Figure 2-104
Logic diagram of reverse power protection
Setting Notes
General
The application of reverse power protection is only possible in 3-phase protected objects. It can only be
assigned to a side of the main protected object or another measuring location. Furthermore, it is a prerequisite
that the device is connected to a three-phase voltage transformer set.
The reverse power protection is only effective and accessible if address 150 was set to
REVERSE POWER
=
Enabled
during configuration of the protection function (Section
).
Under address 5001
REVERSE POWER
the reverse power protection can be switched
ON
or
OFF
. The option
Block relay
allows to operate the protection but the trip output relay is blocked.
Pickup Value
In case of a reverse power, the turbine set must be disconnected from the system as the turbine operation is
not permissible without a certain minimum steam throughout (cooling effect). In case of a gas turbine set, the
motor load can also become too heavy for the network.
In case of a turbine generator unit the level of the active power input is mainly determined by the friction
losses to be overcome and lies within the following ranges:
Steam turbines:
P
reverse
/S
N
≈ 1 % to 3 %
Gas turbines:
P
reverse
/S
N
≈ 3 % to 5 %
Diesel drives:
P
reverse
/S
N
> 5 %
It is recommended, however, to measure the reverse power of the turbine generator unit with the protection
yourself during primary test (section "Commissioning", "Verification of the Voltage Connections"). As setting
value, use approx. half the measured motoring power. The feature to correct angle faults of the current and
voltage transformers should be used especially for very large machines with a particularly low motoring
energy (see Sections
3.3.12 Checking the Voltage Connections and Polarity
2.12.2
Functions
2.12 Reverse Power Protection
SIPROTEC 4, 7UT6x, Manual
225
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...