Notes to SIPROTEC
®
objects
10
7VU68x Redundant T103 Bus mapping
C53000-L2540-C558-1
1.1
Annunciations
1.1.1
Error With A Summary Alarm
The "Error with a summary alarm" (Obj.- Adr. 140) is ON if at least one of the following
internal alarms assumes the value ON:
•
"Error 5V", “Error 0V”, “Error -5V”, “Failure Battery empty”, “Error Power Supply”
•
"Error I/O Board", “Error Board 1“, “Error Board 2“, "Error Board 3“, "Error Board 4“,
"Error Board 5“, “Error Board 6“, "Error Board 7“
•
“Error Offset”, “Calibration data fault”
1.1.2
Alarm Summary Event
The "Alarm summary event" (Obj.- Adr. 160) is indicated, if at least one of the following
internal alarms assumes the ON status:
•
"Failure Current Balance", "Failure Current Summation", "Voltage Balance"
•
“Failure Phase Sequence Current”, “Failure Phase Sequence Voltage”
1.1.3
Stop Data Transmission
The functionality "Stop data transmission" is not supported via IEC 60870-5-103 com-
munication. If "Stop data transmission" is active nevertheless data via IEC 60870-5-
103 will be transmitted furthermore.
Note
The description of the standard mappings contains the pre-allocation of the mapping
files at delivery or first assignment of a mapping in DIGSI
®
4 to the SIPROTEC
®
de-
vice.
Changes of the allocation and the scaling of the measured values are possible in ad-
aptation to the concrete installation environment (ref. to page 3).
Note
Depending on the device composition and the existing protection packages not all of
the indicated binary inputs or protection annunciations (and corresponding IEC
60870-5-103 Information numbers) may be available in the SIPROTEC
®
device
Содержание SIPROTEC T103
Страница 6: ...6 7VU68x Redundant T103 Bus mapping C53000 L2540 C558 1 ...
Страница 36: ...36 7VU68x Bus mapping C53000 L2540 C558 1 ...
Страница 38: ...38 7VU68x Bus mapping C53000 L2540 C558 1 ...