background image

Installation:

•  Remove the front cover.
•  Mount the starter on a vertical wall/ plate free from 

vibrations with proper nuts and bolts. Refer Fig. 8 for 
mounting dimensions and Fig. 4 for permissible mounting 
position.

•  Remove the rubber grommets for the incoming and 

outgoing cable connections.

•  Connect incoming and outgoing cables as follows (Refer 

Fig. 2 & 3):

  –  Use proper cable glands to ensure dust proofing. For 

conduit entry use packed washers.

  –  Select correct size of cables from Table-A
  –  Connect line and motor leads exactly as per wiring 

diagram pasted inside the cover of the starter.

  –  Terminate the incoming cable on terminal block. 

Automatic Star Delta 

Starter 3TE7291-0A

For dependable service, it is of utmost 
importance that instructions given below are 
followed for selection, inspection, installation, 
commissioning, operation and maintenance.

s

ASD-11 Starter (Self reset) 

Selection of Starter    

•  Refer Table A for recommended selection of 3TE72 

starters.

  Table A: kW/HP Rating, thermal overload relay range & 

fuse rating, Coil Voltage, Maximum full load current for 
different types of motors.

1.  ON Push Button
2.  OFF Push Button
3.  Earthing Screws
4.  Rubber Grommet (Not visible in Fig 1.)
5.  Name Plate
6.  Incoming Cable
7.  Outgoing Cable
8.  Cover Fixing Screws
9.  Mechanical Latch (OFF push button) to be used for 

preventing undesired ON operation of Starter

Fig. 1: ASD-11 Starter

  –  Connect outgoing cables on the Relay (K1) terminals

and Delta contactor (Q3) terminals.

  Tightening torque (N-cm):

kW Ratings

Incoming Terminals

Outgoing Terminals

7.5 – 11

80 – 140

80 – 140

15 – 18.5

150 – 210

100 – 150

•  Connect the earthing conductor to terminals marked

(earth) on the starter body with torque 80 to 140 N-cm.

The Starter is now ready for commissioning.
•  Initially set the overload relay to 0.58 times the rated

motor current.

•  Set the timer dial to the nearest value of starting time

available on motor name plate

•  If it is not available then set the dial to approximately

6-8 secs.

Installation, Operation & Maintenance 
Instructions

Please read and understand these instructions before 
installating, operating, or maintaining the equipment. Keep for 
future reference

Danger

Hazardous voltage can cause death or serious injury. Disconnect 
power before working on equipment.

Warning

Automatic Motor Restart. 
Can cause death, serious injury or property damage.

Do not use automatic reset mode when unexpected automatic 
restart of the motor can cause injury to persons or damage to 
equipment.
Reliable functioning of the equipment is only ensured with 
certified components. Commissioning and maintenance by 
qualified personnel only.

NOTICE

This product has been designed for environment A. Use of this product 
in environment B may cause unwanted electromagnetic disturbances in 
which case the user may require to take adequate mitigation measures.

IS/IEC 60947-4-1

6

7

4

8

1

9

3

2

5

Содержание TE7291-0A Series

Страница 1: ... ON operation of Starter Fig 1 ASD 11 Starter Connect outgoing cables on the Relay K1 terminals and Delta contactor Q3 terminals Tightening torque N cm kW Ratings Incoming Terminals Outgoing Terminals 7 5 11 80 140 80 140 15 18 5 150 210 100 150 Connect the earthing conductor to terminals marked earth on the starter body with torque 80 to 140 N cm The Starter is now ready for commissioning Initial...

Страница 2: ...ctions Fig 4 Maximum permissible mounting position from vertical plane Fig 5 Timer Adjustment Commissioning Read the note carefully before commissioning Start the motor and let it run for 30 mins Then gradually reduce the relay settings till it trips Set the relay at a slightly higher value than this setting Restart the motor after some time If the relay does not trip then consider it to be proper...

Страница 3: ...of the contactors if they were severely pitted or when only 40 of the original contact tips remains Fig 6 Operating characteristics of 3UW51 52 relays same The tripping times of the same The tripping times shown are for relays starting from the cold state At operating temperatures heated at rated current these are reduced to about 25 of the value obtained from the characteristics Replacement of Ov...

Страница 4: ...5 25 38 5 22 2 3TS33 00 0A 08K 3TS33 00 0A 08K 3TS32 10 0A 08K 3UW52 02 2C 16 25 3KL812 50 10 4 Code for operating coil voltage 50 Hz Z6 for 200 400V R0 for 415V Other Tables Star Delta Timer AC Input Voltage MLFB 230V 400V 380V 440V 3RP15 76 1NP20 8K 3RP15 76 1NM20 8K Other Tables Motor Output at 415V Type4 kW HP ASD Starter 7 5 10 3TE72910AW74 9 3 12 5 3TE72910A 75 11 15 3TE72910A 77 15 20 3TE72...

Страница 5: ...Notes ...

Страница 6: ...sembling and separation into following materials METALS Segregate into Ferrous types for recycling through authorized dealer PLASTICS Segregate as per material type for recycling through authorized dealer Because of the long lifetime of Siemens Products the disposal guidelines may be replaced by other national regulations when taking the product out of service The local customer care service is av...

Отзывы: