SITRANS LG270 - Operating Instructions
44295-EN-140321
Fault description
Error pattern
Cause
Rectification
4. Measured value re-
mains momentarily
unchanged during fill
-
ing and then jumps to
the correct level
Level
time
0
– Turbulence on the product
surface, quick filling
– Check parameters, change if
necessary, e.g. in dosing ves-
sel, reactor
5. Measured value
jumps sporadically to
100 % during filling
Level
time
0
– Changing condensation or
contamination on the probe
– Carry out a false signal sup-
pression
6. Measured value
jumps to ≥ 100 % or
0 m distance
Leve
l
time
0
– Level echo is no longer
detected in the close range
due to false signals in the close
range. The sensor goes into
overfill protection mode. The
max. level (0 m distance) as
well as the status message
"Overfill protection" are output
-
ted.
– Eliminate false signals in the
close range
– Check installation conditions
–
If possible, switch off the func
-
tion "Overfill protection"
Measurement error during emptying
Fault description
Error pattern
Cause
Rectification
7. Measured value re-
mains unchanged in
the close range during
emptying
Level
time
0
– False echo larger than the level
echo
– Level echo too small
– Eliminate false signals in the
close range
– Remove contamination on the
probe. After having removed
the source of the false signals,
the false signal suppression
must be deleted.
– Carry out a new false signal
suppression
8. Measured value re-
mains reproducible
in one position during
emptying
Level
time
0
– Stored false signals in this
position are larger than the
level echo
– Delete false signal memory
– Carry out a new false signal
suppression
Depending on the reason for the fault and the measures taken, the
steps described in chapter "
Setup
" must be carried out again or must
be checked for plausibility and completeness.
8.5
Exchanging the electronics module
If the electronics module is defective, it can be replaced by the user.
In Ex applications, only instruments and electronics modules with ap-
propriate Ex approval may be used.
If there is no electronics module available on site, the electronics
module can be ordered through the agency serving you. The electron-
ics modules are adapted to the respective sensor and differ in signal
output or voltage supply.
The new electronics module must be loaded with the default settings
of the sensor. These are the options:
Reaction after fault recti-
fication