background image

Installation Instructions 
Document No. 540-149 
September 2, 2008 

Mounting Information 

Always mount the sensor vertically. 
 
Locate the sensor: 

 

According to design specifications and local 
regulations. 

 

Where the air circulates around it freely (not 
in recessed areas or behind doors). 

 

Allowing a minimum of four inches (10 cm) 
free space above and below for proper 
airflow, the front cover removal tool, and the 
computer communication cable. 

 

Away from drafts caused by doors, windows, 
outside walls, air registers, pipes, return air 
plenums, etc. 

 

Away from heat sources such as strong 
lights, fireplaces, direct sunlight, etc. 

 

On an inside wall (preferably), about five 
feet (1.5 m) above the finished floor. 

While not recommended, if you need to mount the 
sensor on exterior brick or cement-type walls, see 

Accessories

Drywall Mounting (No Rough-in), Typical 

1.  Mark the center (cable) hole and the mounting 

hole locations, using the sensor base plate as a 
template. See Figure 2.  

 

CAUTION: 

 

For drywall mounting, only use the top 
and bottom holes. 

TH0703R1

3/16 (4.8)

1 (25.4)

1-3/8

(34.9)

1

(25.4)

2-3/8

(60.3)

 

Figure 2.  Mounting and Center Hole Locations 

Dimensions in Inches (Millimeters). 

2.  Drill two 3/16-inch (4.8 mm) mounting holes. 

3.  Cut a one-inch (25 mm) center hole with a hole 

saw. 

4.  If using screws to attach the sensor, insert two 

plastic wall anchors. 

5.  Pull about three inches (75 mm) of the cable(s) 

and/or fan switch wires through the mounting 
hardware in the order shown. 

 

Figure 3.  Drywall Mounting (No Rough-in), Typical. 

6.  Mount the sensor base plate on the wall, noting 

the UP arrow on the stabilizer plate: 

a.  Install either the two mounting screws 

provided, the drive rivets provided, or 
spring clips, but do not tighten. 

CAUTION: 

 

Pounding too hard or over-tightening may 
cause the sensor base plate to crack or 
bend. 

b.  Level the sensor base plate for 

appearance. 

c.  Tighten the two mounting screws to the 

sensor base plate. 

7.  Do one of the following: 

 

If the cable is terminated: Inspect the RJ-11 
connector for damage. 

Page 2 of 4

 

Siemens Building Technologies, Inc.

 

Содержание TALON

Страница 1: ...2B BACnet Digital Room Temperature Sensor with fan switch white Warning Caution Notations CAUTION Equipment damage or loss of data may occur if you do not follow a procedure as specified Required Tools Phillips sizes 1 and 2 screwdrivers Medium flat blade screwdriver Small flat blade screwdriver Medium duty electric drill 3 16 inch 4 8 mm drill bit 1 inch 25 mm hole saw Small level Tape measure Ma...

Страница 2: ...or base plate as a template See Figure 2 CAUTION For drywall mounting only use the top and bottom holes TH0703R1 3 16 4 8 1 25 4 1 3 8 34 9 1 25 4 2 3 8 60 3 Figure 2 Mounting and Center Hole Locations Dimensions in Inches Millimeters 2 Drill two 3 16 inch 4 8 mm mounting holes 3 Cut a one inch 25 mm center hole with a hole saw 4 If using screws to attach the sensor insert two plastic wall anchors...

Страница 3: ...erature Sensor RTS port on the controller Connect the fan switch cables wires to the appropriate controller terminal The installation is now complete Electrical Box and Rough in Mounting Typical 1 If a locator is attached to the rough in device remove the locator by removing the two screws and lightly rocking the locator to pull it free 2 Untie the twist tie and pull about three inches 75 mm of th...

Страница 4: ...nting 129 073 192 506 Electrical Box Adapter Plate Assembly Kit pkg 5 Electrical boxes mounted flush with the wall and for gyms and similar environments requiring a guard Also see 544 782 Figure 5 192 860 Finish Plate Kit 1 Gang 1 Sensor stainless steel Single sensor low cost mounting Plate is 3 7 5 1 inches 9 5 12 9 cm 155 252P25 TB 238 536 666 Mounting Strap Standard light switch plate field sup...

Отзывы: