7/12
Building Technologies
Electromotoric Actuators
CA1N4505en
HVAC Products
26.10.2006
Technical data
SQL35.00
SQL85.00 SQL36E50
…
SQL36E65
SQL36E110 SQL36E160
Power supply
Operating voltage
AC 230 V
±
15 %
AC 24 V
±
20 %
AC 230 V
–
5 / +10 %
Frequency
50 / 60 Hz
Power consumption
1)
6.5 VA
35 VA
160 VA
235 VA
Control
Positioning signal
3-position
Parallel operation
parallel operation of several actuators not possible
Operating data
Positioning time for 90
°
at 50 Hz
at 60 Hz
125 s
105 s
25 s
20 s
6 s
2)
5 s
12 s
2)
10 s
24 s
2)
20 s
Angle of rotation
90
°
±
1
°
(factory setting)
Torque
1)
20 Nm
40 Nm
100 Nm
400 Nm
1200 Nm
End switch
Switching capacity
AC 250 V, 3 A resistive, 1.5 A inductive
Switching differential
approx. 1
°
Heating element
AC 230 V, 5 W
Medium temperature
Permissible temperature of medium in the assembled valve: 120
°
C
Standards
Meets the requirements for
CE marking in
EMC directive 89/336/EEC
Low-voltage directive 73/23/EEC
Electromagnetic
compatibility
AC emissions: EN 61000-3-ff, EN 55014-1 and EN 55022
AC + DC immunity: EN 61000-4-ff
Product standards for
automatic electrical controls
EN 60730-2-14
DIN EN 61010
C-tick
N474
Housing protection
standard
IP 44 to IEC 60529
IP 67 to IEC 60529
Protection class
III or II to EN 60730
EN ISO 5211
32mm
Flanges and shaft
connection to actuator
F04 / F05
F07
F10
F12 / F16
Dim ensions / weight
Dimensions
see
«
Dimensions
»
Cable glands
4 x
∅
20,5 mm (for M20)
2 x M20
Weight
1.4 kg
4.5 kg
7 kg
14 kg
25 kg
Materials
Housing base, yoke
die-cast aluminium
Cover
plastic
die-cast aluminium
1)
These values apply at nominal voltage, at an ambient temperature of 20
°
C and at the specified nominal
running time
2)
Variable positioning time with SEZ31.1 auxiliary module (see below)
Accessories for SQL35.00 / 85.00
Weight
•
Double auxiliary switch
ASC9.5 / ASC9.4
Switching capacity
Switching differential
AC 250 V, 10 A resistive, 3 A inductive
approx. 1
°
ASC9.4
85 g
ASC9.5
30 g
•
Auxiliary switch with
potentiometer ASZ7.4
Switching capacity
Switching differential
Change in resistance
AC 250 V, 10 A resistive, 3 A inductive
approx. 1
°
0 ...1000
Ω
corresponding to 0 ... 90
°
60 g
Accessories for SQL36E
…
Weight
•
Double auxiliary switch
ASC36
Switching capacity
Switching differential
AC 250 V, 3 A resistive, 1.5 A inductive
approx. 1
°
60 g
•
Potentiom eter ASZ36
Change in resistance
0...1000
Ω
corresponding to 0...90
°
50 g
•
Auxiliary module
SEZ31.1
Positioning time for 90
°
at 50 Hz
SQL36E65:
30...180 s
SQL36E110:
60
…
360 s
SQL36E160: 120
…
720 s
60 g
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.