressure lost 5 Small meters qp 0 6 2 5 m h Overall length 110 mm thread Overall length 130 mm thread Overall length 190 mm thread Overall length 190 mm flange Large meters with threaded joint qp m h PN bar a b ...

Страница 4: ... removable control cable may be separated during the installation When installation is done be sure that only paired parts volume part calculator are connected together Ball valve Example of mounting with a ball valve recommended up to DN25 Welded sleeve with pocket Example of mounting with pockets recommended above DN25 Mounting as a cold meter When mounting a cold meter or combined heat cold met...

Страница 5: ...ction of service loops LOOP 1 n Service loop selection Service loop 1 Service loop 2 LOOP n Service loop n LCD button 1 advances the display to the next loop After the last loop the user loop LOOP 0 appears again LCD button 2 displays the content of the selected service loop Within a loop the LCD button 2 is used to advance to the next line of the display After the last line of the display the fir...

Страница 6: ... flow temperature and return temperature with their date stamp for up to 60 months on the set day of each month Note The standard time used is Central European Time CET If daylight saving time is activated storage will be performed accordingly The monthly values can also be read out via the optical and the 20 mA interface Resolution of the display kWh MWh MJ GJ m Places after decimal point blinkin...

Страница 7: ... rigid or flexible 0 2 2 5 mm flexible with end ferrules 0 25 1 5 mm conductor sizes 26 14 AWG Multiple conductor connection 2 conductors of same cross section rigid or flexible 0 2 0 75 mm flexible with end ferrules without plastic sleeve 0 25 0 34 mm flexible with TWIN ferrules with plastic sleeve 0 5 0 75 mm Recommended screwdriver 0 6 x 3 5 mm Tightening torque 0 4 Nm Permissible combinations ...

Страница 8: ...d version A special version of the pulse module is available with an Opto MOS output Advantages low voltage drop and polarized bipolar Standard pulses Standard pulse significances kWh MJ m 10 15 25 40 2 5 3 5 60 Nom flowrate in m h 10 MJ 0 6 1 kWh 10 kWh 1 m 0 1 m 100 MJ 1 MJ depending on the unit for heat display Pulses for quantity of energy volume tariff register Period duration 200 ms Pulse du...

Страница 9: ...The analog module converts a selectable measured value of the meter into an analog output signal 2 output signals channel 1 channel 2 The following measured values can be selected power Flowrate Flow temperature Return temperature Temperature difference The following can be selected as the output signal 0 20 mA 4 20 mA 0 10 V Radio module Display on LCD RM radio module Please read the appropriate ...

Страница 10: ...ature from the defined return temperature threshold instead of from the temperature difference Above return threshold T1 is summated Below return threshold T2 is summated Display of the tariff situation on the LCD The current tariff status is shown in the user loop together with the quantity of energy or the volume No tariff status is shown for tariffs T7 and T8 for tariffs T2 T3 T4 T5 T6 T10 T11 ...

Страница 11: ... 20 Monthly set day parameterized 21 Master reset performed 22 All times deleted 23 Missing time deleted 24 Event occurs Maxima deleted Read out is performed via the optical interface with the service software Data logger optional The data logger permits the archiving of data that the user can select from a predefined set of values The data logger contains four archives whose 8 channels can be ass...

Страница 12: ... 5 m h length 110mm nominal pressure PN25 connection G B 22 Nominal flowrate 1 5 m h length 190mm nominal pressure PN16 connection G 1 B 23 Nominal flowrate 1 5 m h length 190mm nominal pressure PN25 connection flanged DN 20 24 Nominal flowrate 1 5 m h length 190mm nominal pressure PN25 connection G 1 B 25 Nominal flowrate 1 5 m h length 130mm nominal pressure PN16 connection G 1 26 Nominal flowra...

Страница 13: ...r Pt500 removable mounting in the tube as an option G Sensor Pt500 removable mounted in the tube within a pocket H Sensor Pt100 not removable not mounted in the tube N Sensor Pt100 not removable mounted in the tube P Sensor Pt100 not removable mounting in the tube as an option R Sensor Pt100 not removable mounted in the tube within a pocket S Hardware dependent features 7 Sensor type Code Without ...

Страница 14: ...GSM Module with 2 pulse inputs with battery SMS support WZU GM GPRS module with ext antenna magnetic attachment and UH50 power pack 110 230V cable 5m with interface for up to 8 M Bus meter to be read over GPRS amongst others Email support WZU GPRS Radio module WZU RM Radio module with external antenna WZU RM EXT For mounting of temperature sensors Code Adapter for ball valves to install temp eratu...

Страница 15: ...Ultraheat Ultracold UH50 Configuration Instructions UH 106 101k Page 15 15 ...

Отзывы: