9
SFIDK.PS.028.Q1.02
3. Electrical connection
Turn off the power supply before connecting input and output cables and wait 30
minutes before unscrewing the lid.
3.1 Electrical connection
compact or remote
Mounting and connection
View A
EEx e
1.
M20 black ATEX approved gland, power supply cable "e".
2.
Earthing terminal connected to potential equalisation rails (PEC).
3.
M20, blue ATEX approved gland, input and output cable "ia".
4.
Multi-plug connection to sensor EEx ia.
5.-6.
The power supply and input and output cables must be secured by i.e. cable strap so that
they remain in position even if the cable terminal screws get loose.
7.
Power supply terminals, EEx e maximal core cable 1.5 mm
2
.
Tighten the screws with 0.5 – 0.6 Nm!
Mount the plastic cover, marked "Increased safety" again.
8.
Input and output terminals EEx ia.
It is an absolute requirement that the wires/terminals of the intrinsically safe circuits
cannot
get
into contact with the wires of the other cables. The distance between cables/wires therefore must
be at least 50 mm.
It is recommended to fasten the cables/wires in a way that they, even in case of an error,
cannot
get into contact with each other. Make the wire ends as short as possible.
Intrinsically safe terminals "ia"!