Technical data
6.1 Input
SITOP PSU400M
32
Manual, 05.2018, C98130-A7601-A1-5-7629
U
in
= 300 - 824 V DC: Rated power (480 W) and Extra Power (150 % for 5 s/min)
U
in
= 200 - 300 V DC: Operating range with current derating max. 10 A (2 min. max.)
U
in
= 824 - 860 V DC < 1 min permissible (1x in 1 min.)
U
in
= 860 - 900 V DC < 10 s permissible (1x in 10 min.)
In the operating range from 824 - 900 V DC, the complete output power (20 A) is available within the
specified times.
Between 824 and 860 V, the output voltage is continuously available, if a linear derating of 1 A per
10 V is taken into consideration.
U
in
> 900 V DC: The output voltage is shut down
U
in
> 975 V DC can damage the device
Figure 6-1
Derating input range for product version 1
U
in
= 400 - 824 V DC: Rated power (480 W) and Extra Power (150 % for 5 s/min)
U
in
= 300 - 400 V DC: Operating range with derating (20 A at max. 55°C, 16 A at max. 60°C)
U
in
= 824 - 860 V DC: Linear current derating von 1.4 A per 10 V DC
U
in
= 860 - 880 V DC: Max. 15 A
U
in
= 880 - 900 V DC: Max. 5 A
U
in
> 900 V DC: The output voltage is shut down
U
in
> 975 V DC can damage the device
Figure 6-2
Derating input range for product version 2
Содержание SITOP PSU400M
Страница 8: ...Safety instructions SITOP PSU400M 8 Manual 05 2018 C98130 A7601 A1 5 7629 ...
Страница 22: ...Mounting removal SITOP PSU400M 22 Manual 05 2018 C98130 A7601 A1 5 7629 Figure 3 1 Mounting removal ...
Страница 30: ...Installation 5 2 Output side connection SITOP PSU400M 30 Manual 05 2018 C98130 A7601 A1 5 7629 ...
Страница 44: ...Safety approvals EMC 7 4 EMC SITOP PSU400M 44 Manual 05 2018 C98130 A7601 A1 5 7629 ...
Страница 46: ...Ambient conditions SITOP PSU400M 46 Manual 05 2018 C98130 A7601 A1 5 7629 ...
Страница 56: ...Environment SITOP PSU400M 56 Manual 05 2018 C98130 A7601 A1 5 7629 ...