5.2 In-line switch-disconnectors
SASIL plus with fuses
Cubicles with pluggable in-line switch-disconnectors can
also be equipped with SASIL plus in-line units (Fig. 5/3)
produced by Jean Müller.
Rating data of the vertical distribution busbar SASIL
plus
The vertical distribution busbars with the phase conductors
L1, L2, L3 are arranged at the back of the cubicle. The PE, N
or PEN busbars are arranged in the cable connection com-
partment. In the case of 4-pole feeders, the N conductor is
allocated to the phase conductors L1, L2, L3 at the back of
the cubicle. The vertical distribution busbar is covered test
finger proofed (IP2X). The rated data are stated in Tab. 5/8.
Rating data of the SASIL plus cable feeders
Apart from the space requirements for additional built-in
elements (Tab. 5/9), the derating factor stated in Tab. 5/10
is to be set for determining the permissible operating
current of a fuse link. The space requirements for the cable
feeders of the different in-line units depend on the nominal
device current (Tab. 5/11).
Distribution busbar cross section
60 x 10 mm
2
80 x 10 mm
2
Rated current at 35 °C ambient
temperature
1,560 A
2,100 A
Rated short-time withstand
current
I
cw
(1 sec)
1)
50 kA
50 kA
1)
Rated conditional short-circuit current
I
cc
= 100 kA
Tab. 5/8:
Rating data of the vertical distribution busbar SASIL plus
Fig. 5/3:
Pluggable in-line switch-disconnectors SASIL plus
Built-in elements
Height in mm
Version
Blanking cover for
empty slots
50, 75, 150,
300
Metal
Device compartment
(mounting
plate with
compartment door)
150, 200, 300,
450, 600
Without power tapping,
usable overall device
depth 180 mm
200, 300, 450,
600
With power tapping,
usable overall device
depth 180 mm
Tab. 5/9:
Additional built-in elements for SASIL plus
Tab. 5/10:
Derating factors for SASIL plus fuse links
Size
Nominal device
current
Space requirements of the in-line unit (height)
1)
Rated current
1)
at 35 °C ambient temperature
3-pole
4-pole
00
160 A
50 mm
100 mm
122 A
1
250 A
75 mm
150 mm
203 A
2
400 A
150 mm
300 mm
324 A
3
630 A
150 mm
300 mm
510 A
1)
Rated current with fuse link = nominal device current
The configuration rules stated in the following are to be observed
Tab. 5/11:
Rating data of the SASIL plus cable feeders
Nominal current of fuse link
Derating factor
F
I
n
≤ 32 A
1
32 A <
I
n
≤ 160 A
0.76
160 A <
I
n
≤ 630 A
0.81
Содержание Sivacon S8
Страница 1: ...Totally Integrated Power www siemens com sivacon s8 SIVACON S8 Technical Planning Information 10 2015 ...
Страница 2: ......
Страница 6: ...Chapter 1 System based power distribution ...
Страница 23: ...20 SIVACON S8 Planning Principles SIVACON S8 System overview ...
Страница 35: ...32 SIVACON S8 Planning Principles Circuit breaker design ...
Страница 93: ...90 SIVACON S8 Planning Principles Conforming to standards and design verified ...