Generator Sizing Guide

UPS Generator Compatibility 

Passive (also referenced as standby or off-line) and
Line-Interactive

These technologies are most common for personal workstations
and point of sale applications. They are typically single phase
equipment with size ranges of 350 VA – 2000 VA for passive
and 500 VA to 5000 VA for line-interactive.

Passive UPS’s are the simplest type. Under normal conditions
AC power passes straight through to the UPS load. When the
input power supply goes outside of specifications, the UPS
transfers the load from input power to the internal DC to AC
power inverter. Passive UPS’s do not correct for voltage or 
frequency deviations under “normal” operation.  

Line-interactive is similar to the passive technology except 
it has circuitry that attempts to correct for standard voltage
deviations. Frequency deviations under “normal” power 
operation are not corrected.

Equipment Notes:
These devices tend to be electrically / harmonically very noisy.
A single small UPS is not a significant concern, but applications
with multiple UPS’s can be problematic. 

Passive UPS technology typically has normal tolerances of 
10 – 25% on voltage and 3 hertz on frequency. If the input
source goes outside of these tolerances, the UPS will switch
onto the UPS battery source. Some line-interactive units may
have frequency tolerances factory set to .5 hertz. These units
will need to have their frequency tolerance increased to a 
minimum of 2 hertz.    

Generator Sizing Recommendation:
Limit the total UPS loading to 15% – 20% of the generator
capacity.

Double-Conversion

This technology is most common for critical load applications.
Double-conversion UPS’s constantly rectify AC to DC and then
invert the DC back into AC. This configuration results in an 
output that corrects for voltage and frequency deviations.  

There are single and three phase models covering small
through large applications. Most UPS applications larger than
5000 VA use double conversion technology. This approach is
also the preferred technology for generator applications.

Equipment Notes:
Double-conversion UPS’s that are single phase or unfiltered
three phase models tend to create a significant level of 
electrical/ harmonic noise. This is illustrated by harmonic 
current distortions that are greater than 35%. When three
phase models are supplied with harmonic filters (current 
distortion less than 10%), this concern is no longer an issue.  

Generator Sizing Recommendation:
Single phase models:  limit the total UPS loading to 25% 
of the generator capacity. 

Three phase models without filters (current distortion > 30%):
limit the UPS loading to 35% of the generator capacity.

Three phase models with filters (current distortion < 10%):
limit the UPS loading to 80% of the generator capacity.

Supplier(s)

Passive (Standby)

Line-Interactive

Double-Conversion

APC

Back-UPS Series

Smart-UPS Series

Symmetra Series

Liebert

PowerSure PST and PSP

PowerSure PSA and PSI

UPStation and Nfinity Series

Powerware

3000 Series

5000 Series

9000 Series

Note: Ferrups and Delta-Conversion UPS technologies not included in discussion.

7

Содержание Standby Generators

Страница 1: ...Sizing Guide standby GENERATORS ...

Страница 2: ...trical load consult the manufacturer s nameplate on each major appliance or piece of equipment to determine its starting and running requirements in terms of watts amps and voltage When choosing the generator output for commercial or industrial applications select a rating that is approximately 25 higher than the peak load for example if the load is about 40 kilowatts select a 50 kW genset A highe...

Страница 3: ... 74 49 21 30 375 250 108 20 Ton 240 000 BTU 10 Hp x2 20 98 65 28 20 250 167 72 20 Ton 240 000 BTU 20 Hp 20 n a 65 28 40 500 333 144 25 Ton 300 000 BTU 25 25 n a 82 35 50 625 416 180 30 Ton 360 000 BTU 15 Hp x2 30 n a 98 42 30 375 250 108 30 Ton 360 000 BTU 30 Hp 30 n a 98 42 60 750 500 217 40 Ton 480 000 BTU 20 Hp x2 40 n a 131 57 40 500 333 144 40 Ton 480 000 BTU 40 Hp 40 n a 131 57 80 1000 666 2...

Страница 4: ...heat per 1000 ft 2 12 n a 50 Heat pump elements per 1000 ft 2 7 n a 29 Dryer 5 5 n a 23 Hot tub 5 n a 21 Range oven 5 n a 21 Hot water 4 5 n a 19 Stove top per burner 1 5 n a 6 General receptacles per 1000 ft 2 1 8 3 n a Lighting per 1000 ft 2 0 75 6 3 n a Blow dryer 1 25 10 4 n a Dishwasher 1 5 12 5 n a Microwave 1 8 3 n a Toasters 1 8 3 n a 3 ...

Страница 5: ...s Operating at 3600 RPM Rated Output Surge Capability Surge Capability Running Amps LR Amps at 15 Voltage Dip LR Amps at 30 Voltage Dip Size kW 240V 1ø 208V 3ø 480V 3ø 240V 1ø 208V 3ø 480V 3ø 240V 1ø 208V 3ø 480V 3ø 7 29 24 11 23 n a n a 46 n a n a 10 42 35 15 31 n a n a 63 n a n a 13 54 45 20 38 n a n a 75 n a n a 16 67 56 24 46 n a n a 92 n a n a 20 83 69 30 63 42 24 121 80 47 25 104 87 38 71 47...

Страница 6: ...460 130 50 215 150 30 150 LP vapor LPV Pipe Size in kW 0 75 1 1 25 1 5 2 2 5 3 7 165 570 10 70 255 1000 13 45 170 690 16 30 130 540 20 15 80 340 745 25 50 235 520 35 20 125 290 1030 45 82 195 725 60 45 115 445 1095 70 20 60 260 660 80 15 50 230 590 100 30 165 430 1305 130 70 205 660 150 45 150 490 Note Table values are maximum pipe run in feet Pipe sizing is based on 5 H2O pressure drop Sizing inc...

Страница 7: ... 500 300 119 37 46 40 792 540 20 528 360 0 264 180 850 510 165 41 50 40 1 217 700 20 811 800 0 405 900 1000 600 192 41 50 40 1 416 960 20 944 640 0 472 320 LP Vapor LPV Withdrawal Fuel Consumption Load kW BTU Hr Gal Hr 7 110 000 1 2 10 190 000 2 1 13 215 000 2 4 16 252 000 2 8 20 340 000 3 8 25 390 000 4 3 35 500 000 5 5 45 620 000 6 8 60 800 000 8 8 70 950 000 10 5 80 1 100 000 12 2 100 1 400 000...

Страница 8: ...a minimum of 2 hertz Generator Sizing Recommendation Limit the total UPS loading to 15 20 of the generator capacity Double Conversion This technology is most common for critical load applications Double conversion UPS s constantly rectify AC to DC and then invert the DC back into AC This configuration results in an output that corrects for voltage and frequency deviations There are single and thre...

Страница 9: ... with no listed HP calculate HP based on running amps in the chart on the right Recommended Generator Size ________ Refer to Generator Sizing Instructions on other side of this sheet INSTALL NOTES 1 Suggested concrete pad minimum thickness of 4 with 12 overhang on all sides Fiberglass pad included with air cooled products 2 Consult manual for installation recommendations 3 Consult local authority ...

Страница 10: ...e Table 1 for typical motor sizes and electrical requirements 2 Enter all non motor loads expected to run during peak load levels into Table 7 Reference Table 2 for typical residential loads and rules of thumb 3 Sum the running motor load data but do not include the largest motor that is cycling Add to this value the non motor load data and the starting kW for the largest cycling motor Motor runni...

Страница 11: ... with no listed HP calculate HP based on running amps in the chart on the right Recommended Generator Size ________ Refer to Generator Sizing Instructions on other side of this sheet INSTALL NOTES 1 Suggested concrete pad minimum thickness of 4 with 12 overhang on all sides Fiberglass pad included with air cooled products 2 Consult manual for installation recommendations 3 Consult local authority ...

Страница 12: ... Table 1 for typical motor sizes and electrical requirements 2 Enter all non motor loads expected to run during peak load levels into Table 7 Reference Table 2 for typical residential loads and rules of thumb 3 Sum the running motor load data but do not include the largest motor that is cycling Add to this value the non motor load data and the starting kW for the largest cycling motor Motor runnin...

Страница 13: ... with no listed HP calculate HP based on running amps in the chart on the right Recommended Generator Size ________ Refer to Generator Sizing Instructions on other side of this sheet INSTALL NOTES 1 Suggested concrete pad minimum thickness of 4 with 12 overhang on all sides Fiberglass pad included with air cooled products 2 Consult manual for installation recommendations 3 Consult local authority ...

Страница 14: ... Table 1 for typical motor sizes and electrical requirements 2 Enter all non motor loads expected to run during peak load levels into Table 7 Reference Table 2 for typical residential loads and rules of thumb 3 Sum the running motor load data but do not include the largest motor that is cycling Add to this value the non motor load data and the starting kW for the largest cycling motor Motor runnin...

Страница 15: ...Notes ...

Страница 16: ...siemens com generators RPSA GENSZ 0506 New 3M0506B A Printed in USA 2006 Siemens Energy Automation Inc All Rights Reserved Siemens is a registered trademark of Siemens AG Product names mentioned may be trademarks or registered trademarks of their respective companies Specifications are subject to change without notice ...

Отзывы: