99
SIVACON S8 Planning Principles –
Technical annex
2
3
4
5
6
7
8
9
10
11
1
Standard power
P
Motor current
I
(guide value)
at 400 V
at 500 V
at 690 V
0.06 kW
0.20 A
0.16 A
0.12 A
0.09 kW
0.30 A
0.24 A
0.17 A
0.12 kW
0.44 A
0.32 A
0.23 A
0.18 kW
0.60 A
0.48 A
0.35 A
0.25 kW
0.85 A
0.68 A
0.49 A
0.37 kW
1.1 A
0.88 A
0.64 A
0.55 kW
1.5 A
1.2 A
0.87 A
0.75 kW
1.9 A
1.5 A
1.1 A
1.1 kW
2.7 A
2.2 A
1.6 A
1.5 kW
3.6 A
2.9 A
2.1 A
2.2 kW
4.9 A
3.9 A
2.8 A
3 kW
6.5 A
5.2 A
3.8 A
4 kW
8.5 A
6.8 A
4.9 A
5.5 kW
11.5 A
9.2 A
6.7 A
7.5 kW
15.5 A
12.4 A
8.9 A
11 kW
22 A
17.6 A
12.8 A
15 kW
29 A
23 A
17 A
18.5 kW
35 A
28 A
21 A
22 kW
41 A
33 A
24 A
30 kW
55 A
44 A
32 A
37 kW
66 A
53 A
39 A
45 kW
80 A
64 A
47 A
55 kW
97 A
78 A
57 A
75 kW
132 A
106 A
77 A
90 kW
160 A
128 A
93 A
110 kW
195 A
156 A
113 A
132 kW
230 A
184 A
134 A
160 kW
280 A
224 A
162 A
200 kW
350 A
280 A
203 A
250 kW
430 A
344 A
250 A
Tab. 10/5:
Guide values for the operating currents of three-phase
asynchronous motors (AC-2/AC-3) in accordance with IEC 60947-4-1
10.5 Operating currents of three-
phase asynchronous motors
To enable the conversion of motor power values, Tab. 10/5
specifies guide values for the motor current present with
different voltages.
Содержание Sivacon S8
Страница 1: ...Totally Integrated Power www siemens com sivacon s8 SIVACON S8 Technical Planning Information 10 2015 ...
Страница 2: ......
Страница 6: ...Chapter 1 System based power distribution ...
Страница 23: ...20 SIVACON S8 Planning Principles SIVACON S8 System overview ...
Страница 35: ...32 SIVACON S8 Planning Principles Circuit breaker design ...
Страница 93: ...90 SIVACON S8 Planning Principles Conforming to standards and design verified ...