3. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) of insulation from the ends of the individual wires
4. Insert the cable into the sensor through the cable entry
5. Open the terminals with a screwdriver
6. Insert the wire ends into the open terminals according to the wir-
ing plan
7. Tighten the terminals with a screwdriver
8. Check the hold of the wires in the terminals by lightly pulling on
them
9. Tighten the compression nut of the cable entry gland. The seal
ring must completely encircle the cable
10. Screw the housing lid back on
The electrical connection is finished.
5.3 Wiring plan, single chamber housing
The following illustrations apply to the non-Ex as well as to the Ex-d
version.
3
5
1
2
4
SW E60T
10-55V DC
1
PNP
2 3 4
1
NPN
2 3 4
A
B
0,5 g / cm3
0,7 g / cm3
max 400mA
out
1 2 3 4
+
+
+
Fig. 8: Electronics and terminal compartment, single chamber housing
1 Control lamp
2 DIL switch for mode adjustment
3 DIL switch for switching point adaptation
4 Ground terminal
5 Connection terminals
We recommend connecting SITRANS LVL200S in such a way that
the switching circuit is open when there is a level signal, line break or
failure (safe state).
The instrument is used to control relays, contactors, magnet valves,
warning lights, horns as well as PLC inputs.
Electronics and terminal
compartment
Wiring plan
Siemens Controls
Содержание SITRANS LVL200S
Страница 1: ...Operating Instructions 11 2016 Vibrating Switches SITRANS LVL200S TRANSISTOR NPN PNP Siemens Control ...
Страница 2: ...2 7ML19985KS01 SITRANS LVL200S Operating Instructions 33837 EN 161128 ...
Страница 35: ...Notes 35 7ML19985KS01 SITRANS LVL200S Operating Instructions 33837 EN 161128 Siemens Control ...