Only qualified licensed electricians should install or service SPDs

• 

Hazardous voltages exist within SPDs

• 

SPDs should never be installed or serviced when energized

• 

Use appropriate safety precautions including Personal Protection Equipment

• 

Failure to follow these instructions can result in death, serious injury, and/or equipment damage.

• 

This manual shall be read in entirety prior to installing

Bonding and Grounding Hazard

Verify that the neutral conductor in the service entrance equipment is bonded to ground in accordance with the National 
Electrical Code (NEC®) and all applicable codes.

Verify that the neutral terminal (XO) on the secondary side of distribution transformers are grounded to the system ground 
in accordance with the NEC® and all applicable codes.

During installation into an electrical system the SPD must not be energized until the electrical system is completely installed, 
inspected and tested.  All conductors must be connected and functional including the neutral (if required).  The voltage 
rating of the SPD and system must be verified before energizing the SPD.

Failure to follow these guidelines can lead to abnormally high voltages at the SPD.  This may cause the SPD to fail.  The 
warranty is voided if the SPD is incorrectly installed and/or if the neutral conductor in the service entrance equipment or 
downstream of separately derived systems is not bonded to ground in accordance with the NEC®.

Do Not Hi-Pot Test SPDs

Any  factory  or  on-site  testing  of  power  distribution  equipment  that  exceeds  normal  operating  voltage  such  as  
high-potential insulation testing, or any other tests where the suppression components will be subjected to higher voltage 
than their rated Maximum Continuous Operating Voltage (MCOV) must be conducted with the SPD disconnected from the 
power source.  For 4-wire systems, the neutral connection at the SPD must also be disconnected prior to performing high-
potential testing and then reconnected after test completion.

Failure to disconnect SPD and associated components during elevated voltage testing will damage the SPD and will void 
the warranty.

WARNING -

 

Hazardous Voltage & Shock Hazard

V

Failure to Follow These Instructions Could Result in Death or Serious Injury

Содержание TPS3 11

Страница 1: ...TPS3 11 Surge Protective Device User Manual USA ...

Страница 2: ...age rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance wit...

Страница 3: ...roblems to Avoid 7 Operation 9 Diagnostic Indication 9 Phase indicator LEDs Green 9 Service LED Red 9 Audible Alarm Option 9 Dry Contact Option 9 Remote Monitor Accessory Option 9 Maintenance 10 Troubleshooting Service 10 Please contact us for any service related issues 10 Warranty and Customer Service 10 Limited Warranty 10 Technical Support 10 Figures Figure 1 SPD Types 5 Figure 2 DIMENSIONS AND...

Страница 4: ...s CAUTION indicates a potentially hazardous situation which if not avoided could result in minor or moderate injury These instruction do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance Should further information be required by the user please call Siemens TPS Tech Support at...

Страница 5: ...s internal overcurrent and overtemperature protection that will disconnect effected surge suppression components at the end of their useful life but will maintain power to the load now unprotected If this situation is undesirable for the application follow these instructions for replacing the device TPS3 11 is ultrasonically welded closed and contains no user serviceable parts Table 1 Specificatio...

Страница 6: ...lly more difficult Extra care should be taken to NOT DROP the TPS3 unit into the wall Mount as close as possible to the protected panel Create a wall open ing approximately 6 3 4 tall by 6 1 16 wide See drawing Rotate dimensions 90o as appropriate depending on orientation Preplan and pre connect electrical conductor and conduit connections such that they are completed prior to fastening the TPS3 u...

Страница 7: ...ossible Note that Hi Legs are Phase B 9 Label or mark conductors as appropriate neutral white ground green energized black hi leg orange 10 Make sure system is bonded per NEC and is clear of hazards or faults before energizing N G bonding not per NEC will fail SPDs 1 cause of SPD failures 11 Energize and confirm proper operation of indicators and or options A sealing O ring is provided SPD can be ...

Страница 8: ...ase A BLK Phase B ORNG Neutral WHT Phase C BLK Ground GRN V HI LEG DELTA B High 3 Hots B HIGH 1 Neu 1 Grnd Phase A BLK Phase C BLK Phase B BLK Ground GRN V DELTA HRG WYE 3 Hots 1 Grnd CONTACTS NO C NC DRY SERVICE A B C N A C G B THREE POLE CONTACTS NO C NC DRY SERVICE A B C N A C G B THREE POLE N A C CONTACTS NO C NC DRY SERVICE G A C TWO POLE CONTACTS NO C NC DRY SERVICE A B C N A C G B THREE POL...

Страница 9: ...tacts change state during inoperative conditions including loss of power Any status change can be monitored elsewhere via Dry Contacts A Terminal Block includes two sets of Normally Open N O and Normally Closed N C contacts Both sets of contacts operate the same This is shown in Figure 8 A typical application using a Normally Closed configuration would connect to one set of the N C and Common term...

Страница 10: ...f any product Returned products must be sent to the factory with the transportation charges prepaid In addition the company also warranties unlimited replacement of modular and component parts within the warranty period previously described The company specifically disclaims all other warranties expressed or implied Additionally the company is not be responsible for incidental or consequential dam...

Страница 11: ...11 ...

Страница 12: ...Siemens Industry Inc Building Technologies Division 5400 Triangle Parkway Norcross GA 30092 888 333 3545 info us siemens com 8 9 10 al 8174 ...

Отзывы: