TPS4 06 Installation Instructions for:  
Switchboards and Low Voltage Switchgear 

Full Catalog ID Replacement Instructions

The following general observations should be noted 
concerning field replacement of TPS3-06 assemblies with 
TPS4 06 assemblies:

It is recommended that TPS3-06 installations be replaced 
with TPS3-06 replacements and TPS4-06 installations be 
replaced with TPS4-06 replacements. Otherwise, consult 
factory to replace TPS3-06 with a TPS4-06.

Module Only Replacement Instructions

Figure 9:

  

Switchboards & Low Voltage Switchgear

NOTE:

 TPS4 internal module may be replaced provided all power sources 

are locked out.

NOTE:

 Following replacement of a TPS4 internal module, the LCD display 

will continue to reflect the new serial number for the TPS4-06 unit. 

Step 1) Lock OFF all power supplying this equipment before 
working on it. Turn the internal disconnect to the OFF 
position. 

Step 2) Detach remote display module ribbon cable from top 
of TPS4 module. 

Step 3) Un-bolt the phase wire compression lugs from the 
phase connectors on the TPS4 module.

Step 4) If present, remove neutral wire from mechanical lug 
on the side of TPS4 module.

Step 5) Remove the TPS4 module from back panel by 
removing (4) Hex Head mounting screws located at corners 
of unit.

Step 6) Remove (2) mounting brackets from bottom of TPS4 
module. Note orientation of brackets. Each mounting bracket 
is attached via (2) hex head screws (4 total).

Step 7) Replace unit with the new TPS4 module.

Step 8) Reattach mounting feet to bottom of TPS4 module. 
Torque screws to 29.5 in-lbs.

Step 9) Re-install TPS4 module onto back plate with original 
(4) hex head screws. Torque to 29.5 in-lbs.

Step 10) Reattach line wire compression lugs to phase 
connections on TPS4 module. Torque to 45 in-lbs.

Step 11) If present, reattach neutral wire to mechanical lug 
on side of TPS4 module. Torque to 35 in-lbs.

Step 12) Turn the internal disconnect back to the ON position.

Step 13) Close equipment doors before reenergizing.

The following instructions are for the replacement of Siemens 
TPS4 SPD module in Siemens TPS4 06 unit.

14

TPS4 Surge Protection Devices | 

Installation Guide / User Manual

15

Installation Guide / User Manual

 | TPS4 Surge Protection Devices

Figure 1:  SPLIT

 

2 Hots, 1 Neu, 1 Grnd

Figure 2:  WYE

 

3 Hots, 1 Neu, 1 Grnd

Figure 3:  HI-LEG DELTA  

(B High)

 

3 Hots, (B HIGH), 

1 Neu, 1 Grnd

Figure 4:  DELTA & 

HRG WYE

 

3 Hots, 1 Grnd

Table 8:  

Model Number Catalog Logic

Voltage Code 

Surge Current Rating 

Options 

(1 Alpha numeric Character)

A

 = 240/120V ,1Ø, 3W (Figure 1) 

10

 = 100kA per phase 

X

 = Surge Counter 

(Standard)

B

 = 240/120V, 3Ø, 4W (Figure 3) 

15

 = 150kA per phase 

2

 = Type 2 SPD 

C

 = 208/120V, 3Ø, 4W (Figure 2) 

20

 = 200kA per phase 

       

(Default) Includes UL 1283 EMI/RFI Filters

W = 

220/127V, 3Ø, 4W (Figure 2) 

25

 = 250kA per phase 

0

 = Type 1 SPD

D

 = 240V, 3Ø, 3W (Figure 4) 

30

 = 300kA per phase 

E

 = 480/277V, 3Ø, 4W (Figure 2) 

40

 = 400kA per phase 

F

 = 480V, 3Ø, 3W (Figure 4) 

50

 = 500kA per phase 

G

 = 600V, 3Ø, 3W (Figure 4)* 

 

 

K

 = 380/220V, 3Ø, 4W (Figure 2) 

L

 = 600/347V, 3Ø, 4W (Figure 2) 

S

 = 400/230V, 3Ø, 4W (Figure 2)

T

 = 415/240V, 3Ø, 4W (Figure 2)

*Not avilable in 300, 400 or 500kA versions

Catalog #

     TPS4   

o

   06   

oo

    X  

o

Example: 

 TPS4C0620X2 =

 

SPD for a 208/120V panelboard with a surge current capacity of  

 

200kA per phase and Type 2 SPD.

 

Example: 

 TPS4CL620X2 =

 

SPD for a 208/120V panelboard with a surge current capacity of  

 

200kA per phase and Type 2 SPD.

TPS4 06 for Switchboards and Low Voltage Switchgear 
General Suppressor Series

Voltage Code 

Surge Current Rating 

Options 

(1 Alpha numeric Character)

A

 = 240/120V ,1Ø, 3W (Figure 1) 

15

 = 150kA per phase 

X

 = Surge Counter 

(Standard)

B

 = 240/120V, 3Ø, 4W (Figure 3) 

30

 = 300kA per phase 

2

 = Type 2 SPD

C

 = 208/120V, 3Ø, 4W (Figure 2) 

45

 = 450kA per phase 

       

(Default) Includes UL 1283 EMI/RFI Filters

W = 

220/127V, 3Ø, 4W (Figure 2) 

55

 = 550kA per phase 

0

 = Type 1 SPD 

E

 = 480/277V, 3Ø, 4W (Figure 2) 

75

 = 750kA per phase 

K

 = 380/220V, 3Ø, 4W (Figure 2) 

 

L

 = 600/347V, 3Ø, 4W (Figure 2)* 

 

S

 = 400/230V, 3Ø, 4W (Figure 2) 

 

 

T

 = 415/240V, 3Ø, 4W (Figure 2)

*Not avilable in 450, 550 or 750kA versions

 

Catalog #

     TPS4   

o

   L6    

oo

    X  

o

TPS4 TPS4 L6 10 Mode for Switchboards and Low Voltage Switchgear 
General Suppressor Series

Содержание TPS4 Series

Страница 1: ...usa siemens com spd Installation Guide User Manual Surge Protection Devices TPS4 Series Products for Panelboards Switchboards and other Apparatus ...

Страница 2: ...he SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with the NEC Do No...

Страница 3: ...ally the company is not responsible for incidental or consequential damages resulting from any defect in any product or component thereof The sales contract contains the entire obligation of Siemens This instruction manual shall not become part of or modify any prior existing agreement commitment or relationship Unpacking Preliminary Inspection Inspect the entire shipping container for damage or s...

Страница 4: ...e and use gentle radius on any bends Do not kink wire Prevent wire from encroaching breaker locations Neutral Connection is not applicable on Delta systems Step 6 Torque all connections to the values as specified on the installation and maintenance instruction label affixed to the rear of the dead front Table 3 Content for Installation in Lighting Panelboards Revised P1 7 6 TPS4 Surge Protection D...

Страница 5: ...PD units in the field re use the hardware originally installed and use the table as a guide for proper torque values NOTE For wired installations see details in the previous section only 2 tabs for single phase modules Torque Note For Item 10 see Bus Connection Tightening Torque values on label 15 A 1043 01 inside panel board W Option Instruction The W option includes repositioned phase connection...

Страница 6: ...abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with the NEC Do Not Hi Pot Test SPDs The TPS4 unit needs to be fully disconnected during Hi Pot testing Failure to disconnect ...

Страница 7: ...ne wire compression lugs to phase connections on TPS4 module Torque to 45 in lbs Step 10 If present reattach neutral wire to mechanical lug on side of TPS4 module Torque to 35 in lbs Step 11 Turn the internal disconnect back to the ON position Step 12 Close all doors before reenergizing The following instructions are for the replacement of Siemens TPS4 SPD module in Siemens TPS4 05 unit 12 TPS4 Su...

Страница 8: ...tep 13 Close equipment doors before reenergizing The following instructions are for the replacement of Siemens TPS4 SPD module in Siemens TPS4 06 unit 14 TPS4 Surge Protection Devices Installation Guide User Manual 15 Installation Guide User Manual TPS4 Surge Protection Devices Figure 1 SPLIT 2 Hots 1 Neu 1 Grnd Figure 2 WYE 3 Hots 1 Neu 1 Grnd Figure 3 HI LEG DELTA B High 3 Hots B HIGH 1 Neu 1 Gr...

Страница 9: ...tors one per phase Green is good Extinguished green LED indicates loss of protection Every suppression element in this SPD is monitored N G suppression element monitoring is logic connected to Phase A Service LED red LED illuminates in the event of problems This indicator is logic connected to the Phase LEDs Should a Phase LED go out the Service LED will illuminate and the Audible Alarm will sound...

Страница 10: ...in Screen About Screen The About Screen displays the manufacturer s information the model number and the serial numberfor this specific SPD Pressing the CENTER button will return you to the Main Menu Screen System Info Screen The System Screen displays the important electrical information for this system This includes the nominal operating voltage System configuration ie Wye Delta Single Phase and...

Страница 11: ... the SPD If not corrected SPD problems will reoccur Tip Visually confirm N G bonding Be aware that a voltmeter measuring N G can be misleading For example N G voltage could read 0V because neutral and ground are at the same potential purely by happenstance not because they are bonded Visually confirm bonding Tip Experience indicates that regulation challenged generators can cause Sustained Overvol...

Страница 12: ...22 TPS4 Surge Protection Devices Installation Guide User Manual Notes ...

Страница 13: ...d does not constitute a performance guarantee for any projects Actual results are dependent on variable conditions Accordingly Siemens does not make representations warranties or assurances as to the accuracy currency or completeness of the content contained herein If requested we will provide specific technical data or specifications with respect to any customer s particular applications Our comp...

Отзывы: