background image

Optional Flush Mount Installation Considerations

The TPS3 12 and TPS3 15 are approximately 6” deep. The unit will 
not mount flush unless there is at least 6” of depth clearance. The 
TPS3 12 and TPS3 15 are not designed to mount flush on a typical 
2 x 4 stud wall.

Back Flange Mounting: Mount as close as possible to protected panel. 
Create a wall opening slightly larger than 12” high by 12” wide. See 
drawing.  Configure  a  robust  backing  plate  inside  the  wall  cavity 
6” from the wall face such that the TPS will be supported from its 
back. Note the mounting holes on the back flange. Also note that 
the TPS weighs 25lbs. Be careful not to drop the unit into the wall. 
Configure electrical conductor and conduit connections consistent 
with Installation Instructions beginning on page 4. Carefully reattach 
ribbon cables and faceplate/cover prior to energizing and  testing unit.

The TPS3 12 and TPS3 15 Series are designed for back flange mounting 
only.  Do not attempt to install the TPS such that its weight is supported 
by the front flange. The four mounting holes on the front flange are 
intended to secure the front flange to the outer wall surface. 

Retro-fit to an Existing Panel with No Available Breaker Positions

These  can  be  difficult  with  limited  options.  Follow  all  applicable 
Codes:

• 

Consider consolidating loads in a manner that might free breaker 
positions.

• 

A ten foot tap rule in NEC 240.21(B)(1) allows tapping the bus as 
long as the tap conductors are rated at least 10% of the ampacity 
of the panel.  This works well if the panel is about 600A or less: 
Tap the bus, run short 6 AWG leads to the SPD.  An SPD with a 
Disconnect Switch allows for easier SPD servicing in the future.  
If the panel starts getting large (>800A), then the conductor size 
increases, which may also become too large to fit into the SPD lugs 
or too cumbersome to work with.  In that case, consider tapping 
the bus per NEC 240.21(B)(1).  Run appropriate size conductors to 
a safety switch fused to 60A.  Mount the SPD immediately adjacent 
to the safety switch.  Connect SPD to the load side of the safety 
switch with 6 AWG.  Keep all leads as short as possible.   

• 

Install on Line Side by taking advantage of Type 1 SPD rating.  
Consider an SPD with a Disconnect Switch.

Disconnect Switch (Opt. on TPS3 12, Std. on TPS3 15)

The  disconnect  switch  provides  manual  disconnection  means  for 
phase conductors and the neutral conductor.  Ground is not switched.

Special  care  should  be  taken  while  pre-planning  installation  to 
ensure that leads are as short as possible.  Most TPS3 12’s & TPS3 
15’s in ‘square’ enclosures have backplanes that can be removed and 
repositioned to reduce leads.  See Figure 6.  (Models with rectangular 
enclosures may be repositioned by inverting only.)  (Excludes thru-
door handle options.)

There is limited working space around the Disconnect Switch.  
This is a consequence of reducing internal size and lead lengths.  
Please be patient. 

 

Disconnect switch will accept 6 AWG to 1/0 AWG, with 6 AWG preferred.  
Torque connections to 18 inch-pounds.  Over-torquing connections 
will fail the disconnect switch and will not be covered by warranty.

The disconnect switch is mounted on DIN-rail. It may be removed 
by gently pulling out the mounting tab at the bottom of the switch 
assembly.

Siemens TPS is one of few SPD manufacturers that offer Disconnect 
Switches available as a fully UL qualified option. The Short Circuit 
Current  Rating  posted  on  the  UL  label  of  the  SPD  includes  the 
Disconnect  Switch  and  supercedes  any  rating  on  the  individual 
Disconnect Switch.  When used in a Type 1 line-side application, the 
SPD including its Disconnect Switch has been UL tested and approved.  
Further evaluation is not required by UL, nor is a separate UL 98 rated 
switch required.

UL 1283 required language concerning the installation of EMI Filters

a)  An  insulated  grounding  conductor  that  is  identical  in  size  and 
insulation material and thickness to the grounded and ungrounded 
circuit  supply  conductors,  except  that  it  is  green  with  or  without 
one or more yellow stripes, is to be installed as part of the circuit 
that supplies the filter. Reference should be made to Table 250-122 
of the National Electrical Code regarding the appropriate size of the 
grounding conductor.

b) The grounding conductor mentioned in item a is to be grounded to 
earth at the service equipment or other acceptable building earth ground 

such as the building frame in the case of a high-rise  
steel-frame structure.

c) Any attachment-plug receptacles in the vicinity 
of the filter are to be of a grounding type, and the 
grounding conductors serving these receptacles 
are to be connected to earth ground at the service 
equipment  or  other  acceptable  building  earth 

ground such as the building frame in the case of 
a high-rise steel-frame structure.

d) Pressure terminal or pressure splicing connectors 
and soldering lugs used in the installation of the 
filter shall be identified as being suitable for the 
material of the conductors. Conductors of dissimilar 
metals  shall  not  be  intermixed  in  a  terminal  or 
splicing connector where physical contact occurs 

between dissimilar conductors unless the device is 
identified for the purpose and conditions of use.

Figure 6:  Flush Mount Installation

Step 2:

  

Mount SPD

Step 3: 

 

Install Flush 

Mount Plate 

& Cover

Cutout slightly 
larger than SPD base

Mounting Plate 
6 1/16” from 
outside of front 
wall

STEP 1: 

 

Prepare Wall - 
Must support 
25-55lbs

7

Содержание TPS3 12

Страница 1: ...User Manual USA TPS3 12 TPS3 15 Surge Protective Device ...

Страница 2: ...ge rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with...

Страница 3: ...n Torque 6 System Grounding 6 NEMA 3R Drain Holes for Standard Steel Enclosure 6 Optional Flush Mount Installation Considerations 7 Retro fit to an Existing Panel with No Available Breaker Positions 7 Disconnect Switch Opt on TPS3 12 Std on TPS3 15 7 UL 1283 required language concerning the installation of EMI Filters 7 TPS3 12 and TPS3 15 Installation Instructions 8 Operation 10 Surge Counter Res...

Страница 4: ...tion with installation operation or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purposes the matter should be referred to the local Siemens sales office Do Not Hi Pot Test SPDs Any factory or on site testing of power distribution equipment that exceeds normal operating voltage such as high potential in...

Страница 5: ...eplaceable module Do not attempt to disassemble the module as it stores charge Simplified Explanation of Operation As SPDs sense overvoltage they create a momentary internal short circuit thereby redirecting harmful surge energy to earth ground SPDs are capable of repeating this function repeatedly For optimum protection staged surge suppression should be implemented at the service entrance and al...

Страница 6: ...e Current Rating TPS3 12 TPS3 L12 TPS3 15 TPS3 L15 10 100kA per phase 15 150kA per phase 20 200kA per phase 25 250kA per phase 30 300kA per phase 40 400kA per phase 45 450kA per phase 50 500kA per phase 60 600kA per phase 80 800kA per phase 90 900kA per phase 1K 1000kA per phase AVAILABLE OPTIONS When Option is Not Selected Include a 0 in the Field option code description TPS3 12 TPS3 L12 TPS3 15 ...

Страница 7: ... mount or pull box enclosures are available as options Before installing ensure that your enclosure type and application are appropriate per NEMA 250 with regard to moisture dirt excessive dust flammable materials or atmospheres corrosivevapors etc Pleaseconsultfactoryifenclosure needs changed This SPD is designed to operate in an ambient temperature range of 40 C 40 F to 60 C 140 F with a relativ...

Страница 8: ...e Rating Before installing SPD verify that it has the same voltage rating as the power distribution system Compare the SPDs nameplate voltage or model number and ensure that SPD configuration matches the intended power source See Table 1 The specifier or the user of the device should be familiar with the configuration and arrangement of the power distribution system in which any SPD is to be insta...

Страница 9: ...tems ground impedance should be as low as possible When metallic raceway is used as an additional grounding conductor an insulated grounding conductor should be run inside the raceway and sized per the NEC Adequate electrical continuity must be maintained at all raceway connections Do not use isolating bushings to interrupt a metallic raceway run A separate isolated ground for the SPD may isolate ...

Страница 10: ...oned to reduce leads See Figure 6 Models with rectangular enclosures may be repositioned by inverting only Excludes thru door handle options There is limited working space around the Disconnect Switch This is a consequence of reducing internal size and lead lengths Please be patient Disconnectswitchwillaccept6AWGto1 0AWG with6AWGpreferred Torque connections to 18 inch pounds Over torquing connecti...

Страница 11: ...nfirm panel is deenergized Identify connection breaker location and SPD location Make sure leads are short Reducing inches matters InstallationTips SPDmoduleismountedonbackplanewithin its enclosure In many cases the backplane assembly can be unboltedandrotatedintwoorfourdirectionstoyieldshortest leads SeeFigure7 Carefullydisconnect ribboncable s and unbolt backplane assembly Various configurations...

Страница 12: ... 0 31 DIA 4Plc 15 25 15 25 18 00 20 75 8 87 15 25 STUDS Consult factory for more options at 1 888 333 3545 A Advanced Protection Technologies Inc Clearwater Florida Listed 56E3 TVSS U R L CAUTION 2 1 3 4 6 5 7 8 Advanced Protection Technologies Inc Clearwater Florida Listed 56E3 TVSS U R L CAUTION B C N A B C N A B N C G THREE POLE C Advanced Protection Technologies Inc Clearwater Florida Listed 5...

Страница 13: ...n or technician Until a qualified person evaluates the unit press Alarm Silence to silence the alarm The LED above Alarm Silence illuminates when the alarm is deactivated Normal operation occurs with the Alarm Silence LED extinguished The red Service LED will remain illuminated even though the Audible Alarm has been silenced Test tests the red Service LED the Audible Alarm and changes the state of...

Страница 14: ... Service Please contact TPS Technical Support at 1 888 333 3545 for service related issues Quality SPDs are designed and tested to withstand severe duty However there are various electrical anomalies against which SPDs cannot protect These are generally Sustained Overvoltages also known as Temporary Overvoltages TOVs In this context Sustained Overvoltages may be only a few cycles Failed SPDs tend ...

Страница 15: ... tabs near the inter module diagnostic wiring An illuminated red LED indicates the damaged module ExtraInformation Shouldonedamagedmoduleberemoved theSPD can still function correctly with one module If the diagnostic display cable was connected to the removed module reconnect the cable to the other module s quick release connector The diagnostic display will function correctly TPS3 15 s with Type ...

Страница 16: ...Siemens Industry Inc Building Technologies Division 5400 Triangle Parkway Norcross GA 30092 888 333 3545 info us siemens com 6 17 11 jb 8172 ...

Отзывы: