ABB Total Flow
Wiring plan
+
+
power supply
MODBUS
D0
D1
IS GND
USB
1
2
13
45
2o
ff
on
( )
()
(-)
(-)
8
1
2
6
7
Bus +
Bus -
GND
VBAT
Fig. 54: Connection of SITRANS LG270 to RTU ABB Total Flow
1 SITRANS LG270
2 RTU ABB Total Flow
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
16 Bit Modicon
Input Register Base Number
1
The basic number of the input registers is always added to the input register address of SITRANS
LG270.
Address 1303 must hence be entered as register address for 1302 for RTU ABB Total Flow.