SITOP power flexi 

A5E38522987, 11.2016 

 

English

 

Signalling 

LED does not light up 

No supply voltage (e.g. upstream protection device has opened) or device is defective. 

LED lights up green 

The output voltage is within the tolerance. 

 

LED lights up red 

The device is working at the current limit (max. 10 A) or at the power output limit (max. 120 W). 

 

Connection and terminal assignment of X1  

(connected load: 0.5 to 2.5 mm

or 25 to 15 AWG)

 

Terminal 

Designation 

Function 

X1-1 

L1 

Input voltage AC 120/230 V 

X1-2 

 

X1-3 

PE 

Protective conductor 

X1-4 

AC 120V - 

Necessary jumper for the working range AC 85 to 132 V 

X1-5 

Jumper 

 

X1-6 

⊕ 

L+  

Output voltage 3 to 52  V, 

Max. output current 10 A (in the range 3 to 12 V), max. output power 120 W (in the range 12 to 52 V), 

see figure output characteristic  

X1-7 

⊖ 

M  

X1-8 

 

 

 

Output characteristic 

 

Connection and terminal assignment of X2  

(connected load: 0.14 to 1.5 mm

2

 or 25 to 15 AWG)

 

Terminal 

Designation 

Function 

X2-1 

 

(Jumper 1) 

┐ 

U

soll

 

If the jumper is fitted (as-delivered status), output voltage can be set by means of the potentiometer 

U

A

 

 

(front). If jumper not fitted, remote setting of the output voltage by means of the voltage signal at terminal X2-

2 (signal ground terminal X2-9); here, a voltage signal of 0 to 2.5 V

DC

 corresponds to an output voltage of 0 to 

52 V

DC

X2-2 

X2-3 

Sense + 

Sense cable  connection: enables compensation of voltage drops due to cable resistance. Maximum voltage 

correction 0.5 V per cable. More details see figure 2 sense connection (page 7). 

X2-4 

Sense − 

X2-5 

UH 

Terminal not assigned at the present time (without any function) 

X2-6 

Power Good  

Power-good signal: floating relay contact is closed if the output voltage is within the tolerance (closed-circuit-

current principle). For technical functioning see figure 1 timing-diagram (page 7) 

X2-7 

 

X2-8 

Reset 

Reset signal: Open-collector (30 V, 20 mA); is activated when the voltage at the input falls below the 

minimum voltage and is set at least 1 ms before breakdown  of the output voltage (signal ground terminal    X 

2-9). For technical functioning see figure1 timing diagram (page 7).

 

X2-9 

Ground 

Ground connection for signals at terminal X2-2, X2-8, X2-10 or X2-12. 

X2-10 

I

ist

 

Current monitor signal: 2.5 V typically correspond to an output current of 10 A +/- 5% in total current range 

(signal ground X2-9). 

X2-11 

 

(Jumper 2) 

┐ 

I

soll

 

If the jumper is fitted (as-delivered status), output voltage can be set by means of the potentiometer 

I

Amax

 

(front). If jumper is not fitted, remote setting of the current limit by means of voltage signal at terminal X2-12 

(signal ground X2-9); here, a voltage signal of 0.5 - 2.5 V

DC

  corresponds to a current limit of 2 to 10 A. 

X2-12 

 

 

 

 

0

10

20

30

40

50

60

0

2

4

6

8

10

12

Vo

lt

 

Ampere 

1 ) 

2 ) 

1)  Setting range output voltage 
2)     Setting range current limiting 

Содержание SITOP power flexi

Страница 1: ... Siemens AG 2016 1 8 SITOP power flexi A5E38522987 11 2016 SITOP power flexi 6EP1353 2BA00 Betriebsanleitung A5E38522987 Operating Instructions https support industry siemens com ...

Страница 2: ...mens Niederlassung bzw über die Homepage http www siemens de sitop Technische Änderungen jederzeit vorbehalten In Zweifelsfällen gilt der deutsche Text Note These operating instructions cannot claim to cover all details of the product nor to provide for every possible contingency to be met in connection with installation operation or maintenance For more information please contact your local Sieme...

Страница 3: ... bei Volllast und 230V 75 Einschaltstrombegrenzung 25 C serienmäßig bei 230V 32A 0 8A2 s Netzseitig empfohlener LS Schalter 6A Charakteristik C Eingangsstrom bei 120 230V 2 2 1 3A Leistungsaufnahme 138W Gewicht 0 75kg Ausgangsgrößen Ausgangsgleichspannung Auslieferzustand 24V 1 Nennspannung einstellbar mittels Schraubendreher an Potentiometer UA Gerätevorderseite Position siehe Seite2 im Bereich 3...

Страница 4: ... 0 52VDC X2 2 X2 3 Sense Senseleitungs Anschluss Ermöglicht die Kompensation von Spannungsabfällen infolge Leitungswiderständen Maximale Spannungsausregelung 0 5V je Leitung Weitere Hinweise siehe Abb 2 Sense Leitungs Anschluss Seite 7 X2 4 Sense X2 5 UH Klemme derzeit nicht belegt ohne Funktion X2 6 Power Good Power Good Signal Potentialfreier Relaiskontakt ist geschlossen wenn die Ausgangsspannu...

Страница 5: ...Limitation of inrush current 25 C standard at 230 V 32A 0 8A2 s Recommended circuit breaker on supply side 6A characteristic C Input current at 120 230 V 2 2 1 3A Power consumption 138 W Weight 0 75kg Output variables DC output voltage As delivered conditions 24 V 1 rated voltage adjustable by means of screwdriver at potentiometer UA front of device For position see page2 in the range 3 to 52 V Ri...

Страница 6: ...voltage of 0 to 52 VDC X2 2 X2 3 Sense Sense cable connection enables compensation of voltage drops due to cable resistance Maximum voltage correction 0 5 V per cable More details see figure 2 sense connection page 7 X2 4 Sense X2 5 UH Terminal not assigned at the present time without any function X2 6 Power Good Power good signal floating relay contact is closed if the output voltage is within th...

Страница 7: ...s Anschluss 1 max Spannungsausregelung 0 5V je Leitung d h der Lastleitungsquerschnitt ist so zu wählen das der Spannungsabfall bei Volllast je Leitung max 0 5V beträgt 2 bei Verwendung eines Schaltelements in der Lastleitung müssen Lastleitung und Sense Leitung gemeinsam weggeschaltet werden Note for connecting sense line 1 max voltage correction 0 5 V per load line so ensure that less than 0 5V ...

Страница 8: ...er flexi A5E38522987 11 2016 Siemens AG Österreich AT 1210 Vienna Austria All rights reserved Liefermöglichkeiten und technische Änderungen vorbehalten Availability and technical specifications subject to change without prior notice ...

Отзывы: