M. There are additional ERROR messages which may

appear on the display during operation which were
not covered previously:

The test set has sensed that current is not flowing
properly in the breaker under test and there is either
on open or short circuit between the TS-MD and the
breaker trip unit.

This message will appear if you enter a type of test
that is not available on the breaker being tested.
For example:

This message will appear if you enter a setting value
that does not exist. For example, a MM6B600EW
has continuous current settings of 20, 30, 40, 50,
60, 70, 80, 90 & 100 percent. If you were to enter any
value other than those listed, the above
message would appear.

Test Not Running-- Check Test Cable.
Press any key to continue.

XXXXXX is NOT available on a XXXXXXXX.
Press any key to continue.

Long Time is NOT Available on a LM6B400XCBW.
Press any key to continue.

XX is NOT a Valid Setting.
Press any key to continue.

Test Exceeds Capability of TS-MD.
Press any key to continue.

This message means that a test requires more
current to run than the TS-MD can produce.  The
settings on the breaker should be lowered and the
new settings should be entered into the TS-MD (step
K, option 3).   Then rerun the desired test.

N. The TS-MD will warn you of possible fault coverage

conflicts.  These conflicts may occur if, for example,
the short time and instantaneous pickup settings
overlap or interfere with one another.  In this case,
the following sequence of messages will appear:

These messages indicate that something other than
the desired function may trip the breaker.  You then
have the option of continuing with the test or
aborting it.

Hazardous voltage.
Will cause death or serious
injury.

Turn off and lock out all power
supplying the circuit breaker prior to
cover(s) removal or while cover(s)
are removed and when installing
any internal or external accessory.
Replace the covers and shields
before power supplying this device
is turned on.

You’ve chosen the Long Time test, but the
following may trip first:

Instantaneous
Press any key to continue.

Do you wish to proceed with the test?
[Y/N]

LONG  TIME  TRIP  OUT

Setting
% of In

20%-100%

24.4 to 55.0

33.3 to 75.0

44.4 to 100

77.8 to 175

133 to 300

222 to 500

278 to 625

300 to 675

2.2 sec.

3 sec.

4 sec.

7 sec.

12 sec.

20 sec.

25 sec.

27 sec.

All values are in seconds.