Configuration / project engineering
9.4 Configuration (undelayed)
3TK2826 safety relay
34
Manual, 08/2007, GWA NEB 926 1579-02 DS 02
Setting the configuration
START
Configuration
OK?
Yes
No
LEDs of the incorrectly set
DIP switches flicker
Set the correct
configuration and hold down
SET/RESET for around 3 seconds.
No
Yes
Power supply
Deactivating
Set configuration with
DIP switches
Power supply
ON
All configuration LEDs on
for around 1 second (LED test)
All configuration LEDs off
for around 0.5 seconds
Configuration LEDs on
in accordance with set configuration
Confirmation: SET/RESET
Hold down the button for around 2 seconds
Configuration LEDs flash
in accordance with set configuration
Check the configuration
Configuration
OK?
Confirmation: SET/RESET
Hold down the button for around 1 second
Configuration LEDs off
for around 0.5 seconds
Configuration LEDs on in
accordance with configuration for
around 2 seconds Unit changes to
the protection mode
Figure 9-1
Setting the configuration
Содержание Sirius 3TK2826
Страница 10: ...Product family 3 1 Order numbers 3TK2826 safety relay 10 Manual 08 2007 GWA NEB 926 1579 02 DS 02 ...
Страница 14: ...Functions 5 1 Functions 3TK2826 safety relay 14 Manual 08 2007 GWA NEB 926 1579 02 DS 02 ...
Страница 54: ...External circuitry 10 3 Output circuit 3TK2826 safety relay 54 Manual 08 2007 GWA NEB 926 1579 02 DS 02 ...
Страница 56: ...Commissioning 11 1 Commissioning 3TK2826 safety relay 56 Manual 08 2007 GWA NEB 926 1579 02 DS 02 ...
Страница 60: ...Technical data 12 2 Dimension drawings 3TK2826 safety relay 60 Manual 08 2007 GWA NEB 926 1579 02 DS 02 ...