Mounting
SITRANS AS100
Operating Instructions, 06/2016, A5E31952194-AB
19
Figure 5-1
Cable Gland (optional for use with ATEX II 2GD version)
①
Rubber component
②
Foil Jacket
③
Sleeve
④
Cable with outer jacket
The ATEX II 2GD version is supplied with an approved cable gland. Installation of glands/
conduit must conform to local governing codes.
1.
Disassemble the cable gland and discard the plastic membrane inside.
2.
Route the cable into the M20 section of the gland and thread it onto the housing.
3.
Mark the cable 2” (50 mm) from the entry of the housing then remove the acoustic sensor
from the housing.
4.
Remove the outer jacket of the cable from the acoustic sensor to the mark on the cable.
5.
Reinstall the acoustic sensor into the housing and route the cable through the M20 section
and into the throat of the rubber component.
6.
Peel back the foil jacket (on the cable) over the tapered steel (connected to the rubber
component).
7.
Install the sleeve over the tapered steel part, and thread the remaining two parts of the gland
onto the cable.
8.
Tighten the assembly to ensure a seal of the gland over the cable with outer jacket.
Содержание SITRANS AS100
Страница 6: ...Table of contents SITRANS AS100 4 Operating Instructions 06 2016 A5E31952194 AB ...
Страница 8: ...General Information SITRANS AS100 6 Operating Instructions 06 2016 A5E31952194 AB ...
Страница 16: ...Outline and Dimensions SITRANS AS100 14 Operating Instructions 06 2016 A5E31952194 AB ...
Страница 26: ...Interconnection SITRANS AS100 24 Operating Instructions 06 2016 A5E31952194 AB ...
Страница 32: ...Index SITRANS AS100 30 Operating Instructions 06 2016 A5E31952194 AB ...
Страница 33: ......