SIPLUS PSU (6DL3500-8BA)
SIPLUS PSU Power Supply Unit
A5E00854207E
21 of 30
Copyright (C) Siemens AG 2018
V 8.00 released
2018-05-03
7 Commissioning
7.1 Mounting into the instrumentation and control cabinet
The instructions of chapter 6 “Installation instruction” have to be observed!
Step 1:
Mount the lateral mounting brackets at the housing in the desired installation position.
Figure 14: Installation variant for wall mounting
Figure 15: Installation variant for 19” - mounting
For the horizontal mounting position of the case several positions can be chosen. For this fastening
holes are provided at the mounting brackets in a 18 mm pitch.
∂
For the installation in SPPA standard cabinets choose the foremost position (see figure 15).
∂
For mounting to rear assembly walls turn the mounting bracket around 180° (see figure 14).
For the horizontal mounting position choose the position with the longest distance to the rear
assembly wall in order to get an optimum heat dissipation via airflow at the heat sink.
For unearthed mounting please notice chapter 7.3 “Unearthed Mounting”