background image

 

 

Installation Instructions

Document No. 540-149 

September 2, 2008

 

TALON™ Digital Room Temperature 
Sensors 

 

 

 

Page 1 of 4 

Product Description 

These sensors allow users to view and adjust points 
in the controller using the sensor buttons and digital 
display. 

These sensors work with Siemens controllers, and 
use a 10K 

Ω

 thermistor to detect temperature. The 

effective sensing and set point range is 55 to 95°F 
(13 to 35°C). 

The 587-612B includes an integral fan speed switch 
that allows users to override the ventilation fan. 

These sensors can be mounted on electrical boxes, 
stud-type mounting brackets, or drywall. Obtain the 
necessary mounting hardware and follow the 
appropriate mounting procedures for the type of 
installation required. 

Product Numbers 

587-610B  BACnet Digital Room Temperature 

Sensor - white 

587-612B  BACnet Digital Room Temperature 

Sensor with fan switch - white 

Warning/Caution Notations 

CAUTION 

Equipment damage, or loss of 
data may occur if you do not 
follow a procedure as 
specified. 

Required Tools 

 

Phillips sizes 1 and 2 screwdrivers 

 Medium, 

flat-blade 

screwdriver 

 

Small, flat-blade screwdriver 

 

Medium-duty electric drill 

 

3/16-inch (4.8 mm) drill bit 

 

1-inch (25 mm) hole saw 

 Small 

level 

 Tape 

measure 

 

Marker or pencil 

 

Item Number 540-149, Rev BA 

 

If using non-terminated or damaged cables, you also 
need: 

 

Room sensor connector tool (RJ-11 
crimping tool) 

 

Room sensor connector kit 

Expected Installation Time 

20 minutes 

Prerequisites 

 

Review these instructions before beginning. 

 

Installed: appropriate field wiring (standard 
six-conductor room sensor cables, plenum), 
within the maximum wiring run length for the 
individual equipment controller. The 
maximum recommended length is 100 feet 
(30 m). 

 

All wiring must comply with National Electric 
Code (NEC) and local regulations. 

 

Figure 1.  Room Temperature Sensor with Fan Speed. 

Содержание TALON

Страница 1: ...2B BACnet Digital Room Temperature Sensor with fan switch white Warning Caution Notations CAUTION Equipment damage or loss of data may occur if you do not follow a procedure as specified Required Tools Phillips sizes 1 and 2 screwdrivers Medium flat blade screwdriver Small flat blade screwdriver Medium duty electric drill 3 16 inch 4 8 mm drill bit 1 inch 25 mm hole saw Small level Tape measure Ma...

Страница 2: ...or base plate as a template See Figure 2 CAUTION For drywall mounting only use the top and bottom holes TH0703R1 3 16 4 8 1 25 4 1 3 8 34 9 1 25 4 2 3 8 60 3 Figure 2 Mounting and Center Hole Locations Dimensions in Inches Millimeters 2 Drill two 3 16 inch 4 8 mm mounting holes 3 Cut a one inch 25 mm center hole with a hole saw 4 If using screws to attach the sensor insert two plastic wall anchors...

Страница 3: ...erature Sensor RTS port on the controller Connect the fan switch cables wires to the appropriate controller terminal The installation is now complete Electrical Box and Rough in Mounting Typical 1 If a locator is attached to the rough in device remove the locator by removing the two screws and lightly rocking the locator to pull it free 2 Untie the twist tie and pull about three inches 75 mm of th...

Страница 4: ...nting 129 073 192 506 Electrical Box Adapter Plate Assembly Kit pkg 5 Electrical boxes mounted flush with the wall and for gyms and similar environments requiring a guard Also see 544 782 Figure 5 192 860 Finish Plate Kit 1 Gang 1 Sensor stainless steel Single sensor low cost mounting Plate is 3 7 5 1 inches 9 5 12 9 cm 155 252P25 TB 238 536 666 Mounting Strap Standard light switch plate field sup...

Отзывы: