Technical data
9.6 Number of starting operations
SIRIUS 3RM1 motor starter
144
Manual, 06/2016, A5E0345285095020A/RS-AE/005
9.6
Number of starting operations
Permissible number of starting operations per hour 1/h
Parameter: on-load factor = 50 %
The number of starting operations 1/h is calculated for an effective motor current of 100 %,
and the motor starter's actual performance can be higher.
Motor starter
3RM1.07…
3RM1.02…
3RM1.01…
Unit
Max. rated operating current I
e
7 A
2 A
0.5 A
Motor
Starting current
Starting time
250 %
100 ms
1000
3300
3600
1/h
400 %
100 ms
1000
1000
1000
1/h
400 %
300 ms
400
400
400
1/h
400 %
500 ms
220
220
220
1/h
500 %
100 ms
750
750
750
1/h
500 %
300 ms
250
250
250
1/h
500 %
500 ms
150
150
150
1/h
600 %
100 ms
500
500
500
1/h
600 %
300 ms
150
150
150
1/h
600 %
500 ms
100
100
100
1/h
700 %
100 ms
360
360
360
1/h
700 %
300 ms
100
100
100
1/h
700 %
500 ms
60
60
60
1/h