Functions
2.2 Protection Data Interfaces and Protection Data Topology
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
81
Figure 2-13
Principle and preferred external button wiring for controlling in the "Log out device" mode
Bu1
Button „Log on device“
Bu2
Button „Log out device“
Figure 2-13 shows the preferred variant for changing the “Log out device” mode with the aid of two buttons.
The used binary inputs are to be used as NO contacts.
2.2.2.2
Differential Protection Test Mode
General
If the differential protection test mode (test mode in the following) is activated, the differential protection is
blocked in the entire system. Depending on the parameter settings, either the distance protection assumes the
entire protection function over all zones or the time overcurrent protection becomes effective as emergency
function.
In the local device, all currents from the other devices are set to zero. The local device only evaluates the locally
measured currents, interprets them as differential current but does not send them to the other devices. This
enables to measure the thresholds of the differential protection. Moreover, the test mode prevents the genera-
tion of an intertrip signal in the local device by tripping of the differential protection.
If the device is still connected to the local CT the measured current can lead to a trip of the device.
If the device was logged out of the line protection system before activating the test mode (see “Log out device”
mode), the differential protection remains effective in the other devices. The local device can now also be
tested.
The test mode can be activated/deactivated as follows:
• Using the integrated keypad: Menu Control/Taggings/Set: „Test mode“
• Via binary inputs (No. 3197
„>Test Diff. ON“
, No. 3198
„>Test Diff. OFF“
) if this was allocated
• In DIGSI with Control/Taggings: „Diff: Test mode“
The test mode status of another device of the line protection system is indicated on the local device with the
indication
„TestDiff.remote“
(No. 3192).
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...