Operation
6.6 Examples
SITRANS DA400 for material flow monitoring with protection against explosion
Operating Instructions, 09/2007, A5E00841152-01
57
●
Save alarm.
●
Not report pre-alarm.
●
Report main alarm with digital output 1.
Procedure
1.
Connect the acoustic emission sensor, as described in the "Connecting acoustic emission
sensors" section.
2.
Press the <PAR> button for five seconds to switch to the parameter menu.
3.
Using the and buttons, set parameter "P. 1".
4.
Using the and buttons, set the parameter value "on H".
5.
Using the and buttons, set parameter "P. 5".
6.
Using the and buttons, set the parameter value "20". A pre-alarm is triggered from
20 dB.
7.
Using the and buttons, set parameter "P. 6".
8.
Using the and buttons, set the parameter value "40". A main alarm is triggered from
40 dB.
9.
Using the and buttons, set parameter "P. 13".
10.
Using the and buttons, set the parameter value "60". The alarm is triggered after 60
seconds.
11.
Using the and buttons, set parameter "P. 14".
12.
Using the and buttons, set the parameter value "St.Ac". Alarms are saved.
13.
Using the and buttons, set parameter "P. 15".
14.
Using the and buttons, set the parameter value "oFF". Pre-alarms are not reported.
15.
Using the and buttons, set parameter "P. 16".
16.
Using the and buttons, set the parameter value "doAL1". Main alarms are reported
with digital output 1.
See also
Connecting structure-borne sound sensors (Page 27)
Connecting signal inputs (Page 29)