Technical data
12.1 Technical data (electrical/mechanical)
3TK2826 safety relay
58
Manual, 08/2007, GWA NEB 926 1579-02 DS 02
Type
3TK2826-. ...
Repeatability (only for devices with stop category 0/1)
≤ ±0.1% ±30ms
Max. permissible safety shutdown mat resistance/line
resistance
1000 Ω
Permissible ambient temperature Tu operation/stroage
–25 to +60 °C/–40 to +80 °C
1) You will find the order numbers for the device versions in the table: Order numbers for the device versions
Table 12-2 Mechanical data
Type
3TK2826-. ...
Degree of protection in accordance with EN 60529
IP20
Touch protection, DIN VDE 0106, Part 100
Safe against finger touch
Weight
0.35 kg
Permissible service position
Any
Shock resistance
Half sine wave 8g/10 ms
PFH
7.8 x 10
-9
SFF (%)
99,8%
T1
20 years
Rated operating currents I
e
in accordance with IEC 60 947-5-1
WARNING
Short circuit protection in accordance with IEC 60 947-5-1
The device must have an upstream fuse, 4 A gL/gG or 6 A quick-response, as short circuit
protection.
Table 12-3 Rated operating currents
Terminal(s)
Utilization category
Rated operating
voltage V
e
Rated operating
current I
e
13/14; 23/24; 33/34; 43/44
47/48; 57/58
DC-13/AC-15
24 V/230 V
4 A
31/32, 51/52; 61/62
DC-13/AC-15
24 V/230 V
2 A/3 A
64,74,84
-13 DC
24 V
0.5 A
63/64, 73/74
DC-13/AC-15
24 V/230 V
1 A/1 A
CAUTION
Maximum permitted aggregate current with simultaneous load of multiple contacts: 12 A.
Содержание Sirius 3TK2826
Страница 10: ...Product family 3 1 Order numbers 3TK2826 safety relay 10 Manual 08 2007 GWA NEB 926 1579 02 DS 02 ...
Страница 14: ...Functions 5 1 Functions 3TK2826 safety relay 14 Manual 08 2007 GWA NEB 926 1579 02 DS 02 ...
Страница 54: ...External circuitry 10 3 Output circuit 3TK2826 safety relay 54 Manual 08 2007 GWA NEB 926 1579 02 DS 02 ...
Страница 56: ...Commissioning 11 1 Commissioning 3TK2826 safety relay 56 Manual 08 2007 GWA NEB 926 1579 02 DS 02 ...
Страница 60: ...Technical data 12 2 Dimension drawings 3TK2826 safety relay 60 Manual 08 2007 GWA NEB 926 1579 02 DS 02 ...