TECHNICAL DATA

Housing

Glass-filled  polycarbonate,
sealed  to IP54.

All plates, hood, and swivel of
stainless steel to BS 1449, Point 2

Response Time

S121 and S122 time to alarm
with the T110 should be between
6 and 20 seconds

Temperature

Operating: -10°C (14°F) to 50°C

(122°F)

Storage:

-30°C (-22°F) to 70°C
(158°F)

Humidity

0 through 95%

Weight

1½ pounds

Battery Life

Nickel cadmium: 7 hours (typical)
Carbon zinc:

2 hours (typical)

MAINTENANCE

Battery Indicator

A white flashing light seen through the
eye of the T110 indicates that the Test
Source unit is working normally. A
flashing red LED indicates low battery
voltage; a steady red LED indicates
extremely low battery voltage. If both
the white light and the red LED are off,
the battery is presumed to be dead.

OPERATION

If the detector to be checked is out of
reach, fasten as many poles as neces-
sary (up to three) to reach the detector.
Select the correct rotary switch setting
for the detector (See Figure 1). Hold the
T110 in front of the detector, aligning
the “eye” (See Figure 3). In 6-20
seconds the detector alarm LED should
come on, indicating that the detector
being tested has responded. Lower the
Test Source and turn the rotary switch
to the OFF position.

FIGURE 3

REAR VIEW OF T110

Содержание T110

Страница 1: ... Manual ModelT110 InfraredTest Source P N 315 089116 2 Siemens BuildingTechnologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens BuildingTechnologies Ltd 2185 Derry Road West Mississauga Ontario L5N 7A6 Canada ...

Страница 2: ...or such use may be obtained on a site by site basis The Test Source has a polycarbonate housing approved for increased safety It contains a lamp that is electrically pulsed by an intrinsically safe circuit Infrared energy from the lamp is focused on the detector through a Fresnel lens The unit is powered by either a carbon zinc or nickel cadmium battery The large rotary switch knob on the front of...

Страница 3: ... that the Test Source unit is working normally A flashing red LED indicates low battery voltage a steady red LED indicates extremely low battery voltage If both the white light and the red LED are off the battery is presumed to be dead OPERATION If the detector to be checked is out of reach fasten as many poles as neces sary up to three to reach the detector Select the correct rotary switch settin...

Страница 4: ...attery Indicator above signal a low or nonexistent voltage CAUTION Do not use alkaline batteries in the T110 Test Source Nickel cadmium batteries are recom mended in preference to zinc carbon batteries because of their longer life See Battery Life in TECHNICAL DATA above and only nickel cadmium batteries are permitted by BASEEFA for hazardous areas Insert the new battery only when in a safe area R...

Отзывы: