U.. Pressure Regulating Gas Valve Actuators 

Technical Instructions 

 

Document Number 155-752 

 

July 9, 2014 

Siemens Building Technologies, Inc. 

Page 3

 

 

Specifications, 
Continued 

Physical characteristics 

Weight   

3.5 lb (1.6 kg) 

Enclosure 

NEMA 1, 2, 5 and 12 for indoor use 

 

NEMA 3, 3R, and 4 with optional AGA66 gasket 

 

 

Dimensions 

See Figure 3 

Specification for valve bodies 

See 

gas valve Technical Instructions,

 

 

 

 

P/N 155-512P25 

Connections 

Conduit connection 

Two 1/2-inch NPSM threaded knock-outs 

Electrical connection 

Spring loaded terminals for 14 AWG wires 

Gas connection 

1/4” NPT 

Air connection 

1/4” NPT  

Gas pressure test connection 

Hose barb with close-off screw 

Operating characteristics  Output force 

100 lb (450 N) 

Maximum stroke 

1 inch (26 mm) 

Opening time for maximum stroke 

Varies with valve size, 14 seconds for max. stroke 

Closing time 

< 0.8 seconds 

Operation/installation 

Outlet pressure spring range 

0" to 8.5" WC ( standard, unpainted spring, AGA29) 

for SKP25.0

 models 

6" to 48" WC (yellow spring, AGA22) 

 

40" to 100" WC (red spring, AGA23) 

for SKP25.411U1 models 

1.5 to 10 psi (standard, yellow spring, AGA22) 

 

8.5 to 20 psi (red spring, AGA23) 

With air pressure loading for SKP25.4

 

± 0.6" WC bias (black spring AGA28) 

  models or zero governor 

 

  or for SKP25.611U1 

0" to – 4" WC bias (white spring) 

Maximum sensing line pressure 

20 psi 

Maximum sensing line vacuum 

3 psi for SKP25.0

 models 

Minimum sensing line diameter 

1/4" inside diameter 

Minimum distance between 

 

sensing line and gas valve outlet 

5 times the pipe diameter 

Minimum time required for high to low fire  5 seconds 
load changes 

Auxiliary features 

Proof of closure switch 

Non-adjustable  

Setting range of auxiliary switch 

40% to 100% of stroke 

Switch rating 

6A/250 Vac resistive; 3A/120 Vac pilot duty 

 

Содержание SKP25 Series

Страница 1: ...ed in combination with all VG series gas valve bodies from 1 2 inch to 6 inch in size The actuator is easily mounted on the square flange of any VG valve with four pre mounted screws A visible position indicator on the front of the actuator displays the entire stroke of the valve A light indicates when the actuator is powered Features UL listed FM approved CSA certified for USA and Canada and ISO ...

Страница 2: ...led Accessories Table 2 Product Number Description AGA22 Yellow setpoint spring for 6 to 48 WC 1 5 to 10 psi for SKP25 411U1 AGA23 Red setpoint spring for 40 to 100 WC 8 5 to 20 psi for SKP25 411U1 AGA25 2 Damping orifice for mounting into vent connection of SKP25 0 or SKP25 4 models AGA28 Black bias spring to install if SKP25 0 is used as proportionator or zero governor AGA29 Unpainted setpoint s...

Страница 3: ...m stroke Varies with valve size 14 seconds for max stroke Closing time 0 8 seconds Operation installation Outlet pressure spring range 0 to 8 5 WC standard unpainted spring AGA29 for SKP25 0 models 6 to 48 WC yellow spring AGA22 40 to 100 WC red spring AGA23 for SKP25 411U1 models 1 5 to 10 psi standard yellow spring AGA22 8 5 to 20 psi red spring AGA23 With air pressure loading for SKP25 4 0 6 WC...

Страница 4: ...0 and 100 of the stroke The adjustment screw and scale are located on the right side in the terminal box and are visible through the transparent portion of the terminal cover Figure 1 SKP25 Operation Regulating Function The outlet gas pressure sensing line is connected to the pressure regulator housing The outlet pressure acts on the regulator diaphragm The diaphragm is opposed by an adjustable se...

Страница 5: ...ns must be performed by qualified personnel only Do not pull the actuator shaft If minimum gas pressure detection is required the pressure switch must be mounted upstream of the regulating gas valve to ensure sufficient gas pressure before starting the burner If maximum gas pressure detection is required the pressure switch must be mounted downstream The AGA66 gasket must be installed between the ...

Страница 6: ... setpoint springs for an adjustable range of 1 5 to 20 psi The bias for the SKP25 611U1 model is adjustable from 0 to 4 0 WC See Specifications and Table 2 Clockwise rotation of the setpoint adjustment screw increases the outlet gas pressure The hexagonal cap must be tightened after the setpoint screw has been adjusted and may be sealed from tampering by means of a wire and lead seal WARNING When ...

Страница 7: ...U S A Your feedback is important to us If you have comments about this document please send them to techsupport SCCcombustion com Document No 155 752 Country of Origin US Page 7 Service Terminal Designations There are no serviceable parts on the SKP25 series actuators If inoperative replace the actuator Tag wires before servicing GAS0049R1 SKP25 012U SKP25 011U SKP25 013U Figure 2 Terminal Designa...