Siemens SKP25 Series Скачать руководство пользователя страница 4

)

Technical Instructions 

SKP25

U.. Pressure Regulating Gas Valve Actuators 

Document Number 155-752 
July 9, 2014 
 

Page 4

 

Siemens Building Technologies, Inc. 

 

Operation 

(See Figure 1) 
 

Safety Shut-off Function 

The electro-hydraulic actuator consists of a cylinder filled with oil, a piston containing an 
electric oscillating pump, and a relief system. When power is supplied to the actuator, 
the relief system closes, and the pump moves oil from the reservoir into the pressure 
chamber. This action causes the piston to move downward in the cylinder, opening the 
gas valve. When power to the actuator is interrupted, the relief system opens and the 
gas valve closes in less than 0.8 seconds.  

A position indicator, visible through the transparent portion of the terminal cover, shows 
the entire stroke range of the actuator.  A light, which is visible through the lower left 
transparent portion of the terminal cover, indicates when the actuator receives power. 
An optional, non-adjustable SPDT proof of closure over travel switch signals the closed 
position after the gas valve has closed. An optional SPDT auxiliary switch is adjustable 
between 40% and 100% of the stroke. The adjustment screw and scale are located on 
the right side in the terminal box, and are visible through the transparent portion of the 
terminal cover. 

 

Figure 1. SKP25

 Operation. 

Regulating Function 

The outlet gas pressure sensing line is connected to the pressure regulator housing. 
The outlet pressure acts on the regulator diaphragm. The diaphragm is opposed by an 
adjustable setpoint spring force, which represents the desired gas pressure value. The 
movement of the diaphragm modulates a hydraulic bypass valve connecting the 
pressure chamber to the hydraulic fluid reservoir. When the outlet gas pressure is lower 
than the desired value, the bypass valve is closed by the movement of the diaphragm, 
causing the actuator piston to open the gas valve. The opposite occurs when the outlet 
gas pressure is higher than the desired value; the diaphragm moves to open the bypass 
causing the actuator piston to close the gas valve. The movement of the actuator piston 
stops once the outlet gas pressure is equal to the setpoint. In this position the bypass 
valve is partially open so that the oil flow supplied by the pump is identical to the return 
flow. Unlike the conventional direct acting regulators, the SKP25

 servo operated 

regulating system displays virtually zero droop (offset) across the turndown range. 

Содержание SKP25 Series

Страница 1: ...ed in combination with all VG series gas valve bodies from 1 2 inch to 6 inch in size The actuator is easily mounted on the square flange of any VG valve with four pre mounted screws A visible position indicator on the front of the actuator displays the entire stroke of the valve A light indicates when the actuator is powered Features UL listed FM approved CSA certified for USA and Canada and ISO ...

Страница 2: ...led Accessories Table 2 Product Number Description AGA22 Yellow setpoint spring for 6 to 48 WC 1 5 to 10 psi for SKP25 411U1 AGA23 Red setpoint spring for 40 to 100 WC 8 5 to 20 psi for SKP25 411U1 AGA25 2 Damping orifice for mounting into vent connection of SKP25 0 or SKP25 4 models AGA28 Black bias spring to install if SKP25 0 is used as proportionator or zero governor AGA29 Unpainted setpoint s...

Страница 3: ...m stroke Varies with valve size 14 seconds for max stroke Closing time 0 8 seconds Operation installation Outlet pressure spring range 0 to 8 5 WC standard unpainted spring AGA29 for SKP25 0 models 6 to 48 WC yellow spring AGA22 40 to 100 WC red spring AGA23 for SKP25 411U1 models 1 5 to 10 psi standard yellow spring AGA22 8 5 to 20 psi red spring AGA23 With air pressure loading for SKP25 4 0 6 WC...

Страница 4: ...0 and 100 of the stroke The adjustment screw and scale are located on the right side in the terminal box and are visible through the transparent portion of the terminal cover Figure 1 SKP25 Operation Regulating Function The outlet gas pressure sensing line is connected to the pressure regulator housing The outlet pressure acts on the regulator diaphragm The diaphragm is opposed by an adjustable se...

Страница 5: ...ns must be performed by qualified personnel only Do not pull the actuator shaft If minimum gas pressure detection is required the pressure switch must be mounted upstream of the regulating gas valve to ensure sufficient gas pressure before starting the burner If maximum gas pressure detection is required the pressure switch must be mounted downstream The AGA66 gasket must be installed between the ...

Страница 6: ... setpoint springs for an adjustable range of 1 5 to 20 psi The bias for the SKP25 611U1 model is adjustable from 0 to 4 0 WC See Specifications and Table 2 Clockwise rotation of the setpoint adjustment screw increases the outlet gas pressure The hexagonal cap must be tightened after the setpoint screw has been adjusted and may be sealed from tampering by means of a wire and lead seal WARNING When ...

Страница 7: ...U S A Your feedback is important to us If you have comments about this document please send them to techsupport SCCcombustion com Document No 155 752 Country of Origin US Page 7 Service Terminal Designations There are no serviceable parts on the SKP25 series actuators If inoperative replace the actuator Tag wires before servicing GAS0049R1 SKP25 012U SKP25 011U SKP25 013U Figure 2 Terminal Designa...

Отзывы: