Extended Temperature Version (ET)
①
Vsup: 20 to 30 V DC supply input
②
Vsens: Analog output 0.08 to 10 V DC nominal
③
shield--tied to Sensor casing
*Sensor range selection
high sensitivity range = red and orange to Vsup +
low sensitivity range = red to Vsup + and orange to Vsup -
Note
•
Connect shield to ground at one end only!
•
If Sensor mounting is grounded, leave cable shield disconnected
•
If Sensor mounting is not grounded, connect cable shield to ground
The longer the cable, the more susceptible it is to noise and earth loops. We recommended
using cable with heavy gauge conductors and good RF/electrical shielding (copper braid rather
than drain and foil). A proper junction box close to the sensor is an ideal location not only to
extend the cable, but to also to configure the wiring for high or low sensitivity range operation.
This table provides a guideline for suitable wire gauges where distances are considerable.
Maximum distance between Sensor and supply (24V or Control Unit)
wire size
distance
AWG
mm
mm
2
*
meters
feet
24
7 x 0.20
0.22
500
1600
22
7 x 0.25
0.35
800
2600
20
10 x 0.25
0.5
1200
3900
* nominal wire size
Содержание SITRANS AS100
Страница 6: ...Table of contents SITRANS AS100 4 Operating Instructions 06 2016 A5E31952194 AB ...
Страница 8: ...General Information SITRANS AS100 6 Operating Instructions 06 2016 A5E31952194 AB ...
Страница 16: ...Outline and Dimensions SITRANS AS100 14 Operating Instructions 06 2016 A5E31952194 AB ...
Страница 26: ...Interconnection SITRANS AS100 24 Operating Instructions 06 2016 A5E31952194 AB ...
Страница 32: ...Index SITRANS AS100 30 Operating Instructions 06 2016 A5E31952194 AB ...
Страница 33: ......