Installation Instructions
Document No. 129-401
January 18, 2008
SQM5… Reversing Actuators, with Multiple Analog Control Input
Signals
Item Number 129-401, Rev. DA
Page 1 of 6
Product Description
Reversing actuator used to position flow control
valves, butterfly valves, dampers, or any application
requiring rotary motion with multiple analog input
signals.
Product Numbers
SQM5x.xxxRx
Z
x for 4 to 20 mA, 0 to 135 ohm and
0 to 10 Vdc input signals
Actuator Torque:
SQM50.2… 90 in/lb
SQM50.3… 90 in/lb
SQM50.4… 140 in/lb
SQM53.4… 200 in/lb
SQM56.5… 310 in/lb
SQM56.6… 400 in/lb
Max Shaft Torque:
AGA58.1 200 in/lb
AGA58.3 220 in/lb
AGA58.4 270 in/lb
AGA58.7 400 in/lb
SQM… motors allow torque on either end of the
AGA58.3 and AGA58.4 shafts.
NOTE:
For detailed information, see
Technical
Instructions
(155-517P25).
Caution Notations
CAUTION:
Equipment damage may occur
if you do not follow the
procedures as specified.
Installation
Cover Removal
Use a Phillips screwdriver to loosen the two screws
on the actuator cover corners. See Figure 1.
Lift the screws and raise the cover. See Figure 2.
EA0564R1
EA0568R1
Figure 1.
Figure 2.
Rotational Direction Verification
Actuator model numbers that end with “R” are
factory configured for clockwise (cw), minimum to
maximum rotation when facing the gear end of the
actuator, or counterclockwise (ccw) rotation when
facing the other end of the actuator. The gear end of
the actuator is the side opposite of the visual
position indicator.
Actuator Mounting
SQM5… actuators can be mounted in any
orientation. Optional base mounting brackets are
available.
SQM5… actuators can also be face mounted using
self-tapping screws in combination with the various
holes on the face of the actuator gear end.
Switch Adjustment
SQM5…actuators are factory-wired with Switch I
(maximum), Switch II (fully closed/economy position)
and Switch III (minimum/low-fire). The individual
switch cams I, II, and III are factory set to 90
°
, 0
°
and 10
°
, respectively. See Figures 3 and 4.