INTRODUCTION

The Model T110 Test Source from
Siemens Building Technologies, Inc., is
designed specifically for on-site testing
of the S121 and S122 Flame Detectors.
When the plate with the guide is attached,
the T110 is self-aligning and checks
both the sensitivity and response time of
the detectors. The Test Source consists
of a module in a cradle. The module can
be held by hand up to the detector to be
tested or can be fastened to the end of
an extendable pole with an adapter and
then held up against the detector.

This Test Source is approved by
BASEEFA for use in all zone 1 and
zone 2 areas with gases rated T1 and
T4. Approval for zone 0 areas is not
available for this equipment; however,
permission for such use may be
obtained on a site-by-site basis.

The Test Source  has a polycarbonate
housing approved for increased safety.

It contains a lamp that is electrically
pulsed by an intrinsically safe circuit.
Infrared energy from the lamp is
focused on the detector through a
Fresnel lens. The unit is powered by
either a carbon zinc or nickel cadmium
battery.

The large rotary switch knob on the
front of the unit (See Figure 1) is used
to turn the Test Source on and off. The
knob is also used to select the correct
sensitivity level for testing either S121
(Sxx1) or S122 (Sxx2).

The extendable pole that can be used
with the Test Source comes in 4 foot, 4
inch sections that slot into each other
and are connected to the Tl10 with the
Extendable Pole Adapter (See Figure
2). The maximum recommended length
of the pole is three sections (approxi-
mately 13 feet).

FIGURE 2

EXTENDABLE

POLE ADAPTER

FIGURE 1

T110 TEST SOURCE

Содержание T110

Страница 1: ... Manual ModelT110 InfraredTest Source P N 315 089116 2 Siemens BuildingTechnologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens BuildingTechnologies Ltd 2185 Derry Road West Mississauga Ontario L5N 7A6 Canada ...

Страница 2: ...or such use may be obtained on a site by site basis The Test Source has a polycarbonate housing approved for increased safety It contains a lamp that is electrically pulsed by an intrinsically safe circuit Infrared energy from the lamp is focused on the detector through a Fresnel lens The unit is powered by either a carbon zinc or nickel cadmium battery The large rotary switch knob on the front of...

Страница 3: ... that the Test Source unit is working normally A flashing red LED indicates low battery voltage a steady red LED indicates extremely low battery voltage If both the white light and the red LED are off the battery is presumed to be dead OPERATION If the detector to be checked is out of reach fasten as many poles as neces sary up to three to reach the detector Select the correct rotary switch settin...

Страница 4: ...attery Indicator above signal a low or nonexistent voltage CAUTION Do not use alkaline batteries in the T110 Test Source Nickel cadmium batteries are recom mended in preference to zinc carbon batteries because of their longer life See Battery Life in TECHNICAL DATA above and only nickel cadmium batteries are permitted by BASEEFA for hazardous areas Insert the new battery only when in a safe area R...

Отзывы: