Siemens Symaro AQS2100 Скачать руководство пользователя страница 14

 

 

14 

Siemens 

 

A6V11893002_en--_c 

Smart Infrastructure 

 

2021-07-05 

 

 

Functional data (temperature with QSM2162) 

Range of use 

-

5…45

 °C 

Measuring range 

0…50

 °C/-

35…35

 °C 

Measuring accuracy at DC 24 V in the range of  

20…25

 °C 

15…35

 °C 

-

35…50

 °C 

 
±0.3 k (typical) 
±0.6 k 
±1 k 

Time constant t

63

 

< 3.5 min in 2 m/s moved air 

Output signal, linear (terminal X3) 

 

DC 0...10 V or DC 0...5 V   
0...50 °C/-

35…35

 °C, max. ±1 mA 

 

4...20 mA   0...50 °C/-

35…35

 °C, max. 500 ohm 

 

 

Functional data (humidity with QSM2162) 

Range of use 

5…95

 % r.h. (non-condensing) 

Measuring range 

0…100

 % r.h. 

Measuring accuracy at 23 °C and DC 24 V 

0…95

 % r.h. 

30…70

 % r.h. 

 
±5 % r.h. 
±3 % r.h. (typical) 

Time constant t

63

 

Approx. 20 s 

Output signal, linear (terminal X2) 

 

DC 0...10 V or DC 0...5 V   
0...100 % r.h., max. ±1 mA 

 

4...20 mA   0...100 % r.h., max. 500 ohm 

 

 

Functional data 

Max. air velocity V

max

 

10 m/sec 

 

 

Ambient conditions and protection classification 

Protection degree of housing 

IP54 as per EN 60529 in built-in state 

Protection class 

III as per EN 60730-1 

Environmental conditions

 

  Transport 

 

Climatic conditions 

  Temperature 

  Humidity 

 

Mechanical conditions 

  Operation 

 

Climatic conditions 

  Temperature (housing with electronics) 

  Humidity 

 

Mechanical conditions 

 
IEC 60721-3-2 
Class 2K3 
-25...70 °C 
< 95 % r.h. 
Class 2M2 
IEC 60721-3-3 
Class 3K5 
-5...45 °C 

5…95

 % r.h. (non-condensing) 

Class 3M2 

 

Содержание Symaro AQS2100

Страница 1: ...s acquire PM2 5 and PM10 concentrations relative humidity and temperature Operating voltage AC 24 V or DC 15 35 V Signal outputs DC 0 10 V or DC 0 5 V or 4 20 mA adjustable Range of use 5 45 C 5 95 r h non condensing A6V11893002_en _c Smart Infrastructure 2021 07 05 ...

Страница 2: ...er and delivery When ordering provide both name and type reference e g fine dust duct sensor QSM2100 The sensor is supplied complete with mounting flange cable entry gland M16 and a pre installed AQS2100 in fine dust duct sensor Accessory Name Type Order number Filter cap for QSM2162 replacement AQF3101 Fine dust duct sensor module for replacement AQS2100 S55720 S493 The accessory must be ordered ...

Страница 3: ... of a housing a printed circuit board connection terminals a mounting flange and an immersion rod The immersion rod of the QSM2162 has a meas uring tip The bisectional housing consists of a base and a removable cover snap on design The measuring circuit and the setting elements are located on the printed circuit board inside the cover the connection terminals are located on the base The humidity a...

Страница 4: ... 2 ON PM2 5 PM10 temperature 2 OFF 0 50 C default 2 ON 35 35 C 2 OFF Continuous work mode default ON Smart work mode ON OFF OFF Test MODE 1 1 ON OFF ON Test MODE 2 1 ON ON OFF Test MODE 3 1 ON ON ON Test MODE 4 1 Note 1 For detailed information on the test mode see Activating test function 5 2 These functions are only for QSM2162 Use the test function to check whether the sensor value inaccuracy i...

Страница 5: ... ON DIP6 ON DIP7 ON 5 V 2 5 V 12 mA 5 V 2 5 V 12 mA 5 V 2 5 V 12 mA PM2 5 calibration mode 1 Function 1 2 OFF OFF Mode 1 default OFF ON Mode 2 ON OFF Mode 3 ON ON Reserved Note 1 Mode 1 is for standard use Mode 2 and Mode 3 are for advanced application Mode 1 The sensor is calibrated using the TSI device as reference in Arizona A1 dust Mode 2 The sensor is calibrated using the GRIMM device as refe...

Страница 6: ...gnal output is still 10 V or 20 mA after changing the selected measuring range the cause is a PM2 5 communication error In the following table High means the signal output of terminal is 10 V 5 V 20 mA after 60 s Low means the signal output of terminal is 0 V 0 V 4 mA after 60 s Malfunction Signal output X1 PM2 5 X2 r h X3 Temperature PM2 5 communication error High High High PM2 5 sensor module re...

Страница 7: ...able runs and the closer the cables the greater the electrical interference Use shielded cables in EMC prone environments Twisted pair cables are required for both secondary supply lines and signal lines Mounting To ensure degree of protection IP54 the sensor must be fitted with the cable entry pointing downward Mount the sensor where it can be easily accessed by service If used after humidifier a...

Страница 8: ...ructure 2021 07 05 The air inlet must be placed facing the air flow in order to achieve the uniformity and ac curacy expected Do not install the sensor in a vertical duct Mounting instructions are enclosed in the package Mounting instruc tions ...

Страница 9: ... outputs X1 and X2 and an output signal of 0 V 4 mA at signal output X3 QSM2100 QSM2162 PM2 5 PM10 temperature An output signal of 10 V 5 V 20 mA is provided at signal output X1 and an output signal of 0 V 4 mA at sig nal output X2 Replacing the sensor module NOTICE As the replacement on QSM2162 and QSM2100 is identical the steps to re place the QSM2162 sensor module serve as an example 1 Detach t...

Страница 10: ...10 Siemens A6V11893002_en _c Smart Infrastructure 2021 07 05 2 Remove the module by hand 3 Replace the module by the new one ...

Страница 11: ...e If not possible insert a new sensor module 10 s after the old one is removed Disposal The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage Dispose of the device through channels provided for this purpose Comply with all local and currently applicable laws and regulations ...

Страница 12: ...ed by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technicia...

Страница 13: ... m s Direction of air inlet outlet after mounting facing air flow Analog output signal terminal X1 DC 0 10 V or DC 0 5 V 0 500 μg m3 0 300 μg m3 0 100 μg m3 0 50 μg m3 max 1 mA 4 20 mA 0 500 μg m3 0 300 μg m3 0 100 μg m3 0 50 μg m3 max 500 ohm Data update interval Continuous work mode default 3 8 min smart work mode Functional data PM10 Measuring range selectable 0 500 μg m3 default 0 300 μg m3 0 ...

Страница 14: ...g accuracy at 23 C and DC 24 V 0 95 r h 30 70 r h 5 r h 3 r h typical Time constant t63 Approx 20 s Output signal linear terminal X2 DC 0 10 V or DC 0 5 V 0 100 r h max 1 mA 4 20 mA 0 100 r h max 500 ohm Functional data Max air velocity Vmax 10 m sec Ambient conditions and protection classification Protection degree of housing IP54 as per EN 60529 in built in state Protection class III as per EN 6...

Страница 15: ...ials composition packaging environmental benefit disposal General Cable lengths for measuring signals Perm cable lengths See device data sheet for signal handling Electrical connections screw terminals 1 2 5 mm2 or 2 1 5 mm2 Materials and colors Base Polycarbonate RAL 7001 silver gray Cover Polycarbonate RAL 7035 light gray Immersion rod ABS RAL 7001 silver gray Filter cap Polycarbonate RAL 7001 s...

Страница 16: ...iagrams Connection terminals QSM2100 QSM2162 G Operating voltage AC 24 V SELV or DC 15 35 V G0 Ground and measuring neutral X1 Signal output DC 0 10 V DC 0 5 V or 4 20 mA X2 Signal output DC 0 10 V DC 0 5 V or 4 20 mA X3 Signal output DC 0 10 V DC 0 5 V or 4 20 mA ...

Страница 17: ...17 Siemens A6V11893002_en _c Smart Infrastructure 2021 07 05 Dimensions Dimensions in mm ...

Страница 18: ... Global Headquarters Theilerstrasse 1a CH 6300 Zug 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2020 Technical specifications and availability subject to change without notice Document ID A6V11893002_en _c Edition 2021 07 05 ...

Отзывы: