For further information, please review latest editions of NEC® Art. 285, 

UL 1449, contact your local Siemens sales office or contact Siemens 

TPS Tech Support at 1.888.333.3545.

The TPS3 11 is a Type 1 SPD.  The TPS3 11 is suitable for use almost 
anywhere  (not  as  a  plug-in  SPD).    Type  1  SPDs  are  evaluated  more 
rigorously by UL 1449 for 2008 NEC® Article 285 compliance.  Type 
1 SPDs and their connecting leads have been evaluated for line side 
applications without need for supplemental overcurrent protection.  
Type 1 SPDs include internal overcurrent protection.  As a generalization, 
there are practical maintenance reasons for installing on the load side of 
the main overcurrent device (i.e. Type 2 installation).  When connected 
on load side of main disconnect, we recommend connecting via a 30A 
circuit breaker due to 10 AWG conductors. The circuit breaker serves as 
a disconnect switch and provides NEC® imposed short circuit protection 
to the conductors in Type 2 or 4 applications.    
 
Simplified Explanation of Operation

SPDs sense overvoltage and create a momentary short circuit to redirect 
harmful surge energy to earth ground. SPD’s are not a one time device.  
They reset automatically and wait for the next surge.  SPDs are capable 
of repeating this function thousands of times.

Parts List and Inspection 

Items included in the package consist of the following:

• 

1 TPS3 11 SPD including 3’ (~1m) conductors

• 

1 User’s Manual (this document)

If the Flush Mount Kit was ordered, additional parts are supplied as 
follows:

• 

1 Flush Mount Plate

• 

1 Flush Mount Installation Instructions

• 

4 Mounting Screws

Carefully inspect each item in the package for signs of damage.  If 
damage is found, please contact Siemens TPS Technical Support: 
1.888.333.3545. For more information about this  product or other 
Siemens products, visit www.sea.siemens.com.

Figure 2:  DIMENSIONS AND WEIGHT

TPS3  11’s  have  demonstrated  200kA  Short  Circuit  Current  Ratings 
(SCCR)  including  leads  (120/240V  Split  phase  models  have  100kA 
SCCRs). See UL Label markings on SPD or see Data Sheet for specs.)  
Supplemental overcurrent protection is not required to protect this SPD. 
However, NEC® convention requires that connecting conductors have 
overcurrent protection in Type 2 or 4 applications. Follow applicable 
codes.

This  device  features  internal  overcurrent  and  overtemperature 
protection that will disconnect effected surge suppression components 
at the end of their useful life, but will maintain power to the load – now 
unprotected. If this situation is undesirable for the application, follow 
these instructions for replacing the device.  TPS3 11 is ultrasonically 
welded closed and contains no user serviceable parts.

Table 1: Specifications 

Specifications

Temperature Operating

-40

o

C (-40

o

F) to 60

o

C (+140

o

F)

Temperature Storage

-55

o

C (-67

o

F) to 65

o

C (+149

o

F)

Wire Size & Installation Torque 10 AWG; 18 inch-pounds
Appropriate Circuit Breaker
based on conductor size

30A (SPD includes internal OCP)

NEMA 250 Enclosure Rating

Type 4X with appropriate 
sealing & sealing condulets

Voltage Rating & Application

Before installing SPD, verify by nameplate voltage or model number 
that it has the same voltage rating as the power distribution system. 
If unsure call Siemens TPS Tech Support at 1.888.333.3545 before 
proceeding.  The  SPDs  specifier  or  user  should  be  familiar  with  the 
configuration and arrangement of the power distribution system. The 
system is defined by how the secondary windings of the transformer 
supplying  the  service  entrance  main  or  load  are  configured.  This 
includes whether or not the transformer windings are referenced to 
earth via a grounding conductor. The system configuration is not based 
on how any specific load or equipment is connected to a particular 
power distribution system. SPDs should be installed per the distribution 
system, not per a load or motor’s wiring connection.  

For  example,  suppose  a  480V  three  phase  motor  appears  to  be 
connected  as  a  480V  Delta.    In  actuality,  the  serving  distribution 
system  might  be  a  480Y/277V  grounded  Wye,  with  or  without  a 
neutral pulled to the motor or MCC. The system is still a 480Y/277V 
Wye, even though the load is connected as a Delta.  A grounded Wye 
has a defined reference to ground (i.e., neutral is bonded to ground).  
In  contrast,  some  Delta  systems  are  ungrounded,  which  have  no 
reference to ground.  

Table 2:  Model number decoder

Model

Voltage 

code

Service Voltage

TPS3A11

A

240/120V 1Ø, 3W Plus Ground,

TPS3B11

B

240/120V 3Ø, 4W Plus Ground High Leg Delta 

TPS3C11

C

208Y/120V 3Ø, 4W Plus Ground

TPS3D11

D

240v 3Ø, 3W Plus Ground 

TPS3E11

E

480Y/277V 3Ø, 4W Plus Ground

TPS3F11

F

480v 3Ø, 3W Plus Ground 

TPS3G11

G

600v 3Ø, 3W Plus Ground 

TPS3K11

K

380Y/220V 3Ø, 4W Plus Ground 

TPS3L11

L

600Y/347V 3Ø, 4W Plus Ground 

TPS3S11

S

400Y/230V 3Ø, 4W Plus Ground 

Содержание TPS3 11

Страница 1: ...TPS3 11 Surge Protective Device User Manual USA ...

Страница 2: ...age rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance wit...

Страница 3: ...roblems to Avoid 7 Operation 9 Diagnostic Indication 9 Phase indicator LEDs Green 9 Service LED Red 9 Audible Alarm Option 9 Dry Contact Option 9 Remote Monitor Accessory Option 9 Maintenance 10 Troubleshooting Service 10 Please contact us for any service related issues 10 Warranty and Customer Service 10 Limited Warranty 10 Technical Support 10 Figures Figure 1 SPD Types 5 Figure 2 DIMENSIONS AND...

Страница 4: ...s CAUTION indicates a potentially hazardous situation which if not avoided could result in minor or moderate injury These instruction do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance Should further information be required by the user please call Siemens TPS Tech Support at...

Страница 5: ...s internal overcurrent and overtemperature protection that will disconnect effected surge suppression components at the end of their useful life but will maintain power to the load now unprotected If this situation is undesirable for the application follow these instructions for replacing the device TPS3 11 is ultrasonically welded closed and contains no user serviceable parts Table 1 Specificatio...

Страница 6: ...lly more difficult Extra care should be taken to NOT DROP the TPS3 unit into the wall Mount as close as possible to the protected panel Create a wall open ing approximately 6 3 4 tall by 6 1 16 wide See drawing Rotate dimensions 90o as appropriate depending on orientation Preplan and pre connect electrical conductor and conduit connections such that they are completed prior to fastening the TPS3 u...

Страница 7: ...ossible Note that Hi Legs are Phase B 9 Label or mark conductors as appropriate neutral white ground green energized black hi leg orange 10 Make sure system is bonded per NEC and is clear of hazards or faults before energizing N G bonding not per NEC will fail SPDs 1 cause of SPD failures 11 Energize and confirm proper operation of indicators and or options A sealing O ring is provided SPD can be ...

Страница 8: ...ase A BLK Phase B ORNG Neutral WHT Phase C BLK Ground GRN V HI LEG DELTA B High 3 Hots B HIGH 1 Neu 1 Grnd Phase A BLK Phase C BLK Phase B BLK Ground GRN V DELTA HRG WYE 3 Hots 1 Grnd CONTACTS NO C NC DRY SERVICE A B C N A C G B THREE POLE CONTACTS NO C NC DRY SERVICE A B C N A C G B THREE POLE N A C CONTACTS NO C NC DRY SERVICE G A C TWO POLE CONTACTS NO C NC DRY SERVICE A B C N A C G B THREE POL...

Страница 9: ...tacts change state during inoperative conditions including loss of power Any status change can be monitored elsewhere via Dry Contacts A Terminal Block includes two sets of Normally Open N O and Normally Closed N C contacts Both sets of contacts operate the same This is shown in Figure 8 A typical application using a Normally Closed configuration would connect to one set of the N C and Common term...

Страница 10: ...f any product Returned products must be sent to the factory with the transportation charges prepaid In addition the company also warranties unlimited replacement of modular and component parts within the warranty period previously described The company specifically disclaims all other warranties expressed or implied Additionally the company is not be responsible for incidental or consequential dam...

Страница 11: ...11 ...

Страница 12: ...Siemens Industry Inc Building Technologies Division 5400 Triangle Parkway Norcross GA 30092 888 333 3545 info us siemens com 8 9 10 al 8174 ...

Отзывы: