SITOP power supply 

  

SITOP PSU100C 

Operating Instructions

SITOP PSU100C 12 V/2 A 

6EP1321-5BA00 

SITOP PSU100C 12 V/6.5 A 

6EP1322-5BA10 

SITOP PSU100C 24 V/0.6 A 

6EP1331-5BA00 

SITOP PSU100C 24 V/1.3 A 

6EP1331-5BA10 

SITOP PSU100C 24 V/2.5 A 

6EP1332-5BA00 

SITOP PSU100C 24 V/3.7 A 

6EP1332-5BA20 

SITOP PSU100C 24 V/4 A 

6EP1332-5BA10 

  

06.2013 

C98130-A7599-A1-2-7629 

Overview 

 

 

Safety instructions 

 

1

 

Description, device design, 

dimension drawing 

 

2

 

Mounting/disassembly 

 

3

 

Mounting position, mounting 

clearances 

 

4

 

Installation 

 

5

 

Technical data 

 

6

 

Safety, approvals, EMC 

 

7

 

Ambient conditions 

 

8

 

Applications 

 

9

 

Environment 

 

10

 

Service & Support 

 

11

Содержание SITOP PSU100C 6EP1321-5BA00

Страница 1: ...1321 5BA00 SITOP PSU100C 12 V 6 5 A 6EP1322 5BA10 SITOP PSU100C 24 V 0 6 A 6EP1331 5BA00 SITOP PSU100C 24 V 1 3 A 6EP1331 5BA10 SITOP PSU100C 24 V 2 5 A 6EP1332 5BA00 SITOP PSU100C 24 V 3 7 A 6EP1332 5BA20 SITOP PSU100C 24 V 4 A 6EP1332 5BA10 06 2013 C98130 A7599 A1 2 7629 Overview Safety instructions 1 Description device design dimension drawing 2 Mounting disassembly 3 Mounting position mounting...

Страница 2: ...ated only by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Sieme...

Страница 3: ...l mounting footprint as a result of the low profile design Low energy usage as a result of the high efficiency over the complete load range Minimum energy losses for no load operation 0 75 W Can be snapped onto and removed from mounting rails without requiring any tools Connection using plug in terminals Wide operating temperature range from 20 C up to 70 C derating from 50 C 55 C International pa...

Страница 4: ... 12 V DC 6 5 A 6EP1322 5BA10 Input 100 230 V AC 120 230 V DC Output 24 V DC 0 6 A 6EP1331 5BA00 Input 100 230 V AC 120 230 V DC Output 24 V DC 1 3 A 6EP1331 5BA10 Input 100 230 V AC 120 230 V DC Output 24 V DC 2 5 A 6EP1332 5BA00 Input 100 230 V AC 120 230 V DC Output 24 V DC 3 7 A 6EP1332 5BA20 Input 100 230 V AC 120 230 V DC Output 24 V DC 4 A 6EP1332 5BA10 Accessories Type Order number Pluggabl...

Страница 5: ...and weight 14 3 Mounting disassembly 17 4 Mounting position mounting clearances 19 4 1 Standard mounting position 19 4 2 Other mounting positions 22 5 Installation 23 5 1 Line side connection 23 5 2 Output side connection 25 6 Technical data 27 6 1 Input 27 6 2 Output 29 6 3 Efficiency and power loss 32 6 4 Closed loop control 36 6 5 Protection and monitoring 37 6 6 MTBF 37 6 7 Mechanical system 3...

Страница 6: ...2 7629 8 Ambient conditions 45 9 Applications 47 9 1 Parallel connection to increase the power rating 47 9 2 Parallel connection for redundancy 49 9 3 Series connection for increased voltage 51 9 4 Protection against short time voltage dips 52 10 Environment 53 11 Service Support 55 ...

Страница 7: ...s physical injury as well as extensive property damage Only appropriately qualified personnel may work on or in the vicinity of this equipment Perfect safe and reliable operation of this equipment is dependent on proper transportation storage installation and mounting Before installation or maintenance work can begin the system s main switch must be switched off and measures taken to prevent it be...

Страница 8: ...Safety instructions SITOP PSU100C 8 Operating Instructions 06 2013 C98130 A7599 A1 2 7629 ...

Страница 9: ... is available at the output of the device not for the devices 6EP1331 5BA00 6EP1332 5BA20 The output of the device is isolated no load proof and short circuit proof The LED display indicates the operating status Line input pluggable screw terminal DC output pluggable screw terminal Indicator light output voltage OK Potentiometer 22 2 26 4 V 10 5 12 9 V Slider to manually release Lug for releasing ...

Страница 10: ... can be used to establish the connection to supply voltage The output terminals are used to connect to the loads to be supplied see also Section Installation Page 23 Connections and terminal designations line input L N PE One screw terminal each for 0 5 to 2 5 mm Output 1 screw terminal for 0 5 2 5 mm Output 2 screw terminals for 0 5 2 5 mm 1P 6 6 3 3 6 6 6 6 3 3 PD ෘ PP PP PP PP PP 1P 1P PP PP Fi...

Страница 11: ...6EP1332 5BA10 Type Factory setting Setting range 6EP1321 5BA00 12 V 2 A 6EP1322 5BA10 12 V 6 5 A 12 V 10 5 12 9 V 6EP1331 5BA10 24 V 1 3 A 6EP1332 5BA00 24 V 2 5 A 6EP1332 5BA10 24 V 4 A 24 V 22 2 26 4 V 6EP1331 5BA00 24 V 0 6 A 6EP1332 5BA20 24 V 3 7 A 24 V The following devices do not have a potentiometer 6EP1331 5BA00 and 6EP1332 5BA20 NOTICE Thermal overload possible When adjusting the output ...

Страница 12: ... 24 V 1 3 A 6EP1332 5BA00 24 V 2 5 A 6EP1332 5BA20 24 V 3 7 A 6EP1332 5BA10 24 V 4 A Operating display Green LED for output voltage OK Figure 2 4 Operating displays and signals example of 6EP1332 5BA10 Signaling 6EP1321 5BA00 12 V 2 A 6EP1322 5BA10 12 V 6 5 A 6EP1331 5BA00 24 V 0 6 A 6EP1331 5BA10 24 V 1 3 A 6EP1332 5BA00 24 V 2 5 A 6EP1332 5BA20 24 V 3 7 A 6EP1332 5BA10 24 V 4 A LED lights up gre...

Страница 13: ...rating Instructions 06 2013 C98130 A7599 A1 2 7629 13 2 5 Block diagram 7UDQVIRUPHU 3RZHU WUDQVLVWRUV 3 0 FRQWUROOHU 9ROWDJH FRQWUROOHU 8VHU QWHUIDFH QSXW WHUPLQDO QUXVK FXUUHQW OLPLWHU 5HFWLILHU LOWHU 6HFRQGDU UHFWLILHU 2XWSXW ILOWHU 2XWSXW WHUPLQDO 867 2 Figure 2 5 Block diagram ...

Страница 14: ...s and weight SITOP PSU100C 14 Operating Instructions 06 2013 C98130 A7599 A1 2 7629 2 6 Dimensions and weight 22 5 80 82 22 7 106 5 100 Figure 2 6 Dimension drawing 6EP1331 5BA00 30 82 22 7 106 5 100 80 Figure 2 7 Dimension drawing 6EP1331 5BA10 6EP1321 5BA00 ...

Страница 15: ...awing 2 6 Dimensions and weight SITOP PSU100C Operating Instructions 06 2013 C98130 A7599 A1 2 7629 15 80 45 22 7 82 100 106 5 Figure 2 8 Dimension drawing 6EP1332 5BA00 Figure 2 9 Dimension drawing 6EP1332 5BA20 6EP1332 5BA10 6EP1322 5BA10 ...

Страница 16: ...30 A7599 A1 2 7629 6EP1331 5BA00 24 V 0 6 A 6EP1321 5BA00 12 V 2 A 6EP1331 5BA10 24 V 1 3 A 6EP1332 5BA00 24 V 2 5 A 6EP1322 5BA10 12 V 6 5 A 6EP1332 5BA20 24 V 3 7 A 6EP1332 5BA10 24 V 4 A Dimensions W H D in mm 22 5 80 100 30 80 100 45 80 100 52 5 80 100 Weight Approx 0 12 kg Approx 0 17 kg Approx 0 22 kg Approx 0 32 kg ...

Страница 17: ...dard mounting rails according to EN 60715 35x7 5 15 Mounting To mount the device position it with the mounting rail guide at the upper edge of the standard mounting rail and press down to lock it into place If this is too difficult press slider or lug at the same time as described for Removing Removing To remove press slider by hand downwards or pull the lug using a screwdriver and withdraw the de...

Страница 18: ...perating Instructions 06 2013 C98130 A7599 A1 2 7629 WARNING Use in hazardous zones If the device is to be used in a hazardous zone Ex II 3G Ex nA IIC T4 Gc it must be installed in a distribution box with degree of protection IP54 or higher ...

Страница 19: ...vertically in such a way that the input terminals are at the bottom and the output terminals are at the top to ensure correct cooling A clearance of at least 50 mm must always be maintained above and below the device In the vicinity of cable ducts it is only permissible to reduce the clearance to a minimum of 25 mm see Figure 4 1 Mounting Page 19 Lateral clearances do not have to be maintained PLQ...

Страница 20: ...30 50 2 5 Figure 4 2 6EP1321 5BA00 Output current in the standard mounting position IN OUT SITOP PSU100C 2XWSXW FXUUHQW 7HPSHUDWXUH r 70 4 0 5 2 1 3 0 20 40 60 10 30 50 7 6 6 5 Figure 4 3 6EP1322 5BA10 Output current in the standard mounting position IN OUT SITOP PSU100C 2XWSXW FXUUHQW 7HPSHUDWXUH r 70 0 4 0 0 5 0 2 0 1 0 3 0 20 40 60 10 30 50 0 7 0 6 Figure 4 4 6EP1331 5BA00 Output current in the...

Страница 21: ...40 60 10 30 50 1 5 Figure 4 5 6EP1331 5BA10 Output current in the standard mounting position IN OUT SITOP PSU100C 2XWSXW FXUUHQW 7HPSHUDWXUH r 70 2 0 0 2 5 1 0 0 5 1 5 0 20 40 60 10 30 50 3 0 Figure 4 6 6EP1332 5BA00 Output current in the standard mounting position IN OUT SITOP PSU100C 2XWSXW FXUUHQW 7HPSHUDWXUH r 70 4 3 7 0 2 1 3 0 20 40 60 10 30 50 5 Figure 4 7 6EP1332 5BA20 Output current in th...

Страница 22: ...XWSXW FXUUHQW 7HPSHUDWXUH r 70 4 0 2 1 3 0 20 40 60 10 30 50 5 Figure 4 8 6EP1332 5BA10 Output current in the standard mounting position 2XWSXW FXUUHQW QVWDOODWLRQ DOWLWXGH P 100 60 110 80 70 90 1000 1000 3000 0 2000 4000 5000 6000 Figure 4 9 Mounting height derating For details see Section Ambient conditions Page 45 4 2 Other mounting positions Not permitted ...

Страница 23: ...ystem according to VDE 0100 T 300 IEC 364 3 with a rated voltage of 1 phase 100 230 VAC 50 60 Hz or to a power supply with 120 230 V DC Figure 5 1 Line connection example 6EP1332 5BA10 The line supply is connected using terminal L1 N and PE see Figure 5 1 Line connection example 6EP1332 5BA10 Page 23 and must be implemented according to IEC 60364 and EN 50178 A protective device miniature circuit ...

Страница 24: ...4 V 1 3 A Miniature circuit breaker IEC 898 Characteristic B from 16 A and higher or characteristic C from 10 A 6EP1332 5BA00 24 V 2 5 A Miniature circuit breaker IEC 898 Characteristic B from 16 A and higher or characteristic C from 10 A 6EP1332 5BA20 24 V 3 7 A Miniature circuit breaker IEC 898 Characteristic B from 16 A and higher or characteristic C from 10 A 6EP1332 5BA10 24 V 4 A Miniature c...

Страница 25: ...10 The output voltage is connected via the and terminals at the output of the power supply see Figure 5 2 Connecting the output voltage example 6EP1332 5BA10 Page 25 Make sure that the output cables are dimensioned correctly for the maximum output current rms value and fused accordingly Note If the safety concept of the plant or system specifies that the DC output circuit should be grounded PELV t...

Страница 26: ...Installation 5 2 Output side connection SITOP PSU100C 26 Operating Instructions 06 2013 C98130 A7599 A1 2 7629 ...

Страница 27: ...20 230 V Voltage range for DC 110 300 V Wide range input Yes Overvoltage strength 2 3 x Ue rated 1 3 ms Power failure buffering at Ia rated min 20 ms Power failure buffering at Ue 230 V Rated line frequency 50 60 Hz Line frequency range 47 63 Hz Input current at rated value of input voltage 100 V rated value 0 63 A 1 6 A 0 28 A 0 63 A Input current at rated value of input voltage 230 V 0 31 A 0 8 ...

Страница 28: ...ffering at Ia rated min 20 ms Power failure buffering at Ue 230 V Rated line frequency 50 60 Hz Line frequency range 47 63 Hz Input current at rated value of input voltage 100 V rated value 1 21 A 1 88 A 2 25 A Input current at rated value of input voltage 230 V 0 67 A 0 95 A 1 15 A Inrush current limiting 25 C max 31 A 30 A 34 A I t max 2 4 A s 3 A s 3 A s Integrated input fuse Internal Protectio...

Страница 29: ...tentiometer using a potentiometer Operating display LED green for output voltage OK Response when switching on off Overshoot of Ua approx 5 Overshoot of Ua approx 1 Overshoot of Ua approx 5 Overshoot of Ua approx 5 Starting delay max 0 6 s 1 s 1 s 0 6 s Voltage rise typ 10 ms 500 ms 25 ms 90 ms Rated current Ia rated 2 A 6 5 A 0 6 A 1 3 A Current range Remark 0 2 A 2 A to 55 C 1 1 A to 70 C 0 6 5 ...

Страница 30: ... Setting the output voltage using a potentiometer using a potentiometer Operating display LED green for output voltage OK Response when switching on off Overshoot of Ua approx 1 Overshoot of Ua approx 1 Starting delay max 0 7 s 1 5 s 1 5 ms Voltage rise typ 100 ms 500 ms 400 ms Rated current Ia rated 2 5 A 3 7 A 4 A Current range Remark 0 2 5 A 2 5 A to 50 C 0 75 A to 70 C 0 3 7 A 3 7 A to 50 C 1 ...

Страница 31: ...igure 6 2 Startup delay voltage rise 2XWSXW YROWDJH 9 2XWSXW FXUUHQW 0 2 0 4 0 6 0 1 0 3 0 5 0 7 0 10 0 12 5 5 2 5 7 5 15 8 0 12V 6 5A 12V 2A Figure 6 3 12 V output characteristic 2XWSXW YROWDJH 9 2XWSXW FXUUHQW 0 1 0 1 5 2 5 3 5 0 5 2 0 3 0 4 0 4 5 20 0 25 10 5 15 30 5 0 24V 0 6A 24V 1 3A 24V 2 5A 24V 4A 24V 3 7A Figure 6 4 24 V output characteristic ...

Страница 32: ...ted as long as the overload condition is present 6 3 Efficiency and power loss 6EP1321 5BA00 12 V 2 A 6EP1322 5BA10 12 V 6 5 A 6EP1331 5BA00 24 V 0 6 A 6EP1331 5BA10 24 V 1 3 A Efficiency at Ua rated Ia rated approx 82 86 82 86 Power loss at Ua rated Ia rated approx 5 8 W 12 5 W 2 6 W 4 5 W 6EP1332 5BA00 24 V 2 5 A 6EP1332 5BA20 24 V 3 7 A 6EP1332 5BA10 24 V 4 A Efficiency at Ua rated Ia rated app...

Страница 33: ...YROWDJH 9 ORDG ORDG ORDG 75 80 100 120 140 160 180 81 83 77 76 78 84 85 86 200 87 90 220 240 260 280 79 82 80 88 89 Figure 6 6 Efficiency for AC 6EP1322 5BA10 IILFLHQF QSXW YROWDJH 9 ORDG ORDG ORDG 70 80 100 120 140 160 180 76 78 72 71 73 79 80 81 200 82 85 220 240 260 280 74 77 75 83 84 Figure 6 7 Efficiency for AC 6EP1331 5BA00 ...

Страница 34: ...YROWDJH 9 ORDG ORDG ORDG 75 80 100 120 140 160 180 81 83 77 76 78 84 85 86 200 87 90 220 240 260 280 79 82 80 88 89 Figure 6 8 Efficiency for AC 6EP1331 5BA10 IILFLHQF QSXW YROWDJH 9 ORDG ORDG ORDG 75 80 100 120 140 160 180 81 83 77 76 78 84 85 86 200 87 90 220 240 260 280 79 82 80 88 89 Figure 6 9 Efficiency for AC 6EP1332 5BA00 ...

Страница 35: ...ROWDJH 9 ORDG ORDG ORDG 75 80 100 120 140 160 180 81 83 77 76 78 84 85 86 200 87 90 220 240 260 280 79 82 80 88 89 Figure 6 10 Efficiency for AC 6EP1332 5BA20 IILFLHQF QSXW YROWDJH 9 ORDG ORDG ORDG 75 80 100 120 140 160 180 81 83 77 76 78 84 85 86 200 87 90 220 240 260 280 79 82 80 88 89 Figure 6 11 Efficiency for AC 6EP1332 5BA10 ...

Страница 36: ...x 0 1 0 1 0 1 0 1 Dyn load compensation Ia 10 90 10 Ua typ 3 3 3 3 Load step compensation time 10 to 90 typ 4 ms 3 ms 3 ms 5 ms Load step compensation time 90 to 10 typ 3 ms 3 ms 3 ms 5 ms 6EP1332 5BA00 24 V 2 5 A 6EP1332 5BA20 24 V 3 7 A 6EP1332 5BA10 24 V 4 A Dyn line compensation Ue rated 15 max 0 1 0 1 0 1 Dyn load compensation Ia 10 90 10 Ua typ 3 3 3 Load step compensation time 10 to 90 typ ...

Страница 37: ...ction Yes according to EN 60950 1 Current limitation typ 3 A 4 A 4 8 A Property of the output short circuit proof Yes Short circuit protection Electronic trip automatic restart 6 6 MTBF 6EP1321 5BA00 12 V 2 A 6EP1322 5BA10 12 V 6 5 A 6EP1331 5BA00 24 V 0 6 A 6EP1331 5BA10 24 V 1 3 A 6EP1332 5BA00 24 V 2 5 A 6EP1332 5BA20 24 V 3 7 A 6EP1332 5BA10 24 V 4 A Mean Time Between Failures SN29500 500000 h...

Страница 38: ...rail mounting No Mounting Can be snapped onto standard EN 60715 35x7 5 15 mounting rails 6EP1332 5BA00 24 V 2 5 A 6EP1332 5BA20 24 V 3 7 A 6EP1332 5BA10 24 V 4 A Connection system Screw terminal Connections line supply L N PE removable screw terminal for each 1 x 0 5 2 5 mm Connections output 1 screw terminal for 0 5 2 5 mm 2 screw terminals for 0 5 2 5 mm Width of the housing 45 mm 52 5 mm 52 5 m...

Страница 39: ... be downloaded from the Internet 6EP1321 5BA00 http www automation siemens com bilddb index aspx objKey G_KT01_XX_00411 6EP1322 5BA10 http www automation siemens com bilddb index aspx objKey G_KT01_XX_00468 6EP1331 5BA00 http www automation siemens com bilddb index aspx objKey G_KT01_XX_00415 6EP1331 5BA10 http www automation siemens com bilddb index aspx objKey G_KT01_XX_00419 6EP1332 5BA00 http ...

Страница 40: ......

Страница 41: ...1 3 A 6EP1332 5BA00 24 V 2 5 A 6EP1332 5BA20 24 V 3 7 A 6EP1332 5BA10 24 V 4 A Primary secondary galvanic isolation Yes Galvanic isolation SELV output voltage Ua according to EN 60950 1 and EN 50178 Transformer according to EN 61558 2 16 Protection class Class I Degree of protection EN 60529 IP20 Leakage current typ 0 4 mA Leakage current max 3 5 mA Test voltage See Table 7 1 Test voltage Page 42 ...

Страница 42: ...Connect the input terminals with one another Connect the output terminals and PE together Test C Connect the output terminals with one another and measure with respect to PE Table 7 1 Test voltage Test time Prim sec A Prim PE B Sec PE C 60 s 4200 V DC 2200 V DC 700 V DC Type test 60 s 3000 VAC 1500 VAC 500 VAC 1 s 2200 V DC 2200 V DC 500 V DC Production test 1 s 1500 VAC 1500 VAC 350 VAC 1 s 2200 ...

Страница 43: ...X EX II 3G Ex nA IIC T4 cCSAus CSA C22 2 No 213 M1987 ANSI ISA 12 12 01 2007 Class I Div 2 Group ABCD T4 CB approval Yes Marine approval GL ABS Degree of protection EN 60529 IP20 6EP1332 5BA00 24 V 2 5 A 6EP1332 5BA20 24 V 3 7 A 6EP1332 5BA10 24 V 4 A CE marking Yes UL CSA approval Yes UL cUL CSA approval cULus Listed UL 508 CSA C22 2 No 107 1 File E197259 cCSAus CSA C22 2 No 60950 1 UL 60950 1 NE...

Страница 44: ...burst EN 61000 4 4 4 kV at line supply connections 2 kV at the DC output Surge voltages EN 61000 4 5 3 kV symmetrical at the line supply connections 6 kV symmetrical at the line supply connections 500 V symmetrical asymmetrical on DC output cables High frequency fields EN 61000 4 6 10 V 0 15 80 MHz Magnetic fields EN 61000 4 8 30 A m 50 Hz Voltage dips EN 61000 4 11 100 for 20 ms 60 for 200 ms 30 ...

Страница 45: ...perature change 20 70 C with natural convection from 55 C 3 Ia rated K Tested according to EN 60068 2 1 cold EN 60068 2 2 dry heat EN 60068 2 78 humid heat constant EN 60068 2 14 temperature change Transport and storage temperature 40 85 C Tests packed for shipping according to EN 60068 2 1 cold EN 60068 2 2 dry heat EN 60068 2 30 humid heat cyclic Humidity class Climate class 3K3 according to EN ...

Страница 46: ...according to EN 60068 2 42 Sulfur dioxide 10cm3 m3 4 days EN 60068 2 43 Hydrogen sulfide 1cm3 m3 4 days Atmospheric pressure Operation 1080 795 hPa 1000 2000 m For operation at altitudes of 2000 m up to 6000 m above sea level output must be derated by 7 5 1000 m or the ambient temperature must be reduced by 5 K 1000 m see Figure 4 9 Mounting height derating Page 22 Overvoltage category III up to 2...

Страница 47: ...nected and under no load conditions the voltage difference measured between the terminals that have not been connected together This voltage difference must not exceed 0 2 The cables connected to each power supply at terminals and must have identical lengths and the same cable cross sections or the same impedance up to a common external network junction terminal strip if possible The power supplie...

Страница 48: ...more than two power supplies When connecting more than two power supplies in parallel additional measures must be taken to prevent high reverse currents in the event of a secondary device fault For this purpose a suitable protective circuit e g decoupling diode or DC compatible miniature circuit breaker must be installed between each terminal of the power supply and the common connection point ...

Страница 49: ...upply If one of the power supplies fails then this is signaled using an LED on the redundancy module as well as an isolated relay contact When dimensioning the system it must be ensured that n 1 redundant connected power supplies can handle the total power requirement of the remaining n power supplies Note For a high reliability of the supply it is recommended that the redundant switched power sup...

Страница 50: ...ITOP PSU100C 50 Operating Instructions 06 2013 C98130 A7599 A1 2 7629 Figure 9 3 Parallel connection with redundancy module for NEC Class 2 You can find additional information at SITOP PSE202U manual http support automation siemens com WW view en 42248598 ...

Страница 51: ...r supply The terminal of the first power supply and the terminal of the second power supply are routed to the load Depending on the grounding point of the secondary output voltages voltages of 48 V 24 V or 48 V can be realized In the case of an asymmetric load distribution it is not possible to guarantee correct functionality WARNING SELV is not guaranteed in the case of a fault When connecting tw...

Страница 52: ...rating Instructions 06 2013 C98130 A7599 A1 2 7629 9 4 Protection against short time voltage dips During a drop in the primary side supply voltage SITOP PSU100C power supplies still maintain the output voltage over a short millisecond period see section Technical data Input Page 27 ...

Страница 53: ...7629 53 Environment 10 The device is in conformance with RoHS As a rule only non silicon precipitating materials are used Disposal guidelines Packaging and packaging aids can and should always be recycled The product itself may not be disposed of as domestic refuse ...

Страница 54: ...Environment SITOP PSU100C 54 Operating Instructions 06 2013 C98130 A7599 A1 2 7629 ...

Страница 55: ...r supplies is available in the Internet at the SITOP homepage SITOP http www siemens de sitop Information material SITOP information can be downloaded from the Internet Information and download center http www siemens de sitop infomaterial CAx data 2D 3D data and circuit diagram macros can be downloaded from the Internet Siemens image database http www siemens de sitop cax Request all CAx data via...