Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
286
3.1.2.5
Reassembly
The device is assembled in the following steps:
• Insert the modules carefully in the housing. The mounting locations are shown in figure 3-3. For the model
of the device designed for surface mounting, use the metal lever to insert the C-CPU-2 board. The installa-
tion is easier with the lever.
• First insert the plug connectors of the ribbon cable on the input/output boards C-I/O–11 and then on the pro-
cessor board C-CPU-2. Be careful not to bend any connector pins! Do not use force!
• Connect the plug connectors of the ribbon cable between the processor board C-CPU-2 and the front panel
to the front panel plug connector.
• Press plug connector interlocks together.
• Put on the front cover and screw it onto the housing.
• Put the covers back on.
• Re-fasten the interfaces on the rear of the device housing. This activity is not necessary if the device is de-
signed for surface mounting.
3.1.3
Mounting
3.1.3.1
Panel Flush Mounting
For 7SD610 (Picture 3-12) 4 covers and 4 holes exist.
• Remove the 4 covers at the corners of the front cover. Thus, 4 elongated holes are revealed in the mounting
bracket and can be accessed.
• Insert the device into the control panel section and tighten it with 4 screws. For dimensions refer to Section
• Replace the 4 covers.
• Connect a solid low-impedance protective earthing at the rear of the device with at least one M4 screw. The
cross-section of the earth wire must be equal to the cross-section of any other control conductor connected
to the device. The cross-section of the earth wire must be at least 2.5 mm
2
.
• Connections are realized via the plug terminals or screw terminals on the rear side of the device according
to the circuit diagram.
When using screwed connections with forked lugs or direct connection, before inserting wires the screws
must be tightened so that the screw heads are flush with the outer edge of the connection block.
A ring lug must be centred in the connection chamber, in such a way that the screw thread fits in the hole of
the lug.
The SIPROTEC 4 System Description has pertinent information regarding wire size, lugs, bending radii, etc.
Installation notes are also given in the brief reference booklet attached to the device.
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...