PROFIBUS Interface Center
SPC3
Page 18
V1.3
SPC3 Hardware Description
2003/04
Copyright (C) Siemens AG 2003. All rights reserved.
Bit 0
DIS_START_CONTROL
Monitoring the following start bit in UART. Set-Param Telegram overwrites this memory cell in
the DP mode. (Refer to the user-specific data.)
0 =
Monitoring the following start bit is enabled.
1 =
Monitoring the following start bit is switched off.
Bit 1
DIS_STOP_CONTROL
Stop bit monitoring in UART. Set-Param telegram overwrites this memory cell in the DP mode.
(Refer to the user-specific data.)
0 =
Stop bit monitoring is enabled.
1 =
Stop bit monitoring is switched off.
Bit 2
EN_FDL_DDB
Reserved
0 =
The FDL_DDB receive is disabled.
Bit 3
MinTSDR
Default setting for the MinTSDR after reset for DP operation or combi operation
0 =
Pure DP operation (default configuration!)
1 =
Combi operation
Bit 4
INT_POL
Polarity of the interrupt output
0 =
The interrupt output is low-active.
1 =
The interrupt output is high-active.
Bit 5
EARLY_RDY
Moved up ready signal
0 =
Ready is generated when the data are valid (read) or when the data are accepted
(write).
1 =
Ready is moved up by one clock pulse.
Bit 6
Sync_Supported
Sync_Mode support
0 =
Sync_Mode is not supported.
1 =
Sync_Mode is supported.
Bit 7
Freeze_Supported
Freeze_Mode support
0 =
Freeze_Mode is not supported.
1 =
Freeze_Mode is supported.
Bit 8
DP_MODE
DP_Mode enable
0 =
DP_Mode is disabled.
1 =
DP_Mode is enabled. SPC3 sets up all DP_SAPs.
Bit 9
EOI_Time base
Time base for the end of interrupt pulse
0 =
The interrupt inactive time is at least 1 usec long.
1 =
The interrupt inactive time is at least 1 ms long.
Bit 10
User_Time base
Time base for the cyclical User_Time_Clock-Interrupt
0 =
The User_Time_Clock-Interrupt occurs every 1 ms.
1 =
The User_Time_Clock-Interrupt occurs every 10 ms.
Bit 11
WD_Test
Test mode for the Watchdog-Timer, no function mode
0 =
The WD runs in the function mode.
1 =
Not permitted
Bit 12
Spec_Prm_Puf_Mode
Special parameter buffer
0 =
No special parameter buffer.
1 =
Special parameter buffer mode .Parameterization data will be stored directly in the
special parameter buffer.
Bit 13
Spec_Clear_Mode
Special Clear Mode (Fail Safe Mode)
0 =
No special clear mode.
1 =
Special clear mode. SPC3 will accept datea telegramms with data unit = 0.
Figure 5.1: Mode-Register 0 Bit 12 .. 0.(can be written to, can be changed in offline only)