Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
316
Manual, 09.2018, A5E36758446-5-76
7.8.6.3
ActualUpdateState
Display name
Data type
Definition
Description
UpdateProgress
UInt32
AnalogItemType
Firmware update progress
(0 - 100 %)
UpdateState
UInt32
AnalogItemType
Status or result of the ongoing or
completed firmware update:
0: Firmware is being updated
1: The file download was exited,
the system must be restarted to
initiate the internal update process.
2: The data format of the update
file was not accepted.
3: The update file is too big.
4: The update file does not match
this device.
5: The device is in the buffer mode,
and cannot be updated at the pre-
sent time.
7.8.6.4
Alarm
Display name
Data type
Definition
Description
Alarm_F_CommunicationToModule
Boolean
Sitop_8600_AlarmType
There is a communication error on
the internal communication bus to
the expansion modules. The out-
puts at the modules that cannot be
accessed are switched off.
Alarm_F_CommunicationToPrimary
Boolean
Sitop_8600_AlarmType
There is a communication error to
the primary supply unit. All outputs
are switched off.
Alarm_F_CommunicationToSystem
Boolean
Sitop_8600_AlarmType
The alarm signals that there is a
communication error between the
Profinet module and the main con-
troller.
Alarm_F_DeviceOvertemperature
Boolean
Sitop_8600_AlarmType
Overtemperature condition in a part
of the device. The temperature lies
above the safety threshold. The
device or the channel is shut down
Alarm_F_ExtensionModuleNotAvailable Boolean
Sitop_8600_AlarmType
The expansion module was not
able to be found. Error in the con-
figuration. The system responds
differently depending on the con-
figuration.
Alarm_F_General
Boolean
Sitop_8600_AlarmType
General critical error. All outputs
are switched off.
Alarm_F_IncompatibleModuleDetected
Boolean
Sitop_8600_AlarmType
Incompatible expansion module
detected.
Alarm_F_ModuleDefect
Boolean
Sitop_8600_AlarmType
Module failure
Содержание SITOP PSU8600
Страница 404: ...Technical data 9 9 Dimension drawings Power supply system SITOP PSU8600 404 Manual 09 2018 A5E36758446 5 76 ...
Страница 410: ...Safety approvals EMC 10 4 EMC Power supply system SITOP PSU8600 410 Manual 09 2018 A5E36758446 5 76 ...
Страница 418: ...Environment Power supply system SITOP PSU8600 418 Manual 09 2018 A5E36758446 5 76 ...