Siemens Smart Infrastructure
74 319 0809 0
M4520
2022-06-15
7 / 12
Signal loss mode settings/
信号丢失模式设置
en
State
Position
Run to 0 %
(default)
Hold position Hold position
Run to 100 %
DIP 1
OFF
ON
OFF
ON
DIP 2
OFF
OFF
ON
ON
DIP 3
Reserve
DIP 4
Reserve
zh-cn
状态
位置
运行至
0 %
(默认)
保持位置
保持位置
运行至
100 %
DIP 1
关
开
关
开
DIP 2
关
关
开
开
DIP 3
备用
DIP 4
备用
Calibration/
校准
Calibration
LED D3
Actuator Movement
1. Supply power to
terminal 1 and 2.
Lit
Actuator moves to the position as indicated by control signal.
2. Press button S1 for
3 seconds
Dark
Actuator moves to “
100 %
” position (valve open).
Flash
once
Actuator stops at
“
100 %
” position (valve open)
, indicate light flashes,
and then the actuator is ready to move towards
“
0 %
”position (valve
closed).
Dark
Actuator moves to
“
0 %
”
position (valve closed).
Flash
Actuator stops
at “
0 %
” position (valve closed).
The indicate light
flashes, and then the calibration finished.
3. Calibration finished.
Lit
Actuator moves to the position as indicated by control signal.
校准
LED D3
执行器动作
1.
接通电源
.
长亮
执行器转动,控制信号指示
LED (D4)
闪烁。
2.
按住
S1
保持
3
秒
不亮
执行器转向
100 %
位置(阀门开)
闪一次
执行器在
100 %
的位置停止(阀门开),指示灯闪烁。然后执行器准备向
0 %
的
方向转动(阀门关)
不亮
执行器转动到
0 %
位置(阀门关)
闪烁
执行器在
0 %
位置停止(阀门关),指示灯闪烁。
3.
校准完成
长亮
执行器转动到位,控制信号指示灯长亮。