Here you can insert new limit values via the Information Catalog which are subsequently linked to the meas-
ured value to be monitored using CFC.
This view also allows you to change the default settings of the limit values under Properties.
The settings for limit values must be in percent and usually refer to nominal values of the device.
For more details, see the SIPROTEC 4 System Description and the DIGSI CFC Manual.
Information List
No.
Information
Type of
Informa-
tion
Comments
-
I Admd>
LV
I A dmd>
-
I Bdmd>
LV
I B dmd>
-
I Cdmd>
LV
I C dmd>
-
I1dmd>
LV
I1dmd>
-
|Pdmd|>
LV
|Pdmd|>
-
|Qdmd|>
LV
|Qdmd|>
-
|Sdmd|>
LV
|Sdmd|>
-
|PF|<
LV
|Power Factor|<
273
SP. I A dmd>
OUT
Set Point Phase A dmd>
274
SP. I B dmd>
OUT
Set Point Phase B dmd>
275
SP. I C dmd>
OUT
Set Point Phase C dmd>
276
SP. I1dmd>
OUT
Set Point positive sequence I1dmd>
277
SP. |Pdmd|>
OUT
Set Point |Pdmd|>
278
SP. |Qdmd|>
OUT
Set Point |Qdmd|>
279
SP. |Sdmd|>
OUT
Set Point |Sdmd|>
285
SP. PF(55)alarm
OUT
Set Point 55 Power factor alarm
Energy
Metered values for real and reactive power are determined by the processor system in the background. They
can be called up at the front of the device, read out via the operating interface using a PC with DIGSI, or trans-
ferred to a central master station via the system interface.
Energy Metering
7SD80 integrates the calculated power as a function of time and then provides the results under Measured
Values. The components as listed in
can be read out. The signs of the operating values depend on
the setting at address 1107
P,Q VORZEICHEN
(see Section
2.17.3 Measurement During Operation
margin heading “Display of Measured Values”).
Take into consideration that 7SD80 is, above all, a protection device. The accuracy of the metered values
depends on the instrument transformers (normally protection core) and the device tolerances. The metering is
therefore not suited for tariff purposes.
The counters can be reset to zero or any initial value (see also SIPROTEC 4 System Description).
Table 2-13
Operational metered values
Measured Values
primary
W
p
+
Real power, output
kWh, MWh, GWh
W
p
–
Real power, input
kWh, MWh, GWh
W
q
+
Reactive power, output
kVARh, MVARh, GVARh
W
q
–
Reactive power, input
kVARh, MVARh, GVARh
2.17.8.2
2.17.9
2.17.9.1
Functions
2.17 Auxiliary Functions
SIPROTEC 4, 7SD80, Manual
191
E50417-G1100-C474-A2, Edition 02.2018
Содержание SIPROTEC 4 7SD80
Страница 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...